Potter PFC 2000RC User manual

1
PFC 2000RC • 5403521-REV N• 3/03
ALL SPECIFICATIONS SUBJECT TO REVISION
MANUAL #5403521 - REV N
3/03
2081 Craig Road • P.O. Box 28480 • St. Louis, MO 63146-4161
(800) 325-3936 • (314) 878-4321 • FAX (314) 878-7264
www.pottersignal.com
INSTALLATION, OPERATION
AND INSTRUCTION MANUAL
PFC 2000RC
FIRE CONTROL PANEL
firealarmresources.com

2
PFC 2000RC •5403521-REV N•3/03
Potter Electric Signal Company
2081 Craig Road • P.O. Box 28480 • St. Louis, MO 63146-4161 • (314) 878-4321 • (800) 325-3936
WARRANTY INFORMATION
The essential purpose of any sale or contract for sale of any of the products listed in the POT-
TER catalog or price list is the furnishing of that product. It is expressly understood that in
furnishing said product, POTTER does not agree to insure the Purchaser against any losses
the Purchaser may incur, even if resulting from the malfunction of said product.
POTTER warrants that the equipment herein shall conform to said descriptions as to all affir-
mation of fact and shall be free from defects of manufacture, labeling and packaging for a
period of one (1), three (3), or five (5) year'(s), depending on the product, from the invoice date
to the original purchaser, provided that representative samples are returned to POTTER for
inspection. The product warranty period is stated on the exterior of the product package.
Upon a determination by POTTER that a product is not as warranted, POTTER shall, at its
exclusive option, replace or repair said defective product or parts thereof at its own expense
except that Purchaser shall pay all shipping, insurance and similar charges incurred in con-
nection with the replacement of the defective product or parts thereof. This Warranty is void in
the case of abuse, misuse, abnormal usage, faulty installation or repair by unauthorized per-
sons, or if for any other reason POTTER determines that said product is not operating prop-
erly as a result of causes other than defective manufacture, labeling or packaging.
THE AFORESAID WARRANTY IS EXPRESSLY MADE IN LIEU OF ANY OTHER WARRAN-
TIES, EXPRESSED OR IMPLIED, IT BEING UNDERSTOOD THAT ALL SUCH OTHER
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE WARRANTIES OF MER-
CHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE HEREBY EXPRESSLY
EXCLUDED. IN NO EVENT SHALL POTTER BE LIABLE TO PURCHASER FOR ANY
DIRECT, COLLATERAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNEC-
TION WITH PURCHASER’S USE OF ANY OF THE PRODUCTS LISTED HEREIN, OR FOR
ANY OTHER CAUSE WHATSOEVER RELATING TO THE SAID PRODUCTS. NEITHER
POTTER NOR ITS REPRESENTATIVES SHALL BE LIABLE TO THE PURCHASER OR
ANYONE ELSE FOR ANY LIABILITY, CLAIM, LOSS, DAMAGE OR EXPENSE OF ANY
KIND, OR DIRECT COLLATERAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RELA-
TIVE TO OR ARISING FROM OR CAUSED DIRECTLY OR INDIRECTLY BY SAID PROD-
UCTS OR THE USE THEREOF OR ANY DEFICIENCY, DEFECT OR INADEQUACY OF
THE SAID PRODUCTS. IT IS EXPRESSLY AGREED THAT PURCHASER’S EXCLUSIVE
REMEDY FOR ANY CAUSE OF ACTION RELATING TO THE PURCHASE AND/OR USE
OF ANY OF THE PRODUCTS LISTED HEREIN FROM POTTER SHALL BE FOR DAMAG-
ES, AND POTTER'S LIABILITY FOR ANY AND ALL LOSSES OR DAMAGES RESULTING
FROM ANY CAUSE WHATSOEVER, INCLUDING NEGLIGENCE, OR OTHER FAULT,
SHALL IN NO EVENT EXCEED THE PURCHASE PRICE OF THE PRODUCT IN RE-
SPECT TO WHICH THE CLAIM IS MADE, OR AT THE ELECTION OF POTTER, THE RES-
TORATION OR REPLACEMENT OR REPAIR OF SUCH PRODUCT.
firealarmresources.com

3
PFC 2000RC •5403521-REV N•3/03
Contents
GENERAL DESCRIPTION ............................................................................................................................................................... 5
SYSTEM FEATURES ........................................................................................................................................................................ 5
ORDERING INFORMATION ............................................................................................................................................................ 5
SPECIFICATIONS ............................................................................................................................................................................. 6
HOUSING .................................................................................................................................................................................... 6
VISUAL INDICATORS .............................................................................................................................................................. 6
LCD .............................................................................................................................................................................................. 6
PANEL VISUAL DISPLAY DRAWING ................................................................................................................................... 6
CONTROL SWITCHES ..................................................................................................................................................................... 7
SILENCE SWITCH ..................................................................................................................................................................... 7
RESET SWITCH ......................................................................................................................................................................... 7
TEST SWITCH ............................................................................................................................................................................ 7
ZONE DISABLE SWITCHES .................................................................................................................................................... 7
AUTO RESET SWITCH ............................................................................................................................................................. 7
RELEASING CIRCUIT DISABLE SWITCH .................................................................................................................................... 7
ALARM INITIATING DEVICE CIRCUITS ..................................................................................................................................... 8
MANUAL INITIATING DEVICE CIRCUITS .................................................................................................................................. 8
SUPERVISORY INITIATING DEVICE CIRCUIT .......................................................................................................................... 8
INDICATING APPLIANCE CIRCUITS ........................................................................................................................................... 8
RELEASING CIRCUIT ...................................................................................................................................................................... 9
ABORT CIRCUIT ............................................................................................................................................................................... 9
PRE-DISCHARGE TIMER ................................................................................................................................................................ 9
DISCHARGE TIMER ......................................................................................................................................................................... 9
POWER REQUIREMENTS ............................................................................................................................................................. 10
AUXILIARY POWER OUTPUT ..................................................................................................................................................... 10
AUDIBLE INDICATOR ................................................................................................................................................................... 10
ELECTRONIC OUTPUTS ............................................................................................................................................................... 10
AUXILIARY CONTACT OUTPUTS .............................................................................................................................................. 10
MAIN CIRCUIT BOARD MODULE .............................................................................................................................................. 10
TERMINATION ............................................................................................................................................................................... 10
OPERATING TEMPERATURE RANGE ....................................................................................................................................... 10
APPROVALS AND LISTINGS ....................................................................................................................................................... 11
SERVICE USE .................................................................................................................................................................................. 11
BASIC CIRCUIT OPERATION ....................................................................................................................................................... 11
DESCRIPTION OF SEQUENTIAL MODE ............................................................................................................................. 11
DESCRIPTION OF CROSS-ZONING MODE ......................................................................................................................... 11
ALARM CONDITION .............................................................................................................................................................. 11
TROUBLE CONDITION .......................................................................................................................................................... 11
INITIATING DEVICE CIRCUITS RESPONSE ...................................................................................................................... 11
ABORT CIRCUIT RESPONSE ................................................................................................................................................ 12
INDICATING APPLIANCE AND RELEASING CIRCUITS RESPONSE ............................................................................12
SUPERVISORY CONDITION.................................................................................................................................................. 12
ABORT CONDITION ............................................................................................................................................................... 12
firealarmresources.com

