Sensors
EasySense
Ceiling-Mount
Philips EasySense Quick Installation Guide
Commercial Product Name Order Code
EasySense Ceiling-Mount Sensor SNS100CMP (510651)
Connection Color
White Neutral
Black Line
Green Ground
Purple SR+
Brown SR-
Compatible LED Drivers
Sensor Part Number
Driver Model Number Description
XI040C110V054VPT1 Xitanium 40W 0.1-1.1A 27-54V 120-277V SR
XI075C200V054VPT1 Xitanium 75W 0.1-2.0A 27-54V 120-277V SR
Specications available at www.philips.com/XitaniumSR.
Wiring Diagram
XITANIUM SR
LED DRIVER
LED+
LED+
LED-
LED-
RSET2
SGND
NFC ANTENNA
SR-
Connectors
SR+
RED
WHITE
LINE
NEUTRAL
GROUND NC
36-inch 18AWG solid lead wires in
plenum-rated jacket from sensor stripped
to 3/8". Connect white wire to brown (SR-)
and red wire to purple (SR+) on driver.
Four drivers per sensor maximum.
Polarity must be maintained.
EASYSENSE
Electrical Information
Input Voltage Powered by SR driver low-voltage interface
Current Consumption 13mA
Nominal Power Consumption 200mW
Standby Power < 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type Passive infrared (PIR)
Enable/Disable Default enabled
Detection O/Auto-on; Red LED indicates “on”
Hold Time 1 - 120 minutes
Viewing Angle X=72°, Y = 86° ( See detection pattern)
Background Light Level O or 5-100%
Prolong Time 0 minutes - innity
Grace Fading 0-25 sec
Response Time/Fading to Switch On/O 0.7Sec
Daylight Sensing
Enable/Disable Default enabled
Auto-calibration Upon power-up
Viewing Angle 40° (half value sensitivity); 2% cut-o point at 75°
Task Tuning
Full Light Setting 5-100%
Environment & Approbation
Operating Ambient Temperature Range 0°C to 55°C
Operating Humidity 0 – 95% non condensing
Storage Temperature -25°C to 85°C
Storage Humidity 0-95% non condensing
Max Case Temperature (Tcase) 55°C
Agency Approbations UL, CSA; Tested and approved for use in plenums; FCC ID:
2AF2N-SNS100; IC: 20659-SNS100
Certication California Title 20
Limited Warranty 5 years
Digital Interface Xitanium SR
Other
Status Indicators Red, Yellow. Yellow LED on: Vacancy & Sensor is functional;
Red LED on: Motion is detected
No. Drivers per Sensor Four drivers per sensor maximum; Wiring polarity must be maintained
Field Conguration via NFC, parameters set via Philips Field Apps
© 2016 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right to make changes in specications
and/or to discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.
philips.com/easysense
Philips Lighting North America Corporation
10275 W. Higgins Road, Rosemont IL 60018
Tel: 800-322-2086 Fax: 888-423-1882
Customer/Technical Service: 800-372-3331
OEM Support: 866-915-5886
Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
PLt-1621QG_EasySenseCMP QIG 02/16 page 1 of 2
Document #: 4435 290 61451 REV. A
Operation and Conguration via Mobile App
EasySense operates immediately upon installation and energization without further commissioning. If changes from
default settings are desired, EasySense can be congured via an app through NFC embedded within the sensor.
The “Philips eld app” can be accessed on the Google Play Store. For a complete description of the features and default
settings—as well as details on the app and recommended Android phones—refer to www.philips.com/easysense.
FCC and IC
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS
standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. Any
changes or modications not expressly approved by Philips could void the user’s authority to operate this equipment.
This product is intended for commercial use only.
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et
d’Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes
: (1) Ce dispositif ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris
le brouillage pouvant entraîner un mauvais fonctionnement. Tous les changements ou modications non expressément
approuvés par Philips, sont susceptibles d’annuler le droit de l’utilisateur à se servir de cet équipement. Ce produit est
exclusivement destiné à un usage commercial.
Connection Color
Red LED+
Blue LED-
Orange RSET2
Green SGND