manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pentair
  6. •
  7. Controllers
  8. •
  9. Pentair Pentek Intellidrive User manual

Pentair Pentek Intellidrive User manual

OWNER’S MANUAL
Should you the installer or owner be unfamiliar with the correct installation or operation
of this type of equipment you should contact the distributor/manufacturer for the correct
advice before proceeding with the installation or operation of this product.
Installation / Operation / Parts
PID_OM_2014.indd 1 24/02/2014 1:49:52 PM
Safety 2
Important Safety Instructions
Read the Owner’s Manual and related documentation
carefully before attempting to install or operate the
PENTEK INTELLIDRIVETM
. Make sure that you have a full
knowledge of the equipment, safety information, and
instructions before using this product.
Carefully read and follow all safety instructions in this
manual and on the VFD.
This is the safety-alert. When you see this symbol
on your VFD or in this manual, look for one of the
following signal words and be alert to the potential for
personal injury:
warns about hazards that will cause
serious personal injury, death or major property damage if
ignored.
warns about hazards that cancause
serious personal injury, death or major property damage if
ignored.
warns about hazards that will or can
cause minor personal injury or property damage if ignored.
The word NOTE indicates special instructions which are
important but not related to hazards.
To avoid serious or fatal personal injury and possible
property damage, carefully read and follow the safety
instructions.
Risk of high-voltage electrical shock
from the EMI/RFI Filter if the front cover of the VFD is
open or removed while power is connected to the VFD or
the VFD is running. The front cover of the VFD must be
closed during operation.
• After allowing at least 5 minutes for the EMI/RFI Filter
to discharge and before starting any wiring or
inspection procedures, check for residual voltage with
a voltage tester.
Risk of electrical shock if VFD is
connected to the power wiring before hanging the box.
Always hang the VFD box before connecting the wires to it.
Risk of electrical shock if the VFD is
handled or serviced with wet or damp hands. Always
make sure your hands are dry before working on the VFD.
Perform all operations on the HMI with dry hands.
Risk of electrical shock and hand
injury. Do not reach into or change the cooling fan while
power is on to the VFD.
Risk of electrical shock. Do not touch
the printed circuit board when power is on to the VFD.
Fire hazard if installed with incorrect or
inadequate circuit breaker protection. To make sure of
protection in the event of an internal fault in the VFD,
install the VFD on an independent branch circuit protected
by a circuit breaker (see Table 2, Page 6 for circuit breaker
sizing), with no other appliances on the circuit.
Risk of burns.The drive can become
hot during normal operation. Allow it to cool for 10
minutes after shut-down before handling it to avoid burns.
Risk of electric shock.A means for
disconnection from the supply mains, having a contact
separation in all poles, must be incorporated in the fixed
wiring in accordance with the wiring rules.
Complex equipment. This device is not
intended for use by persons (including children) having
reduced physical, sensory or mental capabilities, or lack of
experience and knowledge.
NOTE: This VFD is classified as Class A EMC/EMI
equipment. It is intended for use in an industrial
environment. There may be potential difficulties ensuring
electromagnetic compatibility in other environments due
to conducted as well as radiated disturbances.
NOTE: The device must be supplied through a Type A
Residual Current Device (RCD) having a rated residual
operating current not exceeding 30 mA.
NOTE: To avoid damage to the drive or problems with the drive:
• Connect the output cables to 3-wire submersible
motors as described in Output Connections, page 7.
Any other order will reverse the motor rotation and
may damage the motor.
• Do not modify the equipment.
• Do not use power factor correction capacitors with this
VFD; they will damage both the motor and the VFD.
• Do not remove any parts unless instructed to do so in
the owner’s manual.
• Do not use a magnetic contactor on the VFD for
frequent starting/stopping of the VFD.
• Do not install or operate the VFD if it is damaged or
parts are missing.
• Before starting a VFD that has been stored for a long
time, always inspect it and test operation.
• Do not carry out a megger (insulation resistance) test
on the control circuit of the VFD.
Risk of high-voltage electrical shock
from EMI/RFI Filter inside Drive.
Make all wiring connections, then
close and fasten the cover before
turning on power to Drive.
DO NOT open the box when power is
connected to the Drive.
Before doing any service
or maintenance inside
the Drive:
1. DISCONNECT power.
2. WAIT 5 minutes for
retained voltage to
discharge.
3. Open box.
Before connecting or
disconnecting any wires
inside the Drive:
1. DISCONNECT power.
2. WAIT 5 minutes for
retained voltage to
discharge.
3. Open box.
PID_OM_2014.indd 2 24/02/2014 1:49:52 PM
Table of Contents 3
Owner’s Information
PENTEK INTELLIDRIVE Model No. _________________________
PENTEK INTELLIDRIVE Serial No. _________________________
Pump Model No. _________________________
Pump Serial No. _________________________
Motor Model No. _________________________
Motor Service Factor Amps _________________________
Pressure Tank Model No. _________________________
Pressure Tank Serial No. _________________________
Dealer/Installer: __________________________________________
________________________________________________________
Installer Phone No. _________________________
Date of Installation _________________________