4
PFC 2000RC •5403521-REV N•3/03
GROUND FAULT ..................................................................................................................................................................... 12
LOSS OR REDUCTION OF AC POWER ................................................................................................................................ 13
AC CIRCUIT BREAKER OPERATION .................................................................................................................................. 13
HIGH OR LOW BATTERY VOLTAGE .................................................................................................................................. 13
BATTERY CIRCUIT BREAKER OPERATION ..................................................................................................................... 13
AUXILIARY POWER FAILURE ............................................................................................................................................. 13
DISCHARGE CIRCUIT DISABLED ....................................................................................................................................... 13
AUTO RESET SWITCH ........................................................................................................................................................... 13
COMMON TROUBLE OUTPUTS ........................................................................................................................................... 13
SILENCING AN ALARM OR TROUBLE CONDITION ....................................................................................................... 14
RESETTING AN ALARM CONDITION ................................................................................................................................ 14
RESETTING A TROUBLE CONDITION ............................................................................................................................... 14
SELECTING PANEL OPERATING CHARACTERISTICS ................................................................................................... 14
SELECTING THE PRE-DISCHARGE TIME .......................................................................................................................... 14
SELECTING INITIATING DEVICE ZONE STYLE D OR B (CLASS A OR B) .................................................................. 14
SELECTING INDICATING APPLIANCE CIRCUIT MODE ................................................................................................ 15
SELECTING THE PRE-DISCHARGE TIMER ACTIVATION MODE ................................................................................ 15
ACTIVATION FROM MANUAL CIRCUIT ........................................................................................................................... 15
SELECTING ABORT CIRCUIT OPERATING MODE .......................................................................................................... 16
SELECTING DISCHARGE TIME ........................................................................................................................................... 16
INSTALLATION INSTRUCTIONS ................................................................................................................................................ 16
PROCEDURE FOR THE REMOVAL OF THE MAIN BOARD MODULE .......................................................................... 16
LOCATION ............................................................................................................................................................................... 16
MOUNTING THE BEZEL ........................................................................................................................................................ 17
INSTALLATION OF BEZEL FOR SEMI-FLUSH INSTALLATIONS DRAWING.............................................................. 17
WIRING HOOKUP .................................................................................................................................................................... 17
TEST PROCEDURES....................................................................................................................................................................... 17
OPERATING INSTRUCTIONS ....................................................................................................................................................... 18
BATTERY SIZE REQUIREMENTS ............................................................................................................................................... 18
TABLE 1, CURRENT REQUIREMENTS ...................................................................................................................................... 19
TABLE 2, SECONDARY POWER SUPPLY REQUIREMENTS ................................................................................................. 19
CALCULATION TABLE ................................................................................................................................................................. 19
INACTIVE CIRCUITS ..................................................................................................................................................................... 19
PFC 2000RC MAIN BOARD CONNECTION DRAWING ............................................................................................................ 20
APPLICATION NOTES ................................................................................................................................................................... 21
TYPICAL 2-WIRE DETECTOR CONNECTION DRAWINGS .................................................................................................... 22
TYPICAL 4-WIRE DETECTOR CONNECTION DRAWING ...................................................................................................... 23
CONNECTION DRAWING POWER SUPPLY MODULE ............................................................................................................ 23
CONNECTION DRAWING FOR CENTRAL STATION & PROPRIETARY OPERATION ...................................................... 24
PFC 2000RC INNER PANEL DRAWING ...................................................................................................................................... 25
2-WIRE SMOKE DETECTOR COMPATIBILITY DATA ............................................................................................................ 26
AUTOMATIC WATER CONTROL VALVES COMPATIBILITY DATA ................................................................................... 27
EXTINGUISHING AGENT CONTROL VALVE COMPATIBILITY DATA .............................................................................. 27
ALARM INDICATING APPLIANCE COMPATIBILITY DATA ................................................................................................. 27
WIRE ROUTING FOR POTTER MODEL PFC 2000RC ............................................................................................................... 28
firealarmresources.com

