Emergency Stop Relays, Safety Gate Monitors
Category 3, EN 954-1
PNOZ X6
Safety gate monitor and emergency
stop relay in accordance with
VDE 0113 part 1, 11/98, EN 60204-1,
12/97 and IEC 204-1, 11/98
Features
●PST 3 compatible
●Single-channel or dual-channel
which detects shorts across the
inputs
●Designed for driving via semi-
conductors
●Automatic or monitored manual
reset
●Simultaneity monitoring can be
switched-on or off
Approvals
Technical Data PNOZ X6
Electrical Data
Supply Voltage
AC: 42, 100, 110 ... 120, 200, 230 ... 240 V
AC/DC: 24 V
Tolerance 85 ... 110 %
Residual Ripple DC Max. 120 %
Power Consumption Approx. 1,5 W/5,0 VA
Voltage and Current at input circuit and 24 VDC, 50 mA
feedback control loop
Switching Capability in accordance with AC1: 240 V/8 A/2000 VA
EN 60947-4-1, 10/91 400 V/5 A/2000 VA
DC1: 24 V/8 A/200 W
EN 60947-5-1, 10/91 AC15: 230 V/5 A
(DC13: 60 cycles/min) DC13: 24 V/7 A
Output Contacts 3 N/O safety contacts
Contact Fuse Protection 10 A quick or 6 A slow
to EN 60947-5-1, 10/91
Max. permitted Switch-on Current 10 A
Times
Response Delay Approx. 300 ms
Delay-on De-energisation Approx. 50 ms
Recover Time Approx. 200 ms
Simultaneity channel 1/2 Approx. 200 ms or ¥
Max. Supply Interrupt before De-energisation
10 ms
Mechanical Data
Max. cross section of 2 x 2.5 mm2
external conductors Single-core or multi-core with crimp
connectors
Dimensions (H x W x D) 87 x 45 x 121 mm
Weight AC: 400 g, DC: 300 g
Description
●45 mm P-97-housing, DIN-Rail
mounting
●Relay outputs, positive-guided:
– 3 (N/O) safety contacts
●Connections:
– e-stop button
– safety gate limit switch
– reset button
●LED indicators: channel 1/2 and
supply voltage
●Increase in the number of
contacts available by connecting
external contactors / relays
Operating Modes
●Single-channel
●Dual-channel
●Automatic reset
●Manual reset
●Monitored manual reset
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-047-07/00
Telefon +49 (7
11) 34
09-0, Telefax +49 (7
11) 34
09-1
PNOZ X6
●
●
●