Wire Lengths in (Meters):
Circuit Breaker to Drive _________________________
PENTEK INTELLIDRIVE to Motor _________________________
Supply Voltage _________________________
Note to Installer: Record the data listed above for future reference. Give manual
to end user or attach to
PENTEK INTELLIDRIVE
when installation is
complete.
Fan
EMI/RFI Filter
6020 0609
Risk of electric shock.
Can shock, burn or kill.
• Drive’s internal
components retain
high voltage for up to
5minutes after input
power is disconnected.
• EMI/RFI Filter carries
high voltage when pump
is running.
• Disconnect power and
wait 5 minutes before
opening
PENTEK
INTELLIDRIVE
 cover.
Safety ................................................................ 2
Owner’s Information .................................................. 3
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Installation ......................................................... 6-9
Initial Startup ....................................................10-11
Programming ....................................................12-15
I/O Connections ..................................................16-17
Additional Information ...............................................18
Troubleshooting ..................................................19-21
EMC Installation ..................................................22-23
PID_OM_2014.indd 3 24/02/2014 1:49:52 PM
Description 4
Specifications/Ratings
Input Voltage .............1-Phase 230VAC Nominal (190–265VAC)
Input Frequency ........................................................... 50/60Hz
Ambient Temperate Range ................................. -20° to 50 °C
Output Connections ......................... 3-Phase, 3-wire, 220V,
.....................................................................3-Wire/1-Phase
..................................................................... 1-Phase/2-wire
Max Motor Cable Length...................................................305m
Enclosure .............................................................................. 3R
Table 1 - Specifications
Model Max
kW
Input
Phase
Motor
Operation
Max
Amps
PID20 1.5 12-wire, 3-wire &
3-phase 13.5
The PENTEK INTELLIDRIVE is specifically
designed to operate 4” submersible pumps and
3-phase, 220V above ground pumps in water well
and residential booster applications. Each Drive is
rated for maximum output amp rating. Any use of
Drive outside of intended design parameters will
void warranty. If Drive is used with above ground
motors not rated for a Variable Frequency Drive,
maximize motor life by limiting lead length to 8m.
Refer to pump Owners Manual and AS/NZS 3000
for proper wire size.
Each carton contains:
• PENTEK INTELLIDRIVE Variable Frequency Drive
• Pressure Transducer
• 3m Pressure Transducer Cable
• Quick Start Guide
• Owner’s Manual
Figure 1 - A typical residential installation layout
PID2000 - 1 1 2 3
Product Family
PID - PENTEK INTELLIDRIVE
Voltage Rating:
1 = 190-265 Volt 1 phase input
Output voltage:
1 = 230v 1 phase output
HP Rating: Motor
Type:
2 = 2.0 HP 3 = 3-wire
PID_OM_2014.indd 4 24/02/2014 1:49:53 PM
Description 5
Transducer
The PENTEK INTELLIDRIVE uses a 4-20mA, 0-668
kPa pressure transducer to control motor speed
(max is 2068 kPa transducer).
The transducer (see Figure 1) senses pressure
in the pipe and converts it to an electrical signal.
The Drive senses and processes the signal in the
PID (Proportional, Integration, Derivative) control.
When operating in AUTOSTART mode, the Drive
increases and decreases the speed of the pump
motor as needed to maintain constant pressure in
the piping system.
Keypad
The keypad programs the Drive, monitors the
status of the pump, and displays faults if they
occur. Each button has a unique function, as
described in Figure 2. The LCD display shows a
text display of the status of the Drive’s operation.
Other LEDs light up to indicate when certain
buttons are pressed or certain events occur.
Fan
The Drive uses a thermostatically controlled
internal fan which operates automatically when
necessary to cool the Drive components.
Figure 2 - PENTEK INTELLIDRIVE keypad functions
6007 0412
Stops the
motor.
Power is ON to Drive.
A fault has
occurred.
Selects menu items and confirms
numeric value changes.
Displays Drive’s current operating
condition and changes display
parameters.
Changes display to previous screen.
Drive is in Warning Mode (TPM); refer to
Troubleshooting section.
Changes internal pressure setpoint
from 103 kPa to transducer max
-20 kPa . ie 2047kPa
Runs the Drive at 45Hz (with no
pressure control) to allow installer to
pump out well.*
Up and down arrows scroll through
menus and change numeric values.
Toggles between English, Spanish, and
French (default is English).
Resets fault that stopped Drive/pump.
With code, locks and unlocks password
protected keys.
Left and right arrows move cursor.
Shows last 15 faults.
Checks for line fill, then starts pump
in constant pressure mode.
Views and changes
parameters.
PID_OM_2014.indd 5 24/02/2014 1:49:53 PM
Installation 6
Table 2 - Circuit breaker and wire sizes
Motor Drive
Model Volts Motor HP Wire Size* Circuit
Breaker**
Generator
(kVA)***
Input Output
2-wire PID20
230
1-1/2 2.5mm² 2.5mm² 25 (with RCD,
Ref page2
)5.3
3-wire PID20 1-1/2 2.5mm² 2.5mm² 25 (with RCD,
Ref page2
)
5.3
2 5.8
* Wiring size will change depending on the length of wire. See Table 3
** With properly-sized circuit breakers, the Drive is protected from short circuit on the input and the
output. There is no risk of fire or electrical shock due to a short circuit. The Drive has NEC Class 10
overload protection.
*** Minimum 240V generator size.
NOTICE Information in Table 3 applies ONLY to PENTEK® motors. For other motors, refer to motor
manufacturer specifications for wire sizing.
