Pichler LG 100 DE Specification sheet

Systematic ventilation.
OPERATING AND
INSTALLATION MANUAL
CEILING UNIT LG 100 DE
COMFORT
VENTILATION

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 2
Changes reserved
Contens
G
1. Introduciton Page 4
2. General Page 4
U
2.1. UNIT IN CEILING DESIGN PAGE 5
2.2. OVERVIEW OF COMPONENTS PAGE 5
3. Functionality of the ventilation system Page 6
4. Designated use Page 6
4.1. INTENDED USE PAGE 6
4.1.1. STIPULATIONS FOR OPERATION WITH FIREPLACES PAGE 7
4.1.2. STIPULATIONS FOR OPERATION WITH EXTRACTOR HOODS PAGE 7
4.1.3. LIABILITY PAGE 7
4.1.4. WARRANTY PAGE 7
5. Safety Page 8
5.1. SYMBOLS USED IN THIS DOCUMENT PAGE 8
5.2. SAFETY REGULATIONS PAGE 8
5.3. SETTING UP THE UNIT PAGE 9
5.4. ELECTRICAL CONNECTION WORK PAGE 9
5.5. PLANT OPERATION PAGE 10
6. Customer service Page 10
7. Design of the ventilation unit Page 10
8. MINI control unit Page 11
8.1. FUNCTIONS PAGE 11
8.2. BUTTONS AND LEDS PAGE 11
9. Operation via PICHLER APP and PICHLER Connect Page 12
9.1. EASY OPERATION WITH THE PICHLER APP PAGE 12
9.2. REMOTE ACCESS WITH PICHLER CONNECT PAGE 12
9.3. DATA PROTECTION PAGE 12
9.4. CREATING AN ACCOUNT PAGE 13
10. Error & warning messages Page 15
10.1. LED ON THE VENTILATION UNIT PAGE 15
10.2. MINI CONTROL UNIT PAGE 15
10.3. PICHLER-APP PAGE 15
11. Filter service Page 16
11.1 .MINI CONTROL UNIT FILTER MESSAGE PAGE 16
11.1.1. CLEARING THE MINI CONTROL UNIT FILTER MESSAGE PAGE 16
11.2. FILTER MESSAGE ON THE UNIT PAGE 16
11.3. FILTER MESSAGE VIA PICHLER APP PAGE 16
11.4. FILTER CHANGE PAGE 16
11.5. PROCEDURE FOR THE FILTER CHANGE PAGE 17
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 3
Changes reserved
S - /
12. Transport, storage and disposal Page 18
12.1. TRANSPORT, STORAGE AND PACKAGING PAGE 18
12.2. DISPOSAL PAGE 18
13. Technische Daten Page 18
13.1. UNIT SET-UP AND DIMENSIONS PAGE 18
13.2. SYSTEM DIAGRAM PAGE 19
13.3. SAFETY DEVICES PAGE 20
13.4. DEVICE DATA PAGE 20
13.5. SOUND DATA PAGE 21
14. Control Page 21
14.1. FROST PROTECTION WITH A PRE-HEATING BATTERY PAGE 21
14.2. MOISTURE PROTECTION PAGE 21
14.3. FROST PROTECTION WITHOUT A PRE-HEATING BATTERY PAGE 22
14.4. VOC/ECO2 CONTROL PAGE 22
14.5. OUTDOOR AIR QUALITY CONTROL PAGE 22
15. Mounting Page 23
15.1. PREPARATORY WORK PAGE 23
15.1.1. ASSEMBLING THE OUTDOOR AIR AND EXHAUST AIR CONNECTING PIECE PAGE 23
15.2. UNIT ASSEMBLY PAGE 23
15.3. PIPEWORK PAGE 24
15.4. ELECTRICAL CONNECTION PAGE 25
S -
16. Maintenance and cleaning Page 27
16.1. SAFETY INSTRUCTIONS PAGE 27
16.2. MAINTENANCE INSTRUCTIONS PAGE 27
16.3. ENTHALPY EXCHANGER PAGE 27
16.4. CLEANING THE EQUIPMENT HOUSING INSIDE PAGE 29
16.5. SERVICE TABLE PAGE 30
17. Commissioning Page 32
17.1. PRINCIPAL QUESTIONS WITH REGARD TO COMMISSIONING PAGE 32
17.2. SETTING SYSTEM PARAMETERS PAGE 32
18. Error description Page 33
18.1. ERROR DESCRIPTION FOR THE MINI CONTROL UNIT PAGE 33
18.2. ERROR DESCRIPTION FOR THE UNIT PAGE 34
19. Installation/operation of service software and firmware updates Page 34
20. Spare parts and accessories Page 35
20.1. CONTROL ELEMENTS PAGE 35
20.2. AIR FILTER PAGE 35
20.3. GATEWAY PAGE 35
21. Changes reserved Page 35
22. EC Declaration of Conformity Page 36
GENERAL
USER
SPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 4
Changes reserved
This manual contains notes and information regarding safe operation and proper installation of the decentralised compact ventilation
unit LG 100 and on its use and servicing. Furthermore, reference this manual during servicing to ensure proper execution of the
tasks.
Troubleshooting and procedures may be performed by an installation company (specialist company) only.
Changes reserved: This manual has been compiled with the utmost care. This does not, however, imply any rights. Your unit may
therefore vary slightly from the description in this manual.
Our "General terms and conditions" in their latest version apply.
2. General
Dear customer
Dear customer,
Thank you for choosing the decentralised compact ventilation unit LG 100 from PICHLER.
To operate your compact ventilation unit safely, properly and economically, please read this manual carefully and follow the
instructions provided. Keep this operating manual in a safe place and readily available. These units are subject to ongoing
improvement and further development. Your unit may therefore vary slightly from the description in this manual.
Use the ventilation unit only when in perfect condition and for its designated use, be aware of safety and any hazards and cognisant
of all the notes and information contained in this manual.
1. Introduction
J. Pichler
Gesellschaft m.b.H
AUSTRIA 9021
KLAGENFURT
Karlweg 5
T +43 (0) 463 32769
www.pichlerluft.at
Equipment type:
08LG100DEFV
Year of
manufacture:
Volume flow:
max. 80 m
3
/h
Weight:
approx. 35 kg
Dimensions WxHxD:
599x945x203 mm
Voltage/frequency:
230V / 50 Hz
Power consumption:
max. 320 W
Order number:
Serial number:
J. Pichler
Gesellschaft m.b.H
AUSTRIA 9021
KLAGENFURT
Karlweg 5
T+43 (0) 463 32769
www.pichlerluft.at
Equipment type:
08LG100UPFV
YYeeaarr ooff
mmaannuuffaaccttuurree::
Volume flow:
max. 80 m3/h
WWeeiigghhtt::
approx. 15 kg
Dimensions WxHxD:
504x882x192 mm
Voltage/frequency:
230V / 50 Hz
Power consumption:
max. 320 W
Order number:
Serial number:
J. Pichler
Gesellschaft m.b.H
AUSTRIA 9021
KLAGENFURT
Karlweg 5
T+43 (0) 463 32769
www.pichlerluft.at
Equipment type:
08LG100APFV
YYeeaarr ooff
mmaannuuffaaccttuurree::
Volume flow:
max. 60 m
3
/h
WWeeiigghhtt::
approx. 25 kg
Dimensions WxHxD:
525x910x203 mm
Voltage/frequency:
230V / 50 Hz
Power consumption:
max. 320 W
Order number:
Serial number:
Compact ventilation unit LG 100 ceiling variant with pre-heating
battery
Compact ventilation unit LG 100 flush-mounted variant with
pre-heating battery
Compact ventilation unit LG 100 surface-mounted variant with
pre-heating battery
Please always keep the model and serial number (see name-
plate on unit) at hand in the case of queries or when ordering
spare parts.
Please contact us if you have any further questions or if you lose
this documentation.
Your PICHLER team
J. Pichler Gesellschaft m.b.H.
9021 KLAGENFURT
Karlweg 5, Postfach 32
T+43 (0)463 32769
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 5
Changes reserved
2.1. Unit in ceiling design
The compact ventilation unit LG 100 in ceiling design comprises a ceiling unit (1) and two variably mountable connections for outdoor
air and exhaust air (2).
GENERAL
USER
SPECIALIST PERSONNEL
21
Components of a ceiling unit
Overview of components
Designation Item number Drawing
Ceiling unit
Ceiling unit with pre-heating battery
08LG100UPF
08LG100UPFV
LG 100 DE BG ODA/EHA connection 40LG100DEBG030
2.2. Overview of components

