24h00
Indicator LED
Test button
Self test version
Once the unit is powered up it will automatically initiate a self test and diagnostics as follows:
Every 4 seconds : Checks for battery disconnection, charger board fault, lamp failure and transformerfailure
Every month : Performs a 3 minute duration test
Every year : Performs a 1 Hour or 3 Hour duration test
Dual color indicator LED:
Green solid on; Ready / normal operation
Green ashing; Testing
Red ashing; Requires service
Note 1: After repairing a service fault, press and hold the test button for 2 seconds to reset
Note 2: Manual testing also works with the self test unit
Manual test version
Charge time
/
Press test button once 30 second duration test
Press test button 2 times within 2 seconds 3 minute duration test
Press test button 3 times within 2 seconds 30 minute duration test
Press test button 4 times within 2 seconds 3 hours duration test
*One ash, 4 seconds pause Battery not connected
** Two ashes, 4 seconds pause Battery short or low battery voltage
*** Three ashes, 4 seconds pause Charger board fault
**** Four ashes, 4 seconds pause Transformer board fault
***** Five ashes, 4 seconds pause LED lamp fault