
Installation Instructions
Transducer Location
Locate where your installation plan recommends fitting the
transducers. For box coolers these should be on the top of the water
manifold of the cooler taking care to avoid the flow directing baffles
inside the manifold lid. On pipes the transducers should be attached
with the use of a pipe adapter which Ultraguard can supply. On hulls
you should locate the transducers as equidistant from hull frames as
you can to allow the maximum resonance response.
Remove the paint and any coatings right back to the bare
substrate.
Ensure the surface is smooth and free of gouges or
dimples that could cause an air gap between the
transducer and the surface.
Clean the surface and the head of the transducer with
acetone until both surfaces are, ‘Surgically,” Clean.
Once the surfaces are clean DO NOT TOUCH them again
with fingers or skin as the oils in your skin affect the
bond. If you do, re-clean thoroughly.
Ensure you are happy with the location and practice dry
fitting the transducer.
Once you are happy with location, get into position to
apply the transducer. The adhesive will cure in seconds
and you have to place the transducer onto the surface
IMMEDIATELY
once the adhesive is applied. (You will not
have time to move from a work bench or other location
before the adhesive cures!)
Fit the supplied nozzle to the adhesive syringe
Have a spatula or similar implement ready to spread and
smooth adhesive.
Apply a serpentine bead across the face of the
transducer and immediately smooth it across the
transducer face with the spatula. The aim is to have an
even coverage of 2mm-3mm thick with no bare spots
which could form air gaps.
IMMEDIATELY place the transducer into location and
hold in place for 30 seconds.
Leave the transducer to fully cure for 24 hours before
connecting its cable to the control unit.
Whilst waiting you can run the main section of
transducer cable back to the control unit. Ultraguard
recommends using suitable cable trays and conduits to
achieve this.
Control Unit Installation
Find a suitable location for the control unit within 40m of
cable run from the transducers. The control units should
be located in a dry position off the deck that allows easy
access.
Using the dimensional diagram on the following sheet,
set out the mounting points required on your vessel. You
may need to manufacture a suitable bracket to mount
the control unit on.
Mount the control unit onto the vessel using the supplied
mounting brackets.
Run a fuse protected 240v AC 1 Phase power supply from
the vessel’s power distribution system into the control
panel via the cable gland and connect it to the power
terminals.
Connect the transducer main cables in order to the
transducer outlet connectors on the bottom of the
panel.
Once the transducers have had 24 hours to bond to the
protected surface, Connect the transducer tail cable to
the control panel via the main cables.
Turn on the main RED isolation switch on the front of the
control unit.
Switch the transducer operating switches to ON one at a
time. Wait until each LED turns green before switching
on the next switch.
Once every transducer is switched ON and the LEDs are
GREEN go to each transducer and ensure that you can
hear it operating. If they are located in a noisy
environment put your ear to the back of the transducer.
You should hear a high pitched tone as the transducer re-
starts each frequency sweep. You may also hear a
scratchy clicking sound as the transducer operates.
If there is a problem or not all of the LEDs are GREEN,
please refer to the Operators Manual supplied with your
Ultraguard system.