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 6
Changes reserved
The compact ventilation unit is not a ready-to-use product. It must not be put into operation until it has been properly installed and
connected. Only qualified and instructed personnel may carry out connection and service work on the unit.
B
In order to prevent an uncontrolled formation of condensate in the unit, continuous operation with an extract air
humidity of more than 60 % has to be avoided at outdoor temperatures below 0°C (e.g. private spa area).
B
Persons transporting, installing or working on the unit must have read and understood the operating instructions, in
particular Section 5 "Safety". The end user must also be instructed on potential hazards.
With the ventilation unit LG 100 you can provide a maximum degree of flexibility to your ventilation concept. The used air is extracted
from the living areas, and fresh, filtered outdoor air is supplied again. In this process, the high-quality enthalpy exchanger allows for
ecient heat and moisture recovery and ensures a well-balanced room humidity and a pleasant room climate.
Highly ecient and low noise EC radial fans allow for extremely energy-saving and low-noise operation. In the switched-o state,
the outdoor and exhaust air openings are automatically closed mechanically. The integrated sensors record the VOC and eCO2
concentration of the extract air and, in automatic mode, allow for an operation depending on the room air quality.
The decentralised compact ventilation unit LG 100 is operated easily and intuitively by means of a pushbutton directly on the unit or
via the PICHLER APP. Therefore the unit comes with a WLAN connection as a standard feature. Optionally you can additionally connect
an external control unit via cable connection.
The compact ventilation unit LG 100 is intended for the installation into ventilation and air conditioning systems for the controlled
domestic ventilation in small and medium-sized residential units (approx. 80m²). The purpose of controlled mechanical ventilation
and deaeration of domestic areas is to improve air quality and reduce the heating energy demand through the use of a highly
ecient heat recovery system, and to impact on indoor air humidity. The scope and intended use for the unit are limited to the use
in residential and recreation spaces for the extraction of used air and the supply of fresh, tempered outdoor air at maximum flow
media temperatures of -15 °C to +35 °C. Furthermore, the air conveyed must be free from aggressive vapours and substances
enhancing wear. Any other use shall be deemed contrary to designated use. The manufacturer shall accept no responsibility for
damages or consequential damages arising from improper use. Designated use also includes adherence to our prescribed operating
and installation manual. This unit is not available to the general public and is intended for the installation in residential or industrial
buildings. The unit is used for mechanical aeration and ventilation of indoor air and, when combined with a heater battery, is also
used to preheat air.
This unit can be used by children from an age of 8 years and furthermore by persons with reduced physical, sensory or mental
capabilities or a lack of experience or knowledge, if they are supervised or if they have been instructed on how to use the unit safely
and if they understand the hazards resulting therefrom. Children must not play with the unit. Cleaning and user maintenance must
not be carried out by children without supervision. The unit is not suitable for outdoor installation and may be installed in suitable and
frost-free interior areas only. The ventilation unit is not suitable for drying new buildings.
3. Functionality of the ventilation system
4. Designated use
4.1. Intended use
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 7
Changes reserved
4.1.1. STIPULATIONS FOR OPERATION WITH FIREPLACES
4.1.2. STIPULATIONS FOR OPERATION WITH EXTRACTOR HOODS
4.1.3. LIABILITY
Local requirements must be taken into consideration by compliance with corresponding standards, laws and directives. The
decentralised compact ventilation unit LG 100 may only be installed in rooms, flats or utilisation units of a comparable size in which
fireplaces dependent on room air are installed, if:
• simultaneous operation of room air-dependent fireplaces and the air extraction unit is prevented by safety devices, or
• the flue gas evacuation of the room air-dependent fireplace is monitored by special safety devices. In the case of room-air
dependent fireplaces for liquid or gaseous fuels, activation of the safety device must lead to the switch-o of the fireplace or
ventilation unit. In the case of room-air dependent fireplaces for solid fuels, activation of the safety device must lead to the switch-o
of the ventilation unit.
The ventilation units for the controlled aeration and ventilation of a flat or a comparable living unit must not be installed if room air-
dependent fireplaces in the living unit are connected to exhaust gas systems, which themselves have multiple connections. Normal
operation requires the possibility of shutting potentially available combustion air ducts as well as exhaust gas systems o from room
air-dependent fireplaces. In the case of exhaust gas systems of fireplaces for solid fuels, it must be ensured that the shut-o device
can only be operated manually. The position of the shut-o device must be identifiable by the setting of the operating handle. This
specification is considered as complied with if a shut-o device against soot is used. With regard to the fire protection installation
regulations for the set-up of the ventilation unit, the provisions of national law, in particular the building regulation concerning the fire
protection requirements with regard to ventilation systems in the relevant latest version must be observed.
Due to the heavy load as well as the irregular operation, the extract air of an existing kitchen extractor hood must not be integrated
into the dwelling's ventilation system. Extract air from such extractor hoods must be conducted separately by means of an exhaust
air pipe over the roof. The supply air must be provided for separately (e.g. by window ventilation).
If an extractor hood without the separate provision of supply air is operated, the balance of the air volume in the dwelling is no longer
kept and the proper function of the dwelling's ventilation system is no longer ensured (odour diversion, etc.). Another option is to
operate the extractor hood in recirculation mode.
The compact ventilation unit LG 100 has been developed and manufactured for controlled mechanical ventilation and deaeration of
spaces with purposes similar, for example, to seminar rooms and small oces. Proper use requires that combustion air lines and
exhaust systems have the facility to be shut o from fireplaces dependent on ambient air.
Any other use than that described in Section 4 shall be deemed improper and may cause personal injury or damage to the ventilation
unit, for which the manufacturer shall accept no liability.
GENERAL
USER
SPECIALIST PERSONNEL
The manufacturer accepts no responsibility for any damage due to:
• non-compliance with the safety, operating and servicing instructions given in this operating and installation manual.
• the installation of spare parts that have not been supplied by the manufacturer, the responsibility for the use of such spare parts
being fully borne by the system builder/installer.
• Normal wear and tear.
4.1.4. WARRANTY
The warranty period shall commence after the unit is put into operation, but no later than one month after delivery. Warranty
details can be found in our “General terms and conditions” in their latest version as well as the merchant conditions of your
respective country. The warranty shall be subject to proof of services performed as per our instructions and executed by a licensed
installer/specialised company. Warranty claims shall be limited to material and/or constructional defects occurring during the
warranty period. In the event of a warranty claim, the compact ventilation unit LG 100 must not be dismantled without prior written
authorisation from the manufacturer. The manufacturer's liability shall be limited to spare parts installed by an installation company
approved by the manufacturer. The warranty shall automatically lapse at the end of the warranty period, following improper operation
such as operation without a filter, if parts other than original manufacturer-supplied parts are installed, or if unauthorised changes
are made to the unit. Furthermore, the warranty is automatically rendered void by failure to comply with the information in this
operating and installation manual.

