
OPERATING AND INSTALLATION INSTRUCTIONS LG 350 AND LG 450 PAGE 9
USER GENERALSPECIALIST PERSONNEL
National and local regulations
must be observed during
installation and setup. The unit
must be installed in compliance with
national installation regulations.
Installation shall be carried out in
accordance with the general, locally
applicable building, safety and installation
regulations of the relevant community or
the water and electricity department and
other bodies.
The unit may only be installed in frost-free
and dry rooms. The room temperature
at the place of installation must be
consistently between +5°C min. and
+35°C max.
The unit is designed for free-standing
installation or wall mounting and must
only be mounted on a suitable load-
bearing structure. The unit must not be
exposed to vibration of any kind.
The proper drainage of condensate
accumulating during operation of the
ventilation unit will be required, including
eective odour blocking traps (siphon).
The piping system for water, heating and
condensate connections must only be
installed by a specialist. The unit must be
installed and executed appropriately so
as to ensure seal-tightness and eective
condensate drainage in order to exclude
the possibility of building damage.
Eective condensate drainage must be
verified on-site prior to initial start-up and
after servicing the unit.
The maximum permissible load must be
observed when transporting the unit.
Components of the ventilation plant,
e.g. air ducts which may need to be
installed in unheated areas, must be
properly insulated to prevent heat loss or
condensate formation (for temperatures
under dew point). Observe all locally-
applicable construction and fire protection
guidelines, regulations and standards. If
necessary, appropriate suitable measures
must be taken when installing the unit,
e.g. the installation of fire dampers in air
ducts, etc.
UNIT SET-UP
Warning of hazardous electrical
voltage! Disregarding the hazard
may result in death, injuries, or
damage to material assets. Before car-
rying out any work on live parts, the unit
must always be disconnected completely
from the power supply (all poles) and
secured against being switched back on.
The earth contact plug and socket-outlet
on the power connection makes it possi-
ble to disconnect all poles of the unit from
the power supply.
Electrical connection work and
work on the system's electrical
components may be carried out
by authorised electricians only, in compli-
ance with national and local regulations.
Before opening the unit and
when carrying out work on the
unit, e.g. maintenance work and
repairs, etc., the unit must be deenergised
(disconnection of the voltage supply for
all poles) and must be protected against
restart for the duration of the work per-
formed.
The compact ventilation unit is designed
for a 230V/50 Hz voltage supply.
Work practices that could
compromise the unit’s safety are
prohibited! To ensure safe oper-
ation, safety devices must not be removed
or bypassed.
Electrical equipment and the unit's
warning and protective devices must be
inspected regularly to ensure that they
are in perfect working order. In the event
of faults in the electrical power supply or
the identification of defects, e.g. loose con-
nections or burnt cables, the unit must be
switched o immediately.
Damaged or faulty power supply cables to
the unit must be repaired immediately to
avoid hazards.
ELECTRICAL CONNECTION WORK