5
PFC 2000RC •5403521-REV N•3/03
GENERAL DESCRIPTION
This microprocessor-based fire detection and releasing control panel meets the requirements of Underwriter Laboratories Standard
864 and is in compliance with the National Fire Protection Association (NFPA) Standards for service usage as follows: NFPA 12-
Carbon Dioxide Systems, NFPA 12A - Halon 1301 Fire Systems, NFPA 12B - Halon 1211 Systems, NFPA 13 - Sprinkler Systems,
NFPA 17 - Dry Chemical Extinguishing Systems, NFPA 72 - National Fire Alarm Code (Local and Proprietary Fire Alarm Systems).
SYSTEMFEATURES
1) Two Style D (Class A) or Style B (Class B) detection zones for smoke and/or heat detectors.
2) One Style D (Class A) or Style B (Class B) manual zone.
3) One Style B (Class B) supervisory initiating device circuit.
4) Two Style Y (Class B) indicating appliance circuits.
5) One (Class B) abort circuit.
6) One (Class B) releasing circuit.
7) Pre-discharge timer selectable from 0 to 60 seconds with 4 modes of activation for the smoke/heat detector circuits. The
predischarge time is also switch selectable to be 0 or 30 seconds upon activation of the manual circuit.
Mode 1 - Single zone activation
Mode 2 - Cross zone activation
Mode 3 - Sequential activation
Mode 4 - Cross zone or Sequential activation
Note: Mode 3 or 4 requires the use of Hochiki detectors with HSB-221 or YBA-M21 bases.
8) Discharge Timer selectable for two minutes or continuous.
9) 32 character alpha-numeric display with backlight indicating all alarm, trouble and supervisory conditions in an English
format.
10) One man test feature
11) Compatible with 2 and 4-wire detectors.
12) Power limited circuits
13) Single alarm/trouble silence switch.
14) Semi-flush mounting option.
15) 24 or 90 hour battery standby available.
16) Main board is removable without disconnecting field wiring.
ORDERING INFORMATION
Model No. Description Stock No.
PFC 2000RC Fire Control/Releasing Panel 3005800 (wht.), 3005802 (red)
PFC-TR Semi-Flush Mounting Trim (white) 5090107
PFC-TW Semi-Flush Mounting Trim (red) 5090114
BT-40 Battery, 12 Volt, 4.0 AH, 24 hr. Standby (2 required) 5130092
BT-80 Battery, 12 Volt, 8.0 AH, 60 hr. Standby (2 required) 5130084
BT-120 Battery, 12 Volt, 12.0 AH, 90 hr. Standby (2 required) 5130090
ARM-1 Optional 4PDT Relay Assembly 3004726
ARM-2 Optional DPDT Relay Assembly 3004725
Spare or Replacements Parts:
EOL Resistor 5080600
EOL Resistor and Diode Assembly for releasing circuit 3005012
Main Circuit Board Module 3005810
Power Supply Module 3004520
Transformer Assembly 3001172
WARNING: This equipment generates, uses and can radiate radio frequency energy. If not installed and used in accordance
with the instruction manual, this product may cause interference to radio communications. This product has been designed to
provide reasonable protection against such interference when operated in a commercial environment. Operation of this equip-
ment in a residential area is likely to cause interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
SPECIFICATIONS
firealarmresources.com

6
PFC 2000RC •5403521-REV N•3/03
HOUSING:
Type: General purpose, indoor, steel enclosure with hinged removable cover and key lock.
Size: 18 1/2" X 14 1/4" X 4 3/4"
Finish: Baked enamel, off-white with grey trim and red logo. Available in other colors and private labeling as
required by users (consult factory).
Knockouts: 8 combination 1/2" - 3/4" knockouts. 2 on each side, top and back.
Option: Bezel for semi-flush mounting in a 4" wall.
VISUAL INDICATORS (With door closed):
AC ON: Green LED comes on when AC voltage reaches 102 Volts, goes off when AC voltage drops below 96
Volts.
Alarm: Red LED comes on when a zone is in alarm condition.
Discharged: Red LED comes on when releasing circuit is activated.
Supervisory: Yellow LED comes on for supervisory condition.
System Trouble: Yellow LED comes on for any trouble condition. Possible conditions are Ground Fault, Initiation
Device Circuit Trouble, Supervisory Zone Activation, Supervisory Circuit Trouble, Indicating Appli-
ance Circuit Trouble, Abort, Abort Circuit Trouble, Battery Trouble, Zone Disable switch operated,
Auto Reset switch operated, AC Voltage Trouble, Releasing Circuit disabled.
LCD: A two line, 32 character alpha-numeric liquid crystal display displays the condition, status and circuit
for all Alarm, Trouble and Supervisory conditions as illustrated. The time to discharge is shown when
the pre-discharge timer has been activated.
PANEL VISUAL DISPLAY
firealarmresources.com

7
PFC 2000RC •5403521-REV N•3/03
CONDITION STATUS CIRCUIT SECSTODISCHARGE
Alarm Low 1 0 - 60
Trouble Silenced 2
Supv. Aborted Manual
Ground Supervisory
Disabled Abort
Discharge Signaling
AC Discharge
Battery
Aux. Power
NOTES: 1) All zones that are in alarm will be displayed simultaneously in the “circuit” area of the display.
Example: “1 2 Manual” would be displayed if all were in alarm.
2) If an alarm condition exists it will remain on the display. If more than one condition exists other than an alarm
condition, the display will be scrolled every 2 seconds.
3) The backlight on the LCD display is off when the AC power is off except when an alarm condition exists. If the
TEST SWITCH is operated during the absence of AC power, the backlight illuminates.
CONTROL SWITCHES
SILENCE SWITCH: Momentary switch silences built in buzzer and devices connected to the indicating appliance circuit.
This will not disable any visual or other alarm outputs such as the electronic outputs or the auxiliary
contacts. Any additional trouble or alarm conditions will reactivate the appropriate circuits.
RESET SWITCH: Momentary switch resets all alarm circuits if the condition has been corrected. Removes power from
the alarm initiating device circuit and also from the auxiliary power circuit if this mode has been
selected. The reset switch must be held for a minimum of 3 seconds. This is to avoid accidental
reset.
TEST SWITCH: Momentary switch activates all indicators, trouble, and alarm outputs. These all return to normal
when the switch is released. If the TEST SWITCH is operated during the absence of AC power, the
backlight illuminates.
ZONE DISABLE
SWITCHES: Supervised switches which disable the associated zone, inhibiting trouble and alarm outputs for the
specified zone (Zone 1 or Zone 2). Operating either of these switches will generate a system trouble
and a zone trouble. When the panel is operated in “cross zone” mode, disable either Zone 1 or Zone
2 to effectively disable both zones for an alarm condition.
AUTO RESET
SWITCH: A supervised switch which disables the latching feature of the alarm initiating device circuits for test
purposes. Operation of this switch will generate a system trouble.
RELEASING
CIRCUIT DISABLE
SWITCH: A supervised switch which disables the releasing circuit. Operation of this switch generates a system
firealarmresources.com