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 8
Changes reserved
5.2. Safety regulations
Installation, initial start-up, maintenance and repairs must only be carried out by an authorised specialist company.
Over and above this operating and installation manual, local and national regulations and standards shall also apply to the operation
of this unit without limitation.
Take instruction from your installer on the unit and on its control unit following installation. The ventilation unit may only be used in
accordance with the information provided in Section 4 "Designated use”.
All safety and danger notices attached to the unit and specified in this description must be observed.
In the event of malfunctioning, switch o the unit immediately and disconnect all poles to switch the unit to zero potential. The unit
must be appropriately secured against restart. Faults must be remedied immediately.
After repairs and maintenance work, qualified personnel must verify that the unit is safe to operate.
Attachment or installation of additional parts and components is not permitted. Any modification of the compact ventilation unit is
prohibited. Only original spare parts may be used.
Modifications and alterations to the ventilation unit are prohibited and absolve the manufacturer from all warranties and liability.
Ensure that children do not play with the unit.
B
Attention/Note!
5. Safety
Read this operating and installation manual carefully and observe the safety instructions while you carry out installation,
commissioning, servicing or general work on the ventilation unit. Keep the operating and installation manual near the unit for its
entire service life.
Always observe the safety regulations, warnings, notes and instructions given in this operating manual. The specifications given
in this document must not be altered. Non-observance of these safety regulations, warnings, notes and instructions may lead to
physical injury or damage to the compact ventilation unit.
The conclusion of a service contract is recommended to ensure that the unit will be checked at regular intervals. Ask your supplier
about approved specialised companies/installers in your area.
The following Safety symbols highlight text containing warnings in respect of danger and potential hazards. Please familiarise your-
self with these symbols.
5.1. Symbols used in this document
B
Attention – High voltage! Ignoring this warning may lead to injury or threat to life and limb.
B
Attention! Ignoring this warning may lead to injury or threat to life and limb and/or damage to the unit.
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 9
Changes reserved
Installation shall be carried out in accordance with the general local building, safety and installation regulations of the relevant
community or the water and electricity department and other bodies. The unit may only be installed in frost-free and dry rooms.
The room temperature at the place of installation must be consistently between +5°C min. and +35 °C max. The unit is designed for
ceiling installation and may only be set up on a suitable, load-bearing construction. The unit must not be exposed to vibration of any kind.
Components of the ventilation unit, e.g. air ducts which may need to be installed in unheated areas, must be suitably insulated to
prevent heat loss or condensate formation (for temperatures under dewpoint). Observe all locally-applicable construction and fire
protection guidelines, regulations and standards. If necessary, appropriate suitable measures should be taken when installing the
unit, e.g. installation of fire dampers in air ducts, etc.
5.3. Setting up the unit
B
The national and local regulations must be heeded when installing and setting up the unit. The unit may only be
installed in compliance with national installation regulations.
GENERAL
USER
SPECIALIST PERSONNEL
B
Any work practices that could potentially impair the safety of the unit are prohibited! To ensure safe operation, safety
devices must not be removed or bypassed.
Electrical equipment and the unit's warning and protective devices must be inspected regularly to ensure that they are in perfect
working order. In the event of faults in the electrical power supply or identification of defects, e.g. loose connections or burnt cables,
the unit must be switched o immediately. Damaged or faulty power supply cables to the unit must be repaired immediately to avoid
hazards. The unit may not be operated until safe operational conditions are restored. Fault finding and immediate remediation of
electrical defects and malfunctions shall be carried out by authorised electricians only. All protective measures must be inspected
(e.g. earth resistance, etc.) after completion of electrical work on the unit.
B
Before opening the unit and when carrying out work on the unit e.g. maintenance work and repairs, the unit must be
isolated from the mains (all poles disconnected) and secured against being switched back on for the duration of the
work. The compact ventilation unit must be connected to a
230 V / 50 Hz voltage supply and with correct phase polarity. The mains supply line must be provided with a strain
relief.
To the external interfaces exclusively fittings may be connected for which it is proven that there is an electrically
protective separation between the interface and those active parts of the fitting, which are not operated with safety
extra-low voltage (SELV/PELV), in compliance with DIN EN 61140, e.g. by double or reinforced insulation complying
with DIN EN 60335-1 or DIN EN 60730-1.
Warning: hazardous electrical voltage! Ignoring the danger may result in death, injuries or material damage.. Before
carrying out any work on live parts, the unit must always be disconnected completely from the power supply (all
poles) and secured against being switched back on.
5.4. ELECTRICAL CONNECTION WORK
B
Electrical connection work and work on the system's electrical components may be carried out by authorised
electricians only, in compliance with national and local regulations.