Table 3 - Wire Sizing, Drive to Pentek 3-Wire, 1-Phase Motor, 40°C Ambient, and 5 percent Voltage
Drop, 60C and 75C Insulation (copper only).
Motor P/N Motor Rating Maximum Cable Length in M
Volts HP SFA 1.5 mm² 2.5 mm² 4.0 mm² 6 mm² 10 mm² 16 mm²
G43A0010B2
230
1 6.4 64 117 188 280 305 -
G43A0015B2 1 1/2 9.4 43 80 128 190 305 -
G43A0020B2 2 12.4 33 60 95 140 240 305
PID_OM_2014.indd 6 24/02/2014 1:49:53 PM
Installation 7
Mounting the Drive
To mount the Drive as shown in Figure 6, follow
this procedure:
1. First, remove the cover by backing out screw
at bottom of front cover.
2. Push on backplate with thumbs while pulling
the cover toward you with index fingers,
creating a gap. See Figures 3 and 4.
3. Pull bottom of cover towards you; lift up on
cover and remove. See Figure 5.
4. With the cover removed, permanently
mount the Drive using the top slotted hole,
plus either the three bottom holes (for flat
surface mounting) or the center bottom hole
(for attaching to a post or stud). See Figure
6.
Gap
Figure 3 - Separate cover and backplate
Figure 4 - Gap between cover and backplate
Figure 5 - Pull out bottom of cover
5. Ensure the Drive’s ventilation holes are
not blocked and there is enough space
around it to allow free air flow (minimum
75mm clearance on top, bottom, and sides).
See Figure 6. Once the Drive is mounted,
electrical wiring can be connected.
6. To reattach the Drive cover, hook the top of it
on backplate (be sure to leave a gap). Lower
bottom of cover into place. Push cover evenly
against backplate, eliminating the gap. See
Figure 7.
7. Replace screw at bottom of front cover.
5997 0412
Figure 6 - Attaching Drive to wall
Typical
230VAC
Circuit
Breaker
(Double
Width)
Figure 7 - Re-attaching Drive cover
PID_OM_2014.indd 7 24/02/2014 1:49:56 PM
Installation 8
Terminal
Removable
(pull down)
01+ 01+ I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD
Transducer Cable
Connections
Submersible Motor: 3-Ph./ 3-W. 1-Ph., follow colors as above.
Submersible Motor: 1-Ph./ 2-W., connect toY and B, any order.
Above-Ground Motors: L1 to R, L2 to Y, L3 to B; verify rotation.
Output
Ground Screw
Input Power
Connections
Input
Ground Screws
Red
Yellow
Black
Green/Yellow (Ground)
Green/Yellow
(Ground)
6539 0412
Motor Connections
Red to AI+
Black to AI–
Green Cable Shield/Screw
Terminal
Removable
(pull down)
Figure 9 - Basic Wiring Connections for Startup
Wiring
To allow for ease of wiring, the enclosure
wiring area is free of electronics other than
the terminals. Conduit holes and knockouts
are located so that the wire can be fed straight
through to the connectors, with minimal bending.
The terminals accept 1.5mm²-16mm² wire.
For wire sizing refer to table 3, page 6.
NOTICE For convenience in wiring, the input and
motor terminals unplug from the box. Pull them
down to remove them for ease of access, as
shown in Figure 8.
Verify that the terminal connectors are completely
seated when you replace them. It is best practice
to connect all output wires (larger wire gauge)
first, then all input wires.
Pump Connections
If the PENTEK INTELLIDRIVE is used with above
ground motors not rated for Variable Frequency
Drive use, maximize motor life by limiting lead
length to 8.0m.
The output of the Drive is single phase (2-wire or
3-wire) or 3-phase, depending on motor selection
during startup.
The output power terminals (motor wire
connections) are located on the lower right side of
the Drive and are labeled R (Red), Y (Yellow), and
B (Black). See Tables 3.
Feed the motor cable through the 20mm conduit
hole on the bottom right side and into the
appropriate terminals. If the wire is large enough
to require a larger conduit hole, remove the
3.2cm knockout and use the appropriate conduit
connections. Attach the motor ground wire to the
grounding screw, located to the upper right of the
terminal block. Attach the motor power wires to
the terminals as shown in Figure 9.
NOTICE Drive does not sense motor temperature
and will not protect motor from over heating.
5999 0509
Figure 8 - Pull input and motor terminals down
to remove, making wiring easier.
PID_OM_2014.indd 8 24/02/2014 1:49:56 PM
Installation 9
Pressure Tank Recommendations
Minimum tank size is 8 litres. Use a pre-charged
pressure tank with Drive, as shown in Table6. The
tank size must equal at least 20 percent of the
pump’s rated flow in litres per minute (LPM), but
cannot be less than 8 litre capacity. For example,
a pump rated at 30LPM would require a tank of
8 litres capacity or larger. A pump rated at 200
LPM would require a 40 litre tank or larger. Tanks
larger than 40 litre can be used, but may require
adjustment of
Wake Delay
parameter.
Table 7 - Control Pressure Set Point and Tank
Pre-Charge Pressure Values (PSI).
Pressure
Point
Setting
(kPa)
Precharge
Pressure
(kPa)
Pressure
Point
Setting
(kPa)
Precharge
Pressure
(kPa)
170 120 440 310
205 145 480 340
240 170 510 360
270 190 545 380
310 220 580 410
350 245 610 430
375 265 650 455
414
(Default) 290 –
NOTICE Set pressure tank’s pre-charge to 70
percent of the system operating pressure. When
using an external set point as well as an internal
set point, pre-charge tank to 70 percent of the
lower setpoint of the two. Some applications may
require a different percentage when determining
the setpoint.
Transducer Connections
A 0-668 kPa 4-20 mA transducer is provided
with Drive. Install the transducer downstream
of tank, as shown in Figure 1. Install transducer
in a tee in a straight section of pipe with at least
30cm of straight pipe on each side of the tee
(i.e., all fittings must be at least 30cm away from
transducer).
Feed transducer cable through the open 13mm
conduit hole on bottom of the Drive enclosure.
As shown in Figure 9, connect the red wire of the
transducer cable to AI+, connect black wire to AI–,
and connect the green cable shield to the metal