8
PFC 2000RC •5403521-REV N•3/03
trouble.
ALARM INITIATING DEVICE CIRCUITS
Two circuits for smoke and/or heat detectors, maximum detector load 2.5mA
Circuits are switch selectable for Style D or B (Class A or B)
Circuits are latching and power limited
Maximum line resistance is 25 ohms
Maximum short circuit loop current is 80 mA
Maximum open circuit loop voltage is 26.4 Volts with 132 Volts AC input
Minimum voltage at end of line resistor is 16 Volts with 20.4 Volts DC input
Minimum loop current required for alarm is 15 mA
Normal standby loop current is 5 mA
Maximum impedance on loop for alarm is 1500 ohms
Maximum impedance on loop for 2nd alarm (when a sequential mode is selected) 560 ohms
End of line resistor is 5.1k ohms
Minimum time to reset is 3 seconds
MANUAL INITIATING DEVICE CIRCUIT
One circuit for manual stations, switch selectable Style D or B (Class A or B)
Circuit is latching and power limited
Maximum loop resistance is 100 ohms
Maximum short circuit loop current is 8 mA
Minimum line current required for alarm is 5 mA
Normal standby loop current is 3 mA
End of line resistor is 5.1k ohms
Minimum time to reset is 3 seconds
SUPERVISORY INITIATING DEVICE CIRCUIT
One Class B circuit
Circuit is non-latching and power limited
Maximum line resistance is 100 ohms
Maximum short circuit loop current is 8 mA
Normal standby loop current is 3 mA
End of line resistor is 5.1k ohms
Current increase causes a supervisory signal and system trouble
Current decrease causes a supervisory trouble and system trouble
INDICATING APPLIANCE CIRCUITS
Two Style Y (Class B) circuits that reverse polarity on alarm
Circuits are power limited
Each circuit rated 24 Volt DC 1 Amp maximum
Normal standby loop current is 3 mA
End of line resistor is 5.1k ohms
Three switch selectable modes of operation:
Mode 1 - Steady on first alarm, pulsing upon activation of predischarge timer.
Mode 2 - Pulsing on first alarm, steady upon activation of predischarge timer.
Mode 3 - One circuit activated on first alarm. Second circuit activated upon activation of predischarge timer.
Note: If the predischarge timer is set to 0 the change in operation described above will occur at the time of release of
the extinguishing agent.
firealarmresources.com

9
PFC 2000RC •5403521-REV N•3/03
RELEASING CIRCUIT
One Class B circuit
Circuit is power limited
Circuit is rated 24VDC at 1 Amp continuous, 3 Amps intermittent
Reverses polarity to release extinguishing agent
Operates at the end of the pre-discharge timer period (or upon actuation of a manual alarm if this mode is selected for the
manual alarm circuit.)
Minimum battery voltage that will maintain 85 - 100% of solenoid voltage = 22.5 Volts
Maximum allowable line resistance = 2 ÷ CURRENT (IN RELEASE MODE)
Maximum short circuit loop current is 8 mA (in standby condition)
Normal standby loop current is 3 mA
End-Of-Line resistor is 5.1k ohms
ABORT CIRCUIT
One Class B switch circuit
Circuit is power limited
Maximum loop resistance is 100 ohms
Maximum short circuit loop current is 8 mA
Normal standby loop current is 3 mA.
End-Of-Line resistor is 5.1k ohms
Two switch selectable modes of operation:
Mode 1 - The release of the extinguishing agent is delayed as long as the abort switch is activated. Deactivation of the
abort switch will result in the release of the extinguishing agent within 10 seconds if the 60 second delay period
has elapsed.
Mode 2 - (IRI Mode) If the abort switch is actuated prior to the actuation of a second alarm, the pre-discharge timer will
not start. If the abort switch is restored after the second alarm, subsequent actuation of the abort switch will not
interrupt the operation of the pre-discharge timer. Actuation of the abort switch after a second alarm will not
interrupt operation of the pre-discharge timer.
PRE-DISCHARGE TIMER
Switch selectable from 0 to 60 seconds in 10 second increments, with 4 switch selectable modes of operation for the smoke/heat
detector circuits (the predischarge circuit, also switch selectable, to be 0 or 30 seconds upon activation of the manual circuit):
Mode 1 Single Zone - Actuation of one or more detectors will create an alarm condition and start the pre-discharge timer (this
mode is usually used with heat detectors).
Mode 2 Cross Zone - Actuation of one or more detectors in any one zone will create an alarm condition. Actuation of one or
more detectors in both zones, in addition to creating an alarm condition will start the pre-discharge timer (this mode is usually
used with smoke detectors).
Mode 3 Sequential - Actuation of one detector in any one zone will create an alarm condition. Actuation of a second detector
in the same zone will start the pre-discharge timer (this mode is usually used with smoke detectors).
Mode 4 Sequential or Cross Zone - Actuation of one detector in any zone will create an alarm condition. Actuation of two
detectors in the same zone, or one detector in each zone will start the pre-discharge timer (this mode is usually used with smoke
detectors).
Manual Circuit Activation - Activation of one or more devices on the Manual Device Circuit will create an alarm condition.
The output of this circuit is switch selectable to start a 30 second pre-discharge timer or to immediately activate the releasing
circuit. Activation of this circuit overrides abort.
DISCHARGE TIMER
firealarmresources.com

10
PFC 2000RC •5403521-REV N•3/03
Switch selectable periods of 2 minutes or continuous.
POWER REQUIREMENTS
Input: 117VAC single phase, 60 Hertz, 100V Amps maximum
Standby: 24VDC, 85mA
Standby Batteries: Gel cell sealed lead-acid batteries
Must be sized to provide the required standby period. 24 or 90 hours depending on the service required.
Alarm: 24 Volts - 240mA for first 2 mins. max., then 200mA.
AUXILIARY POWER OUTPUT
Regulated 24VDC, 500mA max.
Three terminal connections: one common negative, one positive that is interrupted on reset (for use with 4-wire detectors), and
one positive that is constant.
AUDIBLE INDICATOR
Built in buzzer operates on trouble conditions.
ELECTRONIC OUTPUTS
24VDC, 25mA with current limiting to 45mA for each of the following:
Alarm per zone (3)
System Trouble
Releasing Circuit activated
System Alarm
Supervisory
Output for optional 4 pole relay (see below)
AUXILIARY CONTACT OUTPUTS
System Alarm: 1 set SPDT (Form C)
System Trouble: 1 set SPDT (Form C)
Contacts rated 30 Volts, 2 Amps Resistive
Option: System Alarm output - 4PDT (4 pole double-throw)
Contacts rated 30VDC/120VAC, 5 Amps Resistive
MAIN CIRCUIT BOARD MODULE
The Main Circuit Board Module is removable without disconnecting the field wiring.
TERMINATION
AC power input terminals and grounding terminal are capable of handling #12 AWG conductors. All other terminals are
capable of handling #14 AWG conductors.
OPERATING TEMPERATURE RANGE
32 to 120 degrees Fahrenheit
0 to 49 degrees Celsius
}Use power limited and/or Class 2 source only
firealarmresources.com