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 10
Changes reserved
The compact ventilation unit may be operated only in accordance with the project documentation. which shall comply with the
Equipment and Product Safety Act and the pertinent provisions of the EC Directives and Standards. Consider environmental impacts
and refrain from installing the ventilation unit in the vicinity of flammable liquids or gases, in swimming pools or in areas exposed to
chemicals or hazardous substances.
7. Design of the ventilation unit
The compact ventilation unit LG 100 comprises:
• a compact, thermally insulated and soundproof EPP housing
• a casing of galvanised steel sheet
• a swivelling cover for inspection work
• a highly ecient enthalpy exchanger
• energy-saving EC radial fans
• an integrated sensor system for measuring the volumetric flow, temperature, relative humidity and VOC/eCO2 concentration
• outdoor air and extract air filter ISO Coarse 70 % and supply air filter ISO ePM1 55%
• an integrated filter monitoring function - when the time interval is reached
• standard operation via pushbutton on the unit, WLAN interface for controlling the PICHLER-APP and for providing remote access
via PICHLER Connect, and optionally with the “MINI” control unit for setting the basic functions.
6. Customer service
Please contact the installer of your ventilation and air condi-
tioning system or contact us directly for any questions relating
to the delivered compact ventilation unit LG 100.
B
Operation of the unit is exclusively permissible with a connected air duct or mounted system components such as
silencers, in order to ensure that, for example, fans or electrical installation parts, cannot be touched with the hand.
If error messages are output or in the case of damage, the ventilation unit must be switched o and disconnected from the mains
immediately. Ensure that you are safety conscious and aware of risks when you open the unit and when you remove cover plates. Any
work practices that could potentially impair the safety of the unit are prohibited.
The compact ventilation unit may be operated only in accordance with the project documentation. which shall comply with the
Equipment and Product Safety Act and the pertinent provisions of the EC Directives and Standards. Consider environmental impacts
and refrain from installing the ventilation unit in the vicinity of flammable liquids or gases, in swimming pools or in areas exposed to
chemicals or hazardous substances. Never operate the ventilation unit without an air filter. Air filters must be checked regularly for
dirt and damage and replaced, if necessary. The air filters must be changed at least every six months or when the “Change Filter”
message appears on the control unit. Use original replacement filters only. If the plant is not used in summer, the air filters must, for
hygienic reasons, be replaced prior to restarting.
Comply with safety requirements and standards when operating the ventilation unit simultaneously with ambient air-dependent
fireplaces. When using fireplaces dependent on ambient air, combustion air supply must be provided separately. Due to the heavy
load as well as the irregular operation, extractor hoods must in no case be integrated into the exhaust duct of the compact ventilation
unit. Exhaust air extractor hoods must be operated via separate air pips with suitable air replenishment e.g. by means of window
ventilation or in air recirculation mode. For corresponding details see Sections 4.1.1. and 4.1.2.
USER GENERALSPECIALIST PERSONNEL
5.5. Plant operation
B
Operation of the ventilation unit is permitted only if all built-in parts provided e.g. silencers etc., have been properly
connected
B
In the event of any errors or defects that can cause harm to persons or property, the system must be put out of oper-
ation immediately. Further use must be actively prevented until the unit is fully repaired.
J. Pichler Gesellschaft m.b.H.
9021 KLAGENFURT
Karlweg 5, Postfach 32
T+43 (0)463 32769