cable shield screw.
To connect the transducer wires:
1. Strip wire 13mm
2. Push spring terminal up with finger or slotted
screwdriver
3. Insert wires from bottom
4. Release spring terminal
Input Power Connections
The input power terminals are located on the
lower left side and are marked L1 and L2 (see
Figure 9). There is a ground screw for the input
ground wire to the right of the connector (torque
to 1.5 Nm). Feed wire through the 20mm conduit
hole on the bottom left side and into appropriate
terminals. If wire is large enough to require a
larger conduit hole, remove the 3.2cm knockout
and use appropriate conduitconnections.
To determine the correct wire sizes for
installation, see Table 3.
NOTICE The PENTEK INTELLIDRIVE only accepts
230V single phase input power. If incoming power
does not match this, have a qualified electrician
alter supply voltage to 230V/1Ph before connecting
it to the Drive.
PID_OM_2014.indd 9 24/02/2014 1:49:56 PM
Initial Startup 10
Initial Startup and
Programming Procedures
Ensure that the cover is installed before operating
the
PENTEK INTELLIDRIVE.
Most installations will only require the initial
startup settings. However, the installer may need
to set additional parameters. Information about
accessing all parameters, explanations of their
functions, and procedures for changing parameter
values, will be found later in this section.
1. Program the Drive: Apply power to the
PENTEK INTELLIDRIVE.
Setup Guide
will appear
in the display. Follow keypress sequence shown
in Figure 10.
NOTICE If
Setup Guide
does not appear, refer to
Drive Reset Procedure,
Figure 20.
Service Factor Amps
To maximize pump performance, be sure to
enter the correct Service Factor Amps (SF
Amps) in the
PENTEK INTELLIDRIVE
.
• Entering SF Amps higher than the motor
rating lets the Drive supply more amps to the
motor than the motor is designed for and may
allow the motor to overheat (see Table 8).
• Entering SF Amps lower than the motor
rating limits the output amps to less than
the motor is designed for and will reduce the
performance of the pump.
• For any 1-Phase 3-Wire motor, the correct
Service Factor Amp rating for the Drive is Cap
Start/Cap Run amps (see Table 8). This may
not match the motor nameplate, which (for a
Single Phase, 3-Wire motor) will generally be
Cap Start/ Induction Run Amps.
• For any 3-Phase, 220V or 1 Phase, 2-Wire
motor, use the motor nameplate Service
Factor Amprating.
NOTICE
PENTEK®
submersible motors may
differ from motors of the same horsepower
from other manufacturers. For 1-Phase,
3-Wire motors from all other submersible
motor manufacturers, enter the motor
manufacturer’s CS/CR service factor amps
for your motor. For 3-Phase, 220V or 2-Wire
1-Phase motors, use the motor nameplate amp
value. Also see
Retro Fit Applications.
Figure 10 - Drive Setup Guide.
PID_OM_2014.indd 10 24/02/2014 1:49:56 PM
23. Pump out well (if necessary):
Direct pump’s discharge to appropriate location
not connected to system and press
Pump Out.
The pump will run at 45 Hz.
Run the Drive in this mode until the well discharge
runs clear, then press
STOP
button to stop Drive.
Risk of explosion. In
Pump Out
mode, pump runs at a constant speed, which can
cause very high pressure if flow is restricted.
4. Verify installation: Make sure that the system
has properly-sized, pressure-relief valve and
pressure tank.
Make sure pressure tank’s precharge is correct.
(See Table 7).
Make sure pump discharge is connected to
system.
5. System Start:
A. Open valves at the ends of lines so that air
will escape during pressurization.
B. Press
Auto Start;
close valves at the ends of
lines after all air has escaped.
C. The system goes into
Constant Pressure
Operation
as soon as the transducer
registers the
Dry Run Sensitivity
parameter
(default is 68 kPa). If system pressure does
not reach thatkPa value within 3 minutes,
the Drive will stop. Press
Auto Start
again to
restart line fill. If longer priming or line fill
time is required, adjust
Fill Time
parameter.
(See Table 9).
Changing a Parameter Value
This procedure works for ANY parameter.
A. Press MAINMENU button.
B. Follow the keypress sequence shown in
Figure12:
A shorthand way to remember this is:
• Press ENTER to change a value
• Press ENTER again to save it
• If new value is not saved, any screen change will
result in the loss of the new value.
Table 9 lists all available commands and
parameters for the PENTEK INTELLIDRIVE.
Initial Startup 11
6567 0512
Use arrows to
find parameter
Use arrows
to change value
Press Enter
to save
Press Enter
Figure 12 - Changing parameter value.
PID_OM_2014.indd 11 24/02/2014 1:49:57 PM
Programming 12
6569 0512
Press PSI Preset
Use arrows to
change the value
Press Enter to Save
Press Enter
Figure 14 - Change PSI Setpoint using PSIPreset.
6568 0512
Press Auto Start
Use arrows to
change the value
Press Enter to Save
Press Enter
Verify
“Running Fixed Press”
displayed on screen
Figure 13 - Change PSI Setpoint while running pump.
Keypad Lock - Password
The password locks or unlocks the blue buttons on
keypad. All PENTEK
 INTELLIDRIVE
units are shipped
from factory with the default password 7777. It can
be changed to any other 1 to 4 digit number. To reset
password to a unique password for unit, unlock
keypad (see below) and follow the keypress sequence
shown in Figure 8 to make the change.
If installer does not press the password button, then
the keypad will automatically lock 60 minutes after the
Drive is powered up. The time out period is adjustable
(see Table 9).
To unlock keypad press
Password,
use directional ar-
rows to select numeric code and press
ENTER.
NOTICE
For more detailed information on keypad
functions, see Figure 2.
Pump Out Operation
Press
Pump Out.
The Drive will start pump in a con-