11
PFC 2000RC •5403521-REV N•3/03
APPROVALS AND LISTINGS
UL and CSFM listed, FM approved, NYMEA accepted.
SERVICE USE
NFPA 12 - Carbon Dioxide Extinguishing Systems
NFPA 12A - Halon 1301 Fire Extinguishing Systems
NFPA 12B - Halon 1211 Fire Extinguishing Systems
NFPA 13 - Installation of Sprinkler Systems
NFPA 17 - Dry Chemical Extinguishing Systems
NFPA 72 - Local, Central Station (PPU), Proprietary (PPU), NFAC
BASIC CIRCUIT OPERATION
DESCRIPTION OF SEQUENTIAL MODE:
Actuation of one detector in any one zone will create an alarm condition. Actuation of a second detector in the same zone will
start the pre-discharge timer (this mode is usually used with smoke detectors).
DESCRIPTION OF CROSS-ZONING MODE:
Actuation of one or more detectors in any one zone will create an alarm condition. Actuation of one or more detectors in both
zones, in addition to creating an alarm condition will start the pre-discharge timer. This mode is usually used with smoke
detectors.
ALARM CONDITION:
Provided all associated switches are in their normal condition an increase of current on any alarm initiating device circuit to
approximately 15mA or greater will result in the following:
1) The zone or zones that have been activated will be displayed along with the word “ALARM” on the alpha-numeric
display.
2) Operation of the red alarm LED.
3) Operation of the auxiliary alarm contacts.
4) Positive 24 VDC will appear on the associated zone electronic output terminal.
5) Operation of one or both of the indicating appliance circuits depending on how they are programmed.
TROUBLE CONDITIONS:
Microprocessor failure: The yellow “System Trouble” indicator will be on; the “Trouble” buzzer will be pulsating and you will
be unable to silence the buzzer by operating the trouble silence switch. To silence the buzzer, disconnect the battery and turn off
the AC power. After 30 seconds reapply power. If the trouble still exists, call the factory. The supervision of the microproces-
sor is a safeguard feature that is built into the panel.
Other System Trouble: System trouble conditions will result in the following common trouble indications.
1) Operation of the system trouble LED.
2) Operation of the built-in trouble buzzer.
3) Operation of the auxiliary trouble contacts.
INITIATING DEVICE CIRCUITS RESPONSE:
A decrease in current to approximately 3 mA or operation of the zone disable switch to the disable position on any initiating
device zone will result in the following:
1) The zone or zones that are affected will be displayed along with the word “TROUBLE” on the alpha-numeric display.
If more than one trouble condition exists the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
firealarmresources.com

12
PFC 2000RC •5403521-REV N•3/03
ABORT CIRCUIT RESPONSE:
A decrease of current to approximately 1.5mA in the abort circuit will result in the following:
1) The words “ABORT” and “TROUBLE” will be displayed on the alpha-numeric display. If more than one trouble condi-
tion exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
INDICATING APPLIANCE AND RELEASING CIRCUITS RESPONSE:
An increase of current to approximately 8 mA or a decrease of the current to approximately 1.5 mA in either the indicating
appliance circuit or the releasing circuit, or connecting an indicating appliance backward will result in the following:
1) The zone or zones that are affected will be displayed along with the word “TROUBLE” on the alpha-numeric display. If
more than one trouble condition exists the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
NOTE: A current in excess of 1.5 Amps on a indicating appliance circuit when the panel is in the alarm condition will result in
an indicating appliance circuit trouble as described above. Manual operation of the reset switch is required to correct the
trouble condition.
CAUTION: A problem in a device that is connected into the indicating appliance circuit may not be apparent when the panel is
in the normal condition. If the indicating appliance circuit indicates a trouble condition when the panel is in an alarm condition
the problem must be located and corrected.
SUPERVISORY CONDITION:
An increase in current to approximately 4.5 mA or greater in the supervisory circuit will result in the following:
1) The words “SUPV” and “SUPERVISORY” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
3) The yellow supervisory LED will be lit.
4) Positive 24 Volts DC will appear on the associated electronic output terminal.
ABORT CONDITION:
An increase in current to approximately 4.5mA or greater in the abort circuit will result in the following:
1) The words “ABORT” and “ABORTED” will be displayed on the alpha-numeric display. If more than one trouble condi-
tion exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
3) If the abort circuit is in “Mode 1” the release of the extinguishing agent will be delayed as long as this circuit is activated.
4) If the abort circuit is in “Mode 2” (IRI mode) and this circuit is activated before a second alarm occurs the pre-discharge
timer will not start. If this circuit is activated after a second alarm has occurred, it will not interrupt operation of the pre-
discharge timer.
GROUND FAULT:
A Ground Fault on any circuit that is powered by the control panel will result in the following:
1) The words “TROUBLE” and “GROUND” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
firealarmresources.com

13
PFC 2000RC •5403521-REV N•3/03
LOSS OR REDUCTION OF AC POWER:
A loss or reduction in AC input voltage will result in the following:
1) The words “TROUBLE”, “LOW”, and “AC” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
3) The green AC-ON LED will be extinguished.
AC CIRCUIT BREAKER OPERATION:
Operation of the AC circuit breaker will result in the same indication as a loss or reduction of AC power condition. The LED
adjacent to the circuit breaker, located on the power supply board, will be illuminated.
HIGH OR LOW BATTERY VOLTAGE:
A loss of battery voltage, a reduction of battery voltage to 23 V or less, or an increase of battery voltage to 29 V or more will
result in the following:
1) The words “TROUBLE” and “BATTERY” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
BATTERY CIRCUIT BREAKER OPERATION:
Operation of the Battery circuit breaker will result in the same indication as a high or low battery voltage condition. In addi-
tion, the LED adjacent to the circuit breaker, located on the power supply board, will be illuminated.
AUXILIARY POWER FAILURE:
Failure of the auxiliary power supply will result in the following:
1) The words “TROUBLE” and “AUX. POWER” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
DISCHARGE CIRCUIT DISABLED:
Operating the discharge circuit disable switch to the “disabled” position will result in the following:
1) The words “DISCHARGE” and “DISABLED” will be displayed on the alpha-numeric display. If more than one trouble
condition exists, the conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs (see “Common Trouble Outputs”).
AUTO RESET SWITCH:
Operating the Auto Reset Switch to the “AUTO RESET” position will result in the following:
1) The words “AUTO RESET” will be displayed on the alpha-numeric display. If more than one trouble condition exists, the
conditions will be alternately scrolled every 2 seconds.
2) Operation of all of the common trouble outputs except the buzzer (see “Common Trouble Outputs”).
COMMON TROUBLE OUTPUTS:
The common trouble outputs respond with any of the trouble conditions in a manner as follows:
1) Operation of the built-in trouble buzzer.
2) Transfer of the auxiliary trouble contacts.
3) Positive 24 VDC will appear on the associated electronic output terminal.
4) Illumination of the yellow trouble LED.
firealarmresources.com