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 11
Changes reserved
The following compact ventilation unit functions
can be indicated and configured by means of the “MINI” control unit:
• Ventilation level of the compact ventilation unit
• Display of the filter change message
• Display of the fault messages via LED
• Intensive ventilation mode for a defined time
• WIFI modes
The unit is operated via the “MINI” control unit.
8. MINI control unit
8.1. Functions
MINI control unit
8.2. Buttons and LEDs
1. Plus button
Increasing the ventilation level
2. Minus button
Reducing the ventilation level
3. Error LED
Indicates errors with dierent flashing patterns that light up
4. Filter LED
After the filter time has elapsed, the filter has to be checked.
To acknowledge the filter message, press the plus and minus
buttons simultaneously for 5 seconds.
5. WIFI button
- press once to activate the WIFI mode
- press for 2 seconds to deactivate the WIFI mode
- press for 5 seconds to call the Access Point mode
6. WIFI LED
- LED o = WIFI deactivated
- LED is lit = WIFI mode
- LED flashes = Access Point mode
7. Boost button
Activates ventilation level 3 (boost ventilation level) for a
defined period of time (standard: 60 minutes)
8. Boost LED
Is lit when the boost ventilation mode is active.
The LED of the current ventilation level is lit and the LED of
ventilation level 3 flashes.
9. Ventilation level LEDs
Indicate the current ventilation level
When all three LEDs are active, this corresponds to the auto-
matic mode. The ventilation unit follows a demand-controlled
air volume flow regulation via VOC.
Functions of the MINI control unit
GENERAL
USER
SPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 12
Changes reserved
PICHLER APP:
Error messages
via PUSH
notification
When the defined time (configurable) has elapsed in the highest ventilation level, ventilation operation switches back automatically to
the ventilation level set last. Alternatively, you can end the boost ventilation mode manually before the time has passed. Simply press
the [-] button on your control unit.
Ventilation level 1
Boost ventilation mode for a defined time
Ventilation level 2
Boost ventilation mode for a defined time
Ventilation level 3
Boost ventilation mode for a defined time
Pattern Operation
Green LED level 1 is lit
Ventilation level 1
Green LED level 2 is lit
Ventilation level 2
Green LED level 3 is lit
Ventilation level 3
All three LEDs are lit green
“Automatic” ventilation level
9. Operation via PICHLER APP and PICHLER Connect
User-friendly: The compact ventilation unit can be operated
easily with our free smartphone App for Android and iOS,
whether you are at home or out and about:
Load and install the PICHLER-APP from the APP store or
from the Google Play store. The PICHLER APP can control the
ventilation unit directly or via the Internet.
By pressing the WIFI button for 5 seconds (see red marking
in the illustration on the left), the Access Point mode of the
ventilation unit is activated and indicated by a green flashing of
the WIFI-LED.
9.1. Easy operation with the PICHLER APP
Operational safety: Remote access allows the PICHLER customer service to respond quickly and
easily in the event of faults.
When you have installed the PICHLER APP and establish a connection to the device, we assume that you accept our current data
privacy statement (see: www.pichlerluft.at/datenschutz.at).
9.2. Remote access with PICHLER Connect
9.3. Data protection
connect.
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 13
Changes reserved
Afterwards press the “Search for units...” button
If the ventilation unit is found via the Access Point mode, a 12-digit
number is shown.
If no number is shown,
the smartphone is not
connected to the ventilation unit.
Start again!
When the Access Point mode is active, the ventilation unit is visible
via the WLAN settings of the smartphone. Select the network of the
name “LG100AHU” and enter the password “Pichler1234”. When a
connection with the ventilation unit has been established success-
fully, open the PICHLER APP.
The following screen is shown:
Press the “LG100 Access Point” button in order to establish
a direct connection with the ventilation unit.
Press the “Login” button. The APP checks the
connection and loads the data of the ventilation unit.
Go to the “WIFI settings” menu.
The following screen will open:
9.4. Creating an account
GENERAL
USER
SPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 14
Changes reserved
The same 12-digit number as in the Access mode is
shown.
If no number is shown, either the ventilation
unit or your smartphone is not
connected to the Internet router.
Start again!
Connect your smartphone to the Internet router and
select “Connect via Internet” on the screen now.
In order to connect the ventilation unit to the Internet router, you
must enter the network name (WIFI-SSID), the WIFI password and
the WIFI encryption. Then press “Accept”. The direct connection
between the ventilation unit and your smartphone is interrupted.
If the Internet connection with the ventilation unit and your smartphone has been established successfully, you must allocate an
account name, email address and a password. Press the “Save” button and your account is created.
Then you can control your ventilation unit worldwide using your smartphone.
Since you are connected to the same network, press the “Search
for units...” button.
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 15
Changes reserved
10.1. LED on the ventilation unit
10. Error & warning messages
The meaning of the dierent flashing codes is described in greater detail in Section 18 “Error description” (“Specialized personnel”
section). In any case, check the Internet connection and switch the unit on and o before consulting an expert.
The meaning of the dierent flashing codes is described in greater detail in Section 18 “Error description” (“Specialized personnel”
section). In any case, check the Internet connection and switch the unit on and o before consulting an expert.
Display of error messages on the unit
LED
Operating button
GENERAL
USER
SPECIALIST PERSONNEL
10.2. MINI control unit
B
The error messages of the compact ventilation unit on the MINI control unit are indicated by red error LED flashing
patterns.
B
The error messages of the compact ventilation unit are indicated in red by flashing patterns on the LED on the lower
end of the ventilation unit.
MINI control unit error message
The APP indicates a group error message via PUSH notification. To obtain an exact error indication, please read o the flashing
pattern from the control unit or the ventilation unit.
10.3. PICHLER APP

