
5 of 11 ISSUED: 10-01-10 SHEET #: 095-9354-1
Installation to Solid Concrete or Cinder Block
NOTE: Wall arm assembly (A) must be mounted to
wall using inner mounting holes.
Make sure that wall arm assembly is level and use
wall plate as a template to mark four mounting holes.
Top mounting slot will be X" above the screen center
as shown in figure 1.1 and chart 1 on page 4. Drill four
5/16" (8 mm) dia. holes to a minimum depth of 2.5"
(64 mm). Insert anchors (E) in holes flush with wall as
shown. Place wall arm assembly over anchors and
secure with wood screws (D). Level, then tighten all
fasteners. Insert eight fastener caps (G) into mounting
holes.
NOTE: Be sure arrow of label is pointing up when
mounting wall arm assembly (A) to wall as shown in
figure 1.1.
SOLID CONCRETE
CINDER BLOCK
1
• When installing Peerless wall mounts on cinder block, verify that you have a minimum of 1-3/8" (35 mm) of actual
concrete thickness in the hole to be used for the concrete anchors. Do not drill into mortar joints! Be sure to mount
in a solid part of the block, generally 1" (25 mm) minimum from the side of the block. Cinder block must meet ASTM
C-90 specifications. It is suggested that a standard electric drill on slow setting is used to drill the hole instead of a
hammer drill to avoid breaking out the back of the hole when entering a void or cavity.
• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.
• Installer must verify that the supporting surface will safely support the combined load of the equipment and all at-
tached hardware and components.
WARNING
• Tighten screws so that wall plate is firmly attached,
but do not overtighten. Overtightening can damage
screws, greatly reducing their holding power.
• Never tighten in excess of 80 in. • lb (9 N.M.).
• Always attach concrete anchors directly to load-
bearing concrete.
• Never attach concrete anchors to concrete covered
with plaster, drywall, or other finishing material.
If mounting to concrete surfaces covered with a
finishing surface is unavoidable (not evaluated by
UL), the finishing surface must be counterbored
as shown below. Be sure concrete anchors do not
pull away from concrete when tightening screws. If
plaster/drywall is thicker than 5/8" (16 mm), custom
fasteners must be supplied by installer (not evaluated
by UL).
WARNING
CUTAWAY VIEW
INCORRECT CORRECT
wall
plate
wall
plate
plaster/
drywall
plaster/
drywall
concrete concrete
1
3
2
E
Drill holes and insert anchors (E).
Place plate (A) over anchors (E) and secure with screws (D).
Tighten all fasteners.
A
F
E
D
concrete
surface
A
G
D
E