
THERMAL MANAGEMENT SOLUTIONS EN-TraceTekTTDM128-IM-H5734103/13 4 / 6
Connect the alarm relays.
The TTDM-128 has three relays, for service ck, leak bt, and fault
bs. Each relay provides two Form-C relay contacts, and normally
open and normally closed contacts are both provided. The relays
are de-energized to indicate an alarm condition. The illustration
shows the relay status in the alarm (de-energized) state.
The illustrations that follow show how relays can be jumpered
together to allow remote monitoring of the TTDM-128 status with
only a single pair of wires. The TTDM-128 de-energizes its relays
to signal an alarm condition. Therefore, loss of power, as well as
any other type of alarm, would signal the remote alarm.
Note: Therelayplugscanacceptwires10AWG(4.7sq.mm)or
smaller.Werecommend18AWG(1.0sq.mm)wires.Cableshould
have a temperature rating of 65°C.
Note: Maximum load for relays is 5 A.
LEAK RELAYSERVICE RELAY FAULT RELAY
Monitoring circuit
(alarm on open circuit)
Relays wired
in series
Alarm on open circuit
Monitoring circuit
(alarm on closed circuit)
Relays wired
in parallel
Alarm on closed circuit
Test after supplying power.
•Closeandlatchtheenclosuredoor.
•Supplypowertotheunit.Whenpowerissupplied,thegreenLED
illuminates, and the unit goes through a series of self-tests. Af-
terthestart-upsequenceiscomplete,themoduleshouldreport
a fault alarm (this is normal; there is no sensing cable attached).
PresstheredSilencekeytosilencetheaudiblealarm.Verifythat
the display appears similar to the one shown here (the time and
date may be different):
If anything other than the above occurs, check all connections. If
unit still does not appear to operate properly, contact a TraceTek
representative for assistance.
•PresstheTestbutton.Themoduleconductsanumberofself-tests.
•Ifthetestsaresuccessfullycompleted,recordthisontheinstal-
lation record.
•Turnoffthepowersupplytotheunit.
Test with TTDM-128 test plug.
•Toconductamorecompletetest,usetheTraceTekTTDM-CTPtest
plug (packed in a plastic bag in the TTDM packaging). Insert the plug
into the sensing cable socket cn on the sensor interface board 9.
•Closeandlatchtheenclosuredoor.
•Supplypowertotheunit.Whenpowerissupplied,theunitwillagain
go through a series of self-tests. If the test plug is in the sensing cable
socket,afterthemodulecompletesthestart-upsequenceitshould
soundanddisplayaleakalarm.PresstheSilencekeytosilencethe
audible alarm. The red Leak LED and green Monitoring LED should
both be illuminated, and the screen display should appear similar to
the one shown here (depending on the setting).
•Ifanythingotherthantheaboveoccurs,checkallconnections.Ifunit
still does not appear to operate properly, contact a TraceTek represen-
tative for assistance.
•Ifthetestissuccessfullycompleted,recordthisontheinstallation
record.
•Turnoffthepowersupplytotheunit.
•RemovetheTTDM-CTPtestplugandstoreitinasecureplacefor
future use.
•Ifnotimmediatelyconnectingthesensingcable,orTraceTeknet-
work, close and latch the enclosure.
Depending on the units selected, the leak
distance should be within the values below:
feet: 527 to 548 ft
meters: 160 to 168
zones: 11
Testing the Module