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 16
Changes reserved
11. Filter service
When the filter service life has elapsed (factory setting 6 months) the control unit
reports the necessity of a filter check. This takes place via the LED provided for this
purpose (on the bottom left), which will then be lit yellow permanently.
Required filter change
Reset the filter counter after changing the filter.
Press the [+] and the [-] button at the same time for 5 seconds in order to do this.
The filter message disappears after entering this combination.
Premature filter change
If the air filters are replaced prematurely, the filter counter must be reset without a
pending filter message.
To do this, you again press the [+] and the [-] button simultaneously for five seconds.
When the filter service life has elapsed, the APP shows a filter message
via PUSH notification.
11.1. MINI control unit filter message
11.1.1. Clearing the MINI control unit filter message
11.3. Filter message via PICHLER APP
B
At every filter maintenance always all 3 filters must be replaced.
MINI control unit filter message
Flashing LED
11.4. Filter change
B
Only original replacement filters of the specified filter class may be used
for the filter replacement.
B
When replacing the air filters, avoid soiling the unit and its components. Dirty air filters must be immediately and
suitably disposed of. The used air filters can be disposed of as residual waste.
When the filter service life has elapsed (factory setting 6 months), the unit
indicates a filter change on the control by the LED alternately flashing in
green and red. To acknowledge the filter message, keep the button pressed
for 5 seconds.
11.2. Filter message on the unit
USER GENERALSPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 17
Changes reserved
B
When inserting the new filters, observe the mounting position (direction of air).
Symbol Designation Item no.:
ODA pre-filter (outdoor air)
ETA filter (extract air)
Coarse 70% 40LG0500006A
SUP fine filter (supply air) ePM1 55% 40LG0500007A
1. Filter message on the MINI control unit or via the Pichler APP.
2. Set the unit to Standby.
3. Open the rotary closures.
4. Open the swivelling cover.
5. Remove the filter covers by pressing the latches positioned at the sides towards the inside.
6. Remove the respective air filter by the flaps. Note the direction of the air stream!
7. Insert the new air filter and close the filter cover. Note the direction of the air stream!
8. Close the swivelling cover again.
9. Acknowledge the filter message.
11.5. Procedure for the filter change
Open the rotary closures
Remove the filter cover
Open the swivelling cover
Change the air filter
GENERAL
USER
SPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 18
Changes reserved
12. Transport, storage and disposal
The compact ventilation unit is delivered in a transport packaging. The safety markings on the packaging must be observed. The unit
must be stored in its packaging in suitable dry rooms.
In order to prevent possible transport damage, handle the compact ventilation unit LG 100 with care and secure it correspondingly
during transport. Ensure that the unit is not damaged from being toppled or overturned. Avoid knocks and blows during
transportation. Applicable safety and accident regulations must be complied with during transportation. If transported manually,
ensure that necessary human lifting and carrying forces are reasonable.
The packaging materials must be disposed of in accordance with local regulations; wooden pallets or cartons must be recycled,
for instance.
Units that are no longer in working order must be dismantled by a specialised company and properly disposed of via suitable
collection centres in accordance with the Waste Electrical and Electronic Equipment Ordinance (WEEE), which provides for the
implementation of community law, Directive 202/95/EC (RoHS) and Directive 2002/96/EC (WEEE Directive).
S - /
12.1. Transport, storage and packaging
12.2. Disposal
B
Any transport damage and/or missing parts must be reported immediately in writing to the forwarder or supplier.
13. Technical specifications
13.1. Unit set-up and dimensions
USER GENERALSPECIALIST PERSONNEL
1 Supply air
2 Extract air
3 Outdoor air (100 mm)
4 Exhaust air (100 mm)
5 Enthalpy exchanger
6 Outdoor air fan
7 Exhaust air fan
8 Controller
9 Outdoor air flap
10 Exhaust air flap
11 Outdoor air filter ISO Coarse 70%
12 Supply air filter ePM 55%
13 Extract air filter ISO Coarse 70%
14 Cable inlets
15 Multi-room supply air (Komflex 75)
16 Multi-room extract air (Komflex 75)
17 Pre-heating battery