stant speed mode (default 45 Hz). The pump will run
until
STOP
or
Auto Start
are pushed.
Setting the Pressure
NOTICE Default pressure setting is 414 kPa. If
this value is changed, adjust tank pressure ac-
cordingly (see Table 7).
There are three ways to change the pressure
setpoint:
• While running the pump
Follow keypress sequence shown in Figure 13
to make desiredchange
. This parameter al-
lows either
Internal
or
External Setpoint
to be
changed, depending on which one is referenced
at the time the change is made.
• Via the PSI Preset
Follow keypress sequence shown in Figure 14 to
make desiredchange.
• Via the Main Menu (Main Menu/Settings/Set
point/Internal Setpoint)
PID_OM_2014.indd 12 24/02/2014 1:49:57 PM
Programming 13
Table 9 - Main Menu and Parameters
Menu
Settings Parameter Unit of
Measure
Value Description
Default Min. Max.
Time/Date
Hour Format Hours 12Hr 12Hr 24Hr Selects 12 or 24 hour time scale.
Time mm:ss 1:00 AM 1 24 Sets current time. Used for time
stamp in fault log.
Date MM/DD/YYYY 1/1/12 – – Sets current date. Used for date
stamp in fault log.
PID Control
Proportional
Gain – 2500 0 10000
Sets the PID controller gain. Used
in conjunction with all
PID Control
parameters to control how fast or
slow the Drive reacts to pressure
changes.
Integration
Time Milliseconds 500 ms 20 ms 65000
ms
Sets the PID controller integration
time. Used in conjunction with all
PID Control
parameters to control
how fast or slow Drive reacts to
pressure changes.
Derivation
Time Milliseconds 60 ms 0 ms 10000
ms
Sets PID controller derivation
time. Used in conjunction with all
PID Control
parameters to control
how fast or slow Drive reacts to
pressure changes.
Derivative
Limit – 120 0 2000 Sets derivative filter time constant
for PID controller.
Sleep
Boost
Differential kPa 21 kPa 21 kPa 69 kPa
First part of
Boost Process.
Pressure boost that happens
before it goes to
Wake Delay.
Boost Delay MM:SS 1 Min 30 Sec 5 Min
The time Drive takes to start
Boost Process
after system has
stabilized.
Wake Up
Differential kPa 34 kPa 34 kPa 103 kPa Pressure amount below setpoint
that wakes up Drive.
Wake Delay MM:SS 15 Sec 3 Sec 2 Min
Second part of the
Boost Process.
The time it takes to ramp down
pressure during the
Boost Process.
Password
Password
Time Out HrHr:mm 1 Hr 1 Min 6 Hr
Amount of time it takes to lock
keypad (after last button is
pressed).
Password – 7777 0000 9999
Password used to unlock keypad.
Table 9 lists all available commands and parameters for the PENTEKINTELLIDRIVE.
PID_OM_2014.indd 13 24/02/2014 1:49:57 PM
Table 9 (continued)
Menu
Settings Parameter Unit of
Measure
Value Description
Default Min Max
Setpoints
Internal
Setpoint kPa 414 kPa 103 kPa
668 kPa
(Max
Sensor
Value
minus
30 kPa)
Main pressure setpoint used. Sets
main system operational pressure.
This parameter is accessed here,
through PSI Preset button, or by
pressing Enter button while in
Constant Pressure operation.
External
Setpoint kPa 276 kPa 103 kPa
Max
Sensor
Value
minus
20 kPa.
Second pressure setpoint. When
another pressure setting is desired
other than Internal Setpoint.
Additional programming needed in
I/O section. Requires an external
switch or timer to wired to I1or
I2 terminals. It is only active
when there is voltage present
I1terminals (see Figure 11)
Sub Menu Parameter Unit of
Measure Default Max Min Description
Motor
Motor Phase _ 1 3 1
Selects phase of motor to be
operated. An additional sub menu
will appear, based on phase
selection, to select proper motor
type.
Connection
Type – 3 wire 3 wire 2 wire
Wire type for 1 phase motor
operation only. Can only access
by first setting Motor Phase
parameter to 1 Phase.
Motor Type – Subm Subm Above
Gnd
Motor type for 3 phase, 220V,
motor operation only. Can only
access by first setting Motor Phase
parameter to 3 Phase.
Service Factor
Amps A 00.0 A 00.0 A
Per
drive
and
motor
Service factor amps (max. load) of
motor the Drive is operating. Sets
maximum allowed amps at output
of Drive. See Table 7 for values.
Min Frequency Hz 30 Hz 30 Hz 1 below
Max Hz
Minimum frequency (speed) motor
will run.
Max
Frequency Hz 50 Hz 1 above
Min Hz Hz Maximum frequency (speed) motor
will run.
Sensor
Max Sensor
Value kPa 689 kPA 2068
kPa 68 kPa
Maximum pressure value of
transducer sensor used with Drive.
Only change if different transducer
is used with Drive, other than 689
kPA max scale.
Programming 14
PID_OM_2014.indd 14 24/02/2014 1:49:57 PM
Table 9
(continued)
Menu or
Sub Menu Parameter Unit of
Measure
Value Description
Default Min Max
Ex Runtime
Excessive
Runtime
Detection
_ Enabled
Disabled
Enabled Enables or disables Excessive
Runtime Detection.
Excessive
Runtime
Hours
Hours 24 1 100 Number of hours Drive can run
before it faults on Excessive
Runtime.
Dry Run
Auto Restart
Delay Minutes 10 Min 3 Min 60 Min Time Drive waits to restart pump
when Dry Run is detected.
Number of
Resets – 3 0 5 Number of tries Drive attempts
to restart pump when Dry Run
condition is detected.
Detection
Time M:SS 15 Sec 5 Sec 10 Min Time the Drive takes to recognize
Dry Run condition.
Sensitivity kPa 68 kPA 0 2068
kPa
Pressure value that Dry Run
condition is detected at. Dry Run
fault will occur if this pressure
cannot be met within Detection
Time window. Lower pressure =
less sensitivity.
Fill Time M:SS 1 M 15 S 10 M
Time allowed to fill (prime) pipes
during Auto Line Fill process.
Relates to Dry Run Sensitivity
value. (Time starts after 55 Hz is
reached).
I/O
Digital Input 1
– Unused – –
Selects operation of Drive when
terminal I1 is used. Select between
Unused, Run Enabled, Ext Fault,
and Setpoint. The Drive will
respond to selected command
when voltage is present at I1
terminal.
Digital Input 2
Relay Output – Unused – –
Selects the operation of Drive
when terminal O1 is used. Select
between Unused, Run, and Fault.
The Drive closes the Relay when