14
PFC 2000RC •5403521-REV N•3/03
SILENCING AN ALARM OR TROUBLE CONDITION:
Operate the momentary type Silence switch.
CAUTION: Where audible and/or visual indicators are being used as an evacuation signal, do not silence an alarm condition
without investigating and determining that an emergency condition does not exist.
RESETTING AN ALARM CONDITION:
1) Determine the cause of the alarm condition and if necessary remove the cause.
2) Operate the momentary type Reset switch and hold for approximately 3 seconds. This delay is to prevent accidental
resetting of the alarm condition.
RESETTING A TROUBLE CONDITION:
1) Determine the cause of the trouble condition and if necessary remove the cause.
2) Trouble conditions are self-restoring when the panel is operating in its normal mode. When all trouble conditions are
removed all indications will return to normal.
Exceptions:
1) When an initiating device zone is operated in a Style D (Class A) mode, any trouble condition on those zones will
require manual operation of the Reset switch to restore the panel to normal after the fault has been corrected.
2) A trouble condition of a indicating appliance circuit that is the result of a current in excess of 1.5 Amps when the
panel is in the alarm condition requires manual operation of the Reset switch.
SELECTING PANEL OPERATING CHARACTERISTICS:
Operating characteristics are selected by setting the two 8PST ( 8 Pole Single Throw) dip-switches that are located in the lower
right-hand corner of the main circuit board module. Switches are turned on by pressing them down on the right-hand side of
the switch.
SELECTING THE PRE-DISCHARGE TIME:
The time delay length of the pre-discharge timer is selectable from 0 to 60 seconds in 10 second increments. This time is set by
the top three dip-switch positions (with 1 being at the top) of the upper dip-switch as shown below.
Time in Seconds
Switch No. 010 20 30 40 50 60
1 OFF ON OFF ON OFF ON ON
2 OFF OFF ON ON OFF OFF ON
3 OFF OFF OFF OFF ON ON ON
SELECTING INITIATING DEVICE ZONE STYLE D OR B (CLASS A OR B):
Zones 1, 2 and the manual initiating device circuit can be selected to operate in either a Style D (Class A) or Style B (Class B)
mode. To place a circuit in a Style D mode turn the switch associated with that circuit “on” by pressing down on the right-hand
side of the switch.
Mode Circuit Switch No. Position
Style D (Class A) Zone 1 4 ON
Style D (Class A) Zone 2 5 ON
firealarmresources.com

15
PFC 2000RC •5403521-REV N•3/03
Style D (Class A) Manual Ckt. 6 ON
SELECTING INDICATING APPLIANCE CIRCUIT MODE:
There are 3 modes of operation for the indicating appliance circuit. Select the desired mode by setting switches 7 and 8 as shown
in the following:
Mode Operation Switch No. Position
1 Steady on first alarm, pulsating on second alarm or upon 7 ON
activation of manual circuit. 8 OFF
2 Pulsing on first alarm, steady on second alarm or upon activation of 7 OFF
manual circuit. 8 ON
3 No. 1 circuit activated on first alarm, No. 2 circuit activated on 7 ON
second alarm or upon activation of manual circuit. 8 ON
Note: Pulse time period is approximately 1/2 second.
SELECTING THE PRE-DISCHARGE TIMER ACTIVATION MODE:
There are 4 modes of starting the pre-discharge timer from zones 1 and/or 2. Select the desired mode by setting switches 9 and
10 as shown in the following:
Mode Operation Switch No. Position
1 Single zone activation 9 ON
10 OFF
2 Cross zone activation 9 OFF
10 ON
3 Sequential activation 9 ON
10 ON
4 Sequential or cross zone (any 2 detectors) 9 OFF
10 OFF
NOTE: Mode 3 or 4 requires the use of Hochiki detectors and HSB-21 or YBA-M21 bases.
ACTIVATION FROM MANUAL CIRCUIT:
In addition to the above activation modes, there are two modes of activation from the manual device circuit. Select the desired
mode by setting switch 11 as shown in the following:
Mode Operation Switch No. Position
1 Immediate discharge upon activation of the manual circuit. 11 OFF
2 30 second delay of discharge after activation of the manual circuit. 11 ON
firealarmresources.com

16
PFC 2000RC •5403521-REV N•3/03
SELECTING ABORT CIRCUIT OPERATING MODE:
There are two modes of operation for the abort circuit. Select the desired mode by setting switch 12 as shown in the following:
Mode Operation Switch No. Position
1 Releasing circuit is delayed as long as the abort circuit is activated. 12 OFF
2 (IRI applications) Pre-discharge timer will not start if abort circuit is 12 ON
activated before second alarm occurs.
SELECTINGDISCHARGETIME:
There are two modes of operation for the releasing circuit. Select the desired mode by setting switch 13 as shown in the following:
Mode Operation Switch No. Position
1 Releasing circuit operating time 2 minutes 13 OFF
2 Releasing circuit operating time continuous 13 ON
NOTE: For use in sprinkler systems installed in accordance with the requirements of NFPA 13, either (a) switch 13 must be
programmed “on” to provide continuous operation of the releasing device circuit or (b) the alarm trip valve must be of the
latching type, such that water will continue to flow through the sprinkler system if power is removed.
INSTALLATION INSTRUCTIONS
NOTE: Please read the entire manual before attempting to install this panel.
Use wire routing drawing on page on page 28.
CAUTION: This panel, associated wiring and devices should be installed and maintained in accordance with Section 760, Fire
Protection Signaling Systems, and all other applicable Sections of the National Electrical Code, NFPA 72 - National Fire Alarm
Code (Central Station, Proprietary and Local), all local codes and the authority having jurisdiction.
Review the circuit parameters listed in the “Specifications” section of this manual before installing the panel.
CAUTION: Do not install the diode/resistor assembly across terminals 5 and 6. For testing install a 5.1K resistor only. Install
diode/resistor assembly at solenoid location.
PROCEDURE FOR THE REMOVAL OF THE MAIN BOARD MODULE:
1) If the module is being removed for replacement, disconnect the AC and battery power by pulling out the black pins on
the two circuit breakers that are located at the upper right hand corner of the power supply board.
2) Disconnect the power cable, accessible at the cutout on the left side of the main panel.
3) Remove the 16 point terminal from the top left hand side of the panel by pulling upward.
4) Pull out the two top corner locks or remove the screws.
5) Hold the top of the panel out approximately 1/2".
6) Insert a screwdriver between the ends of the terminal strip and the panel at the points indicated by the arrows.
7) Pry the panel toward the top of the housing. Hold onto the Main Board Module tightly. The Main Board Module should
become free of the terminal strip at which time it may be removed from the panel.
LOCATION:
This unit should be installed in a dry location where it will not be exposed to temperature extremes. This unit should be
mounted in a convenient location approximately 5 feet from the floor where it will be accessible for testing and servicing.
NOTE: Mounting the unit too high will make the alpha-numerical display difficult to read. The display is most visible when
firealarmresources.com