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 19
Changes reserved
13.2. System diagram
1. Supply air (SUP) Supply air is the air supplied to the room.
2. Extract air (ETA) Extract air is the air that is extracted from the room.
3. Outdoor air (ODA) Outdoor air is the air that is drawn in from outside.
4. Exhaust air (EHA) Exhaust air is the air that is blown out into the open.
5. Enthalpy exchanger Serves to transfer heat and recover humidity from the warmer to the colder air.
6. Outdoor air fan Provides for the required air volume flow in the supply air.
7. Exhaust air fan Provides for the required air volume flow in the extract air.
8. Controller
The ventilation unit is regulated in a demand-oriented fashion via the VOC/eCO2 sensor system
integrated into the ventilation unit.
The ventilation unit can be controlled optionally by using the pushbutton on the unit, via Pichler APP or
via the “MINI” control unit.
9. Outdoor air flap Closes the outdoor air connection of the unit when the unit is switched o.
10. Exhaust air flap Closes the exhaust air connection of the unit when the unit is switched o.
11. Outdoor air filter ISO Coarse 70% Serves to pre-filter the outdoor air and to protect the unit interior.
Furthermore the filter replacement intervals of the supply air filter are prolonged.
12. Supply air filter ISO ePM1 55% Serves to filter particulate matter in the supply air.
13. Extract air filter ISO Coarse 70% Serves to filter the coarse impurities from the extract air, in order to protect the unit’s interior from
being contaminated.
14. Cable inlets Electric connecting cable
15. Supply air connections for multi-room
applications Serves to provide the KOMFLEX system connection with the possibility of ventilating further rooms.
16. Extract air connections for multi-room
applications
Serves to provide the KOMFLEX system connection with the possibility of air extraction from further
rooms.
17. Electric pre-heating battery
Provides protection against the formation of condensate and against freezing in the heat exchanger at
very cold outdoor temperatures. The optional electric pre-heating battery serves to preheat the outdoor
air as a function of the outdoor and exhaust air temperature.
GENERAL
USER
SPECIALIST PERSONNEL

