
USER GENERALSPECIALIST PERSONNEL
The national and local regulations
must be heeded when installing
and setting up the unit. The unit
may only be installed in compliance with
national installation regulations.
Installation shall be carried out in
accordance with the general local build-
ing, safety and installation regulations of
the relevant community or the water and
electricity department and other bodies.
The unit may only be installed in frost-free
and dry rooms. The room temperature at
the place of installation must be consist-
ently between +5°C min. and +35°C max.
The unit is designed for free-standing
installation and may only be set up on a
suitable, load-bearing construction. The
unit must not be exposed to vibration of
any kind.
Suitable drainage of condensate arising
during operation of the unit will be re-
quired, including eective odour blocking
traps (siphon). Installations for water,
heating and condensate connections may
be performed by a specialist only. The unit
must be installed and executed appropri-
ately so as to ensure seal-tightness and
eective condensate drainage in order to
exclude the possibility of building damage.
Eective condensate drainage must be
verified on-site prior to initial start-up and
after servicing the unit.
The maximum permissible load must be
observed when transporting the unit.
Components of the ventilation unit, e.g.
air ducts which may need to be installed
in unheated areas, must be suitably insu-
lated to prevent heat loss or condensate
formation (for temperatures under dew-
point). Observe all locally-applicable con-
struction and fire protection guidelines,
regulations and standards. If necessary,
appropriate suitable measures should be
taken when installing the unit, e.g. instal-
lation of fire dampers in air ducts, etc.
UNIT SET-UP
Warning: hazardous electrical
voltage! Ignoring the danger
may result in death, injuries or
material damage. Before carrying out
any work on live parts, the unit must
always be disconnected completely from
the power supply (all poles) and secured
against being switched back on.
The shockproof connector system on the
mains supply line allows for disconnect-
ing all poles of the unit from the power
supply.
Electrical connection work and
work on the system's electrical
components may be carried out
by authorised electricians only, in compli-
ance with national and local regulations.
Before opening the unit and
when carrying out work on the
unit, e.g. maintenance work and
repairs, the unit must be isolated from
the mains (all poles disconnected) and
secured against being switched back on
for the duration of the work. The compact
ventilation unit is designed for a voltage
supply of 230V/ 50Hz.
Work practices that could
potentially damage the unit are
prohibited. To ensure safe oper-
ation, safety devices must not be removed
or bypassed.
Electrical equipment and the unit's
warning and protective devices must be
inspected regularly to ensure that they
are in perfect working order. In the event
of faults in the electrical power supply or
identification of defects, e.g. loose con-
nections or burnt cables, the unit must be
switched o immediately.
Damaged or faulty power supply cables to
the unit must be repaired immediately to
avoid hazards.
ELECTRICAL CONNECTIONS