Run or Fault is selected.
Over
Press
Over Pressure kPa 552 kPa 103
kPa
2047
kPa
Sets Over Pressure Warning value.
Change if higher than 552 kPa
system pressure is needed.
No Ground
No Ground
Detection – Enabled
Disabled
Enabled
Selects whether Ground Detection
parameter is Enabled or Disabled.
If Disabled is selected, it will revert
back to Enabled after 72 hours.
Warning LED will flash entire time
it is Disabled.
Reset
Factory Reset – No No Yes
Resets all parameters to factory
defaults. Displays Setup Guide
after it is complete. Software
version displayed here. Does not
clear fault log.
SW
Update
Software
Update – Disabled Disabled Enabled Used to update software, if
necessary.
Programming 15
PID_OM_2014.indd 15 24/02/2014 1:49:57 PM
I/O Connections 16
The I/O terminals are located in the center of
the wiring compartment, as shown previously in
Figure9.
The Digital Input connections (I1 and I2) are used to
control the Drive based on the state of an external
device, such as a flow switch, moisture sensor,
alternator, or other device.
Programming is needed to activate any of these
functions (see Table 9).
The Output Relay (O1) is used to control an external
device based on two states of Drive; either Running
the pump or Faulted.
Programming is needed to activate any of these
functions (see Table 9).
Cable Installation
Three 13mm conduit knockouts are provided
on the bottom of the Drive enclosure for the I/O
wires.
Break out the closest 13mm knockout and route
the wires through. Use a cord grip to prevent the
wire from rubbing and causing a short.
NOTICE Never run low voltage I/O wire through
the same conduit hole as the 230V input wires or
motor wires.
To connect the external wires to the terminals:
1. Strip wire 13mm
2. Push spring terminal up with finger or slotted
screwdriver
3. Insert wires from bottom
4. Release spring terminal
Connection Examples
Figures 15-18 show various connection schemes
for typical applications. Table 10 describes each
I/O terminal, including purpose and rating.
6540 0412
Figure 15 - Example Input with internal
24 volt supply
6542 0412
Figure 17 - Example Output relay with internal
24 volt supply
6541 0412
115 VAC
or
230 VAC
+
-
Figure 16 - Example external Input with
externalsupply
6541 0412
115 VAC
or
230 VAC
+
-
Figure 18 - Example Output with externalsupply
PID_OM_2014.indd 16 24/02/2014 1:49:58 PM
I/O Connections 17
Table 10 - I/O Function, Connections, Ratings
Label Function Connection Rating
AI+ Positive connection for transducer Red transducer wire
24 Volt
(supplied)
AI- Negative connection for transducer Black transducer wire
V+ Positive side of 24 volt power supply.
Used to power external devices.
Positive side of 24V external device, i.e.,
flow switch, moisture sensor, alternator,
etc. Need to complete the circuit with V-.
See Figures 15 and 17. 40mA maximum
output
V- Negative side of 24 volt power supply.
Used to power external devices.
Typically to I1-, I2-, or O1-. Used with a
flow switch, moisture sensor, alternator,
etc. Need to complete the circuit with V+.
See Figures 15 and 17.
I1+
Positive (dry contacts) connection of
Digital Input 1
. Connect when using an
external device to control Drive.
From an external device i.e., flow
switch, moisture sensor, alternator, etc.
Requires complete circuit connection
with I1-. See Figures 15 and 16.
Accepts 24VDC
and up to
230VAC
I1-
Negative (dry contacts) connection of
Digital Input 1
. Connect when using an
external device to control Drive.
Can be from V- or from the negative side
of an external power supply. Requires
complete circuit connection with I1+. See
Figures 15 and 16.
I2+
Positive (dry contacts) connection of
Digital Input 2
. Connect when using an
external device to control Drive.
From an external device, i.e., flow
switch, moisture sensor, alternator, etc.
Requires complete circuit connection
with I2-. See Figures 15 and 16.
I2-
Negative (dry contacts) connection of
Digital Input 2
. Connect when using an
external device to control Drive.
Can be from V- or from the negative side
of an external power supply. Requires
complete circuit connection with I2+. See
Figures 15 and 16.
O1+
Output relay (dry contacts) connection.
Programmed to close when pump is
Running or Faulted.
Positive wires of an external device. See
Figures 17 and 18. Accepts up
to 5Amps at
24VDC and
8Amps at up to
230VAC
O1+
Output relay (dry contacts) connection.
Programmed to close when pump is
Running or Faulted.
Positive wires of an external device. See
Figures 17 and 18.
PPositive connection of an RS-485
communication device (see Figure 15). Positive wire from RS-485 device.
Per RS-485
Standard
NNegative connection of an RS-485
communication device (see Figure 15). Negative wire from RS-485 device.
PID_OM_2014.indd 17 24/02/2014 1:49:58 PM
RS-485 Communications
RS-485 is a US-based telecommunications
standard for binary serial communications between
devices. It is the protocol, or set of specifications,
that needs to be followed to allow devices that
implement the standard to speak to each other.
A fully compliant RS-485 port is included in the
PENTEK INTELLIDRIVE system to permit serial
connections among more than two devices on an
RS-485 compliant network. Figure 19 shows two-
wire connection to the Drive.
Lightning/Surge Protection
Lightning arrestors or other surge suppressing
devices can be used with this product. MOV(Metal
Oxide Varistor), SOV(Silicon Oxide Varistor).
Accessories
Part Description Qty Part Number
Alternating Control Panel 1 VFD-ALT
Moisture Sensor 1 VFD-WS
Surge Protection Kits 1 VFD-SGA
300 PSI Transducer 1 U17-2000
Flow Switch 1 U17-1999
Retrofit Applications
When retrofitting an installation with the
PENTEK INTELLIDRIVE, most of the preceding text
can be applied. The recommended Service Factor
Amps for non-PENTEK motors please refer to the