17
PFC 2000RC •5403521-REV N•3/03
viewed at eye level. The viewing angle can be adjusted slightly by the adjustment located just below the display.
MOUNTING THE BEZEL:
1) This unit may be surface mounted or semi-flush mounted by using the optional trim bezel. For semi-flush installations mount
the housing so that the front edge protrudes 1" from the finished wall surface.
2) The main panel should be removed before attempting to mount the cabinet. For instructions on removal of the Main Board
Module, refer to “Procedure for the Removal of the Main Board Module”.
3) Install all required conduits, external wiring and devices making all connections that are external to the panel.
4) If this is a semi-flush mount installation, after the wall surface is finished, slide the trim bezel in place and fasten with four
#6-32 screws as shown below.
INSTALLATION OF BEZEL FOR SEMI-FLUSH INSTALLATIONS
WIRINGHOOKUP:
1) With the AC power turned off at the circuit breaker panel, connect the 120VAC HOT, NEUTRAL and GROUND wire to the
terminal block as shown on the power supply connection drawing. Verify that the transformer cable is securely connected.
2) Connect all the other wiring to the terminals as shown in the main board connection drawings. Plug the main board into the
card edge connection portion of the terminal strip. Plug the power cable into the main board. Turn the AC power on.
Observing proper polarity, connect the standby batteries with the cable provided.
3) The operation of the complete system should be verified as outlined in the test procedure section.
TEST PROCEDURES
CAUTION: The system should be inspected and tested in compliance with NFPA-72 National Fire Alarm Code or the authority
having jurisdiction.
1) Notify the fire department or other receiving station of alarm, supervisory, and/or trouble signals that will be transmitted.
2) Notify the proper building personnel so that audible and/or visual, signals can be disregarded during testing.
3) Remove the two wires from the releasing circuit, reverse and reconnect them. The panel should go to a trouble condition
and remain there (if the panel restores to a normal condition when the leads are reversed it indicates that the diode in the
end of the line assembly is open and the solenoid valve can not operate until the entire EOL assembly, part #3005012, is
replaced). Disconnect and restore the leads to their correct position. The panel should restore to a normal condition.
4) Operate the Releasing Circuit Switch to the disable position. This will cause a trouble condition.
5) Momentarily operate the Test/Reset switch to the Test position. This will cause all audible and visual indicators to activate.
Releasing the Test switch will restore the panel to the condition it was in prior to operation of this switch.
6) Operate each zone switch to the disable position. This should result in a trouble condition and operate all indicators as
described in the sections on “Trouble Conditions” and “Initiating Device Circuits Response”. Restoring the switch to the
enable position should restore all indicators to normal.
7) Momentarily open each of the following circuits:
A) Each initiating device zone. There is a brief delay when these circuits are in the Style D (Class A) mode.
B) Supervisory circuit.
firealarmresources.com

18
PFC 2000RC •5403521-REV N•3/03
7) Momentarily open each of the following circuits:
A) Each initiating device zone. There is a brief delay when these circuits are in the Style D (Class A) mode.
B) Supervisory circuit.
C) Indicating Appliance circuits.
D) Abort Circuit.
Verify that this results in a trouble condition and all indicators operated as described in the appropriate preceding section for
the particular circuit that is faulted.
8) Turn off AC power at the circuit breaker panel. The green "AC ON" LED will be extinguished. Verify that all the trouble
indicators described in the section on "Loss or Reduction of AC Power" occur. Operated the Reset/Test switch to the Test
position. All audible and visual indicators should operate. Restore the switch to normal. Restore the AC power.
9) Operate the Auto Reset switch to the on position.
10) Operated each alarm imitating device on all zones. All audible and visual devices should operated. These devices will cease to
operate after period of approximately 3 seconds. Power will automatically be removed from the initiating device circuit for
approximately 15 seconds. No alarm can be initiated during this period. If the imitating device has not been restore the panel
will go back into the alarm condition.
11) Operate each initiating device on the supervisory circuit. Verify that all the indications described in the section on
"Supervisory Conditions" occur.
12) Restore the Releasing Circuit Switch.
13) Return the Auto Reset switch to the off position. All the LED's on the panel except the green "AC ON" LED should be off. All
audible and visual indicators connected to the indicating appliance circuit should be off.
14) Notify all building personnel that the test has been concluded.
15) Notify the fire department or other receiving station that the test has been concluded.
OPERATING INSTRUCTIONS
Fill in the name, address and telephone number of the servicing agency on the instruction sheet provided and post in a
prominent place. There are two Operating Instruction sheets provided, one if abort mode 1 is used and the other if abort mode
2 is used.
BATTERY SIZE REQUIREMENTS
These panels require a 24 Volt gel-cell battery for proper operation. 24 hours of standby power is required for NFPA 722-
Central Station Systems, Local Systems and Proprietary Systems.
The chart below will assist you in selecting the proper size battery:
Battery Size Hours of Standby Maximum Auxiliary Current Load
4.0 AH 24 .100
8.0 AH 24 .175
8.0 AH 90 0
12.0 AH 24 .250
12.0 AH 90 .075
Note: Batteries rated above 10AH require a separate battery cabinet.
Alternate method of calculating battery size using the "Calculation Table" on page 19.
1)List in column #1 all devices used in the system, include all modules, bells, horns, door holders and smoke detectors (see Table
#1 or manufacturers specifications).
2) List in column #2 the quantity of each device.
3) List in column #3 the standby current of each device (exclude all indicating appliance devices).
4) List in column #5 the alarm current of each device.
5) For each line, multiply the figure in column #2 by the figure in column #3 and enter the product in column #4. Then multiply the
figure in column #2 by the figure in column #5 and enter the product in column #6.
6) Add the figures in column #3 and #6, then enter the sums in the appropriate Total mA box.
7) Convert these figures from milliampere to amperes by multiplying by .001, enter the product in the appropriate Total A box.
8) Multiply the standby total amperes by required time in hours from Table 2.
9) Divide the alarm total amperes by 12 for 5 min. or by 6 for 10 min. (see Table 2).
10) Add the standby AH and the alarm AH and divide this sum by .85 (Efficiency Factor). Select a battery that has an AH rating
above this figure but not less than 6.5 AH.
firealarmresources.com