OPERATING AND INSTALLATION MANUAL CEILING UNIT LG 100 DE PAGE 20
Changes reserved
Properties
Volume flow constant function yes
Humidity control yes
Air quality control (VOC, eCO2) yes
Mechanical cover flap in the outdoor air and exhaust air pipe yes
Characteristic values in compliance with EN13141-7:20111)
Temperature ratio 80.4%
Temperature ratio supply air 64.3%
Specific input power SIP 0.36Wh/m3
Classification of air filters in accordance with EN ISO 16890
ODA filter (outdoor air - pre-filter) ISO Coarse 70%
SUP filter (supply air - fine filter) ISO ePM1 55%
ETA filter (extract air) ISO Coarse 70%
Operating conditions
Permissible operating temperature (outdoor air)
with / without preheating battery -15 °C/ -5°C
Condensate drainage not required 2)
Electrical system
Electrical connection 230V/1 ~ / 50 Hz/ 13 A
Power consumption of ventilation unit 8 – 40 watts
Electrical power consumption pre-heating battery 280 watts
Materials and components
Inner part EPP and galvanised steel sheets
Design front sheet steel, galvanised
Heat exchanger Enthalpy counterflow heat exchanger with a polymer membrane
Fans EC radial fans
13.3. Safety devices
B
To ensure safe operation of the system, safety devices and covers must by no means be rendered inoperative;
nor may measures be taken to bypass or dismantle them.
In the event of any errors or defects on the ventilation system, which may cause harm to persons or property, the system must be put
out of operation immediately or be protected against restart. Further use must be actively prevented until the unit is fully repaired.
The unit may only be repaired by a specialised company.
13.4. Device data
Equipment type LG 100 DE - ceiling
System Centralised
Application Multi-room application
Article number ventilation unit 08LG100DEF
Article number ventilation unit with pre-heating battery 08LG100DEFV
Device data
Ventilation stages 1 - 2 - 3 - automatic
Level 1 - basic ventilation 25
Level 2 - normal ventilation 56
Level 3 - boost ventilation 80
Automatic (demand-based) 25- 80
Energy eciency class A
USER GENERALSPECIALIST PERSONNEL
Table of contents
Other Pichler Fan manuals

Pichler
Pichler LG Series User manual

Pichler
Pichler LG 500 System VENTECH User manual

Pichler
Pichler LG 350 User manual

Pichler
Pichler LG 100 AP Specification sheet

Pichler
Pichler LG 500 System VENTECH User manual

Pichler
Pichler LG 350 User manual

Pichler
Pichler LG 740 Specification sheet

Pichler
Pichler LG 750 User manual

Pichler
Pichler LBE 250AO Specification sheet

Pichler
Pichler LG 500 System VENTECH User manual