manufacturer literature.
Additional Information 18
6544 0412
01+ 01- I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD
Figure 19 - Example RS-485 Connection
NOTICE The PENTEK INTELLIDRIVE will not
operate Franklin Electric 2-wire motors.
Repair Parts
Part Description Qty Part
Number
Input Terminal Block
Connector 1 PID-CON2
Output Terminal Block
Connector 1 PID-CON3
Cooling Fan 1 PID-FAN-R
Pressure Transducer 1 U17-1561-R
3m/10’ Transducer Cable 1 U18-1593
8m/25’ Transducer Cable* 1 U18-1594
15m/50’ Transducer
Cable* 1 U18-1595
30m/100’ Transducer
Cable* 1 U18-1596
45/150’ Transducer Cable* 1 U18-1597
61m/200’ Transducer
Cable* 1 U18-1598
Keypad 1 PID-HMI-R
* Purchase Separately
PID_OM_2014.indd 18 24/02/2014 1:49:59 PM
Troubleshooting* 19
Fault Possible Causes Solution
Over Current
Shorted output Check for any shorts in motor cables.
Locked rotor Check for debris in pump.
Damaged wire insulation Check motor wire insulation with a megger.
Over Voltage
Internal Drive short With power to Drive off, measure outputs with
ohmmeter to detect short.
Power cycling on and off Check for a generator or switching on input
line.
High line voltage Measure incoming line voltage to Drive; should
be between 190V and 265V.
Under Voltage
Low line voltage
Temporary loss of power Check for local power outage.
Excessive load current Check motor is correctly sized for the
application.
Loss of a motor phase Check correct voltage is present on all motor
leads.
Power was removed from Drive Check correct voltage is present on all input
lines.
Cannot Start Motor
Exceeding Service Factor Amps
Check Service Factor Amps entered are
correct.
Check pump and motor are correct.
No Service Factor Amps value entered Check Service Factor Amps entered and are
correct.
There is an open (connection) in motor
wires Check resistance of all motor wires is correct.
Locked rotor Pull pump check for debris in pump.
Dry Run
Operation at open discharge May need to reduce Dry Run Sensitivity
pressure or apply back pressure on transducer.
Drive cannot read transducer signal Check linearity of transducer, as it may be
damaged. See Troubleshooting Guide for more
information.
Possible leak Check for pipe break or large leak.
Dry running pump Check water level in well.
Ground Fault
Ground wire shorted to motor phase Check the ground wire for short to motor
phase wire or check insulation integrity with a
megger.
Long motor cable length If motor cable length is more than 305m
a reactor or filter may be needed to limit
capacitance between motor wires.
System Not
Grounded
Ungrounded Drive Ground Detect parameter can be disabled, but
will reactivate after 72 hours.
Unbalanced or three phase incoming
voltage.
Line to line voltage must be twice line to
ground voltage. You cannot use two legs from
three phase power.
PID_OM_2014.indd 19 24/02/2014 1:49:59 PM
*
For additional Troubleshooting information, please visit www.sta-rite.com/resources/images/16455.pdf for a downloadable guide.
Troubleshooting
(continued)
20
Fault Possible Causes Solution
Open Transducer
Intermittent connection Check all transducer wires are securely
connected or for damaged cable insulation.
Open Connection Check for proper wiring of all transducer wires
and verify cable connector securely attached to
transducer.
Drive cannot read transducer signal Check electrical system for ground loops or no
ground connection.
Transducer wires crossed Check red is in AI+ and black is in AI-.
Possible failed transducer Check linearity of transducer; see
Troubleshooting Guide for more information.
Shorted Transducer
Short in transducer wires Check for shorted transducer wire or damaged
insulation.
Possible failed transducer Check linearity of transducer; see
Troubleshooting Guide for more information.
Over Temperature Excessive heating in drive
Check ambient temperature is not above 50°C
(122°F).
Check for inoperable or unobstructed fan.
Check vents are not obstructed.
Excessive Runtime
Leak detected Check for leaks in pipe system.
Application calls for long run times Extend Excessive Runtime Hours limitation.
Disable Excessive Runtime Fault.
Internal Fault Internal voltages are out of range
Drive will auto reset and attempt to clear fault.
Fault Reset can be pressed to clear fault
as well. Then try to operate pump. If fault
continues Drive may need replacement.
Hardware Fault Internal hardware failure Fault Reset can be pressed to clear fault. Then
try to operate pump. If fault continues Drive
may need replacement.
External Fault The external device detected fault
condition and closed the I1 or I2 input Check external device.
Low Amps
Under-sized pump Increase Minimum Speed to 35 Hz.
Low current draw from pump
Thermal protector open in motor (3
wire) Wait 20 minutes then restart pump.
Missing motor phase Check all motor connections at the Drive.
Warning Possible Causes Solution
Warning LED
flashing
Ungrounded Drive, with ground
detection parameter disabled (will
operate for 72 hours and then fault).
Verify ground wire is connected on both
incoming voltage side and motor side of Drive.
With the power disconnected, use an
ohmmeter to verify which pipe the Drive’s
transducer is connected to. Also verify that the
input ground wire is at the same potential, e.g.,
has approximately the same ohm reading.
Verify the input ground is connected all the way
back to electrical panel.
Jam Warning Debris in pump stopping motor from
turning (locked rotor). Drive tries to free debris in pump by reversing
or pulsing motor.
Over Pressure
Warning Pressure rising above Over Pressure
setting.
Drive stops and waits 1 minute, then checks
that pressure is below the Setpoint pressure.
Below it restarts, if not checks again in another
minute. Can increase over-pressure value.
PID_OM_2014.indd 20 24/02/2014 1:49:59 PM