19
PFC 2000RC •5403521-REV N•3/03
Use a battery with a higher AH rating than Required AH
INACTIVE CIRCUITS
All inactive alarm and supervisory initiating device circuits and indicating appliance circuits must have the end-of-line resistor
installed on the panel terminals. On circuits that have four terminals, this resistor must be on the outside two terminals.
Total mA
Convert to A
Total A
5 min/12 or 10 min/6
Total Alarm AH
+ Total Standby AH
Total AH
Efficiency Factor
Required AH
x .001
x____
x .001
÷__
÷.85
TABLE 1 CURRENT REQUIREMENTS
Module/Device Standby mA Alarm mA
PFC2000RC 85 240*
*Includes one zone short circuit current.
TABLE 2 SECONDARY POWER SUPPLY REQUIREMENTS
NFPA Standard Standby Time Alarm Time
NFPA-72 National Fire Alarm Code
•Central Station Systems 24 hrs. 5 mins.
•Local Systems 24 hrs. 5 mins.
•Proprietary Systems 24 hrs. 5 mins.
FMRC 1011 & 1012, Deluge & Pre-action Systems 90 hrs. 10 mins.
CALCULATION TABLE
12 3 4 5 6
Module/Device Quantity Standby mA Per Unit Total Standby Current Alarm mA Per Unit Total Alarm Current
Total mA
Convert to A
Total A
Multiply by hours from Table 2
Total Standby AH
firealarmresources.com

20
PFC 2000RC •5403521-REV N•3/03
PFC 2000RC MAIN BOARD CONNECTION DRAWING (IDENTIFIER "A")
USE WIRE ROUTING DRAWING, PAGE 28
NOTES:
1.) USE ONLY SMOKE DETECTORS THAT ARE LISTED
IN COMPATIBILITY LIST, ON INSIDE OF DOOR.
2.) ANY ZONE CAN BE OPERATED IN A CLASS A
MODE. PLEASE REFER TO INSTRUCTION
MANUAL. THE END- OF-LINE RESISTOR IS IN THE
PANEL WHEN CLASS A MODE IS USED.
3.) WHEN USED IN A SEQUENTIAL OR CROSS
SEQUENTIAL MODE USE ONLY HOCHIKI
DETECTORS WITH YBA-M21 OR HS-21D BASES.
4.) LEAVE END-OF-LINE RESISTORS ON INACTIVE
CIRCUITS.
5.) ALL CIRCUITS POWERED BY THIS CONTROL ARE
POWER LIMITED.
6.) COMBINED LOAD OF ALL EXTERNAL DEVICES
INCLUDING INDICATING DEVICES NOT TO
EXCEED 3 AMPS.
7.) AUX. CONTACTS RATED 2A 30 VDC
RESISTIVE.
ALL AUXILIARY CONTACTS ARE SHOWN IN
THE NORMAL CONDITION. NOT TO BE USED
FOR MOTOR LOADS OR PILOT DUTY
APPLICATION.
WARNING: EXCEEDING RECOMMENDED
RATINGS MAY VOID WARRANTY! USE
POWER LIMITED CIRCUIT AND/OR CLASS 2
SOURCE ONLY.
8.) AUXILIARY POWER 24V MAX.
FOR LIMITATIONS, SEE SECTION "BATTERY
SIZE REQUIREMENTS"
COMBINED LOAD ON THESE TERMINALS NOT TO
EXCEED 500 MA. MAX.
SEE SECTION ON "COMPATIBILITY DATA".
9.) FOR MAX. CURRENT, RESISTANCE, AND MIN. BATTERY
VOLTAGE, SEE SECTION ON "RELEASING CIRCUIT".
FOR LIST OF COMPATIBLE SOLENOIDS AND VALVES,
SEE SECTION ON "EXTINGUISHING AGENT CONTROL
VALVE COMPATIBILITY DATA".
10.) POLARITY SHOWN ON BELL AND RELEASING CIRCUITS
IS FOR NORMAL STANDBY CONDITION. REVERSES TO
ACTIVATE DEVICES. CONNECT THE NEGATIVE LEAD
OF THE INDICATING APPLIANCE TO THE POSITIVE
TERMINAL OF THE PANEL. CONNECT THE POSITIVE
LEAD OF THE INDICATING APPLIANCE
TO THE NEGATIVE TERMINAL OF THE
PANEL.
11.) END OF LINE DIODE ASSEMBLY (PART
#3005012) MUST BE LOCATED AT
SOLENOID VALVE LOCATION.
12.) COMBINED LOAD OF INDICATING AND
RELEASING CIRCUITS NOT TO EXCEED
2.5 AMPS.
13.) IF OPTIONAL AUXILIARY RELAY MODULE
ARM-2 IS USED ON THIS CIRCUIT, THE
ADDITIONAL POWER REQUIRED BY THE
RELAY MUST BE SUBTRACTED FROM
THE TOTAL CIRCUIT CURRENT NOTED.
SEE BULLETIN #5400977.
SEE APPLICATION NOTE 1 ON PAGE 21.
firealarmresources.com
Table of contents
Other Potter Control Panel manuals

Potter
Potter PFC-100RC User manual

Potter
Potter PFC-4064 Operating instructions

Potter
Potter PFC-6075R Owner's manual

Potter
Potter PFC-8000 Series User manual

Potter
Potter PFC-6006 Owner's manual

Potter