Other manuals for Pentek Intellidrive

7

Other Pentair Controllers manuals

Pentair AUTOTROL LOGIX 740 User manual

Pentair

Pentair AUTOTROL LOGIX 740 User manual

Pentair AUTOTROL Performa 263 User manual

Pentair

Pentair AUTOTROL Performa 263 User manual

Pentair AVID XA+ Manual

Pentair

Pentair AVID XA+ Manual

Pentair SPEEDEO CONNECT User manual

Pentair

Pentair SPEEDEO CONNECT User manual

Pentair raychem ngc-30/uit2 Operating instructions

Pentair

Pentair raychem ngc-30/uit2 Operating instructions

Pentair Autotrol 255 Series User manual

Pentair

Pentair Autotrol 255 Series User manual

Pentair RAYCHEM RAYSTAT-ECO-10 User manual

Pentair

Pentair RAYCHEM RAYSTAT-ECO-10 User manual

Pentair intellidrive pid10 User manual

Pentair

Pentair intellidrive pid10 User manual

Pentair FLECK 5800 XTR2 User manual

Pentair

Pentair FLECK 5800 XTR2 User manual

Pentair COLOR SYNC User manual

Pentair

Pentair COLOR SYNC User manual

Pentair COLOR SYNC User manual

Pentair

Pentair COLOR SYNC User manual

Pentair FLECK 2750 NXT2 User manual

Pentair

Pentair FLECK 2750 NXT2 User manual

Pentair FLECKXT User manual

Pentair

Pentair FLECKXT User manual

Pentair LINCOLN SYSTEM SENTRY 84530 Owner's manual

Pentair

Pentair LINCOLN SYSTEM SENTRY 84530 Owner's manual

Pentair AUTOTROL LOGIX 740 User manual

Pentair

Pentair AUTOTROL LOGIX 740 User manual

Pentair AK110 User manual

Pentair

Pentair AK110 User manual

Pentair TRACETEK TTDM-128 User manual

Pentair

Pentair TRACETEK TTDM-128 User manual

Pentair MYERS K4563 Manual

Pentair

Pentair MYERS K4563 Manual

Pentair FLECK SXT User manual

Pentair

Pentair FLECK SXT User manual

Pentair IntelliBrite User manual

Pentair

Pentair IntelliBrite User manual

Pentair 3200NXT User manual

Pentair

Pentair 3200NXT User manual

Pentair SOLARTOUCH 521592 User manual

Pentair

Pentair SOLARTOUCH 521592 User manual

Pentair FLECK 5800 XTR2 User manual

Pentair

Pentair FLECK 5800 XTR2 User manual

Pentair Intellichem 521498 User manual

Pentair

Pentair Intellichem 521498 User manual

Popular Controllers manuals by other brands

Daikin FWEC2T Installation and use manual

Daikin

Daikin FWEC2T Installation and use manual

Mircom RB-MD-1086 Series installation instructions

Mircom

Mircom RB-MD-1086 Series installation instructions

LS Smart I/O datasheet

LS

LS Smart I/O datasheet

GE EntelliPro ES Series Installation and instruction manual

GE

GE EntelliPro ES Series Installation and instruction manual

I2R Tech Lighting Solutions Moving Head Controller 2.0 user manual

I2R Tech Lighting Solutions

I2R Tech Lighting Solutions Moving Head Controller 2.0 user manual

AMX AXLINK WIRING CONSIDERATIONS instruction manual

AMX

AMX AXLINK WIRING CONSIDERATIONS instruction manual

Trane Technologies Symbio 800 Integration guide

Trane Technologies

Trane Technologies Symbio 800 Integration guide

Sungrow EMS300 user manual

Sungrow

Sungrow EMS300 user manual

Danfoss 101N0715 quick start guide

Danfoss

Danfoss 101N0715 quick start guide

esera automation 11319 operating instructions

esera automation

esera automation 11319 operating instructions

V2 CALYPSO Series instructions

V2

V2 CALYPSO Series instructions

Emerson Fisher FIELDVUE DVC6005 Series quick start guide

Emerson

Emerson Fisher FIELDVUE DVC6005 Series quick start guide

TCS Basys Controls SZ1143b product manual

TCS Basys Controls

TCS Basys Controls SZ1143b product manual

Johnson Controls LN Series installation instructions

Johnson Controls

Johnson Controls LN Series installation instructions

ZyXEL Communications Network Device NXC-8160s quick start guide

ZyXEL Communications

ZyXEL Communications Network Device NXC-8160s quick start guide

EBECO EB-Connect WiFi manual

EBECO

EBECO EB-Connect WiFi manual

dixell T66 Installing and operating instructions

dixell

dixell T66 Installing and operating instructions

LEGRAND C2G 29977 Operation manual

LEGRAND

LEGRAND C2G 29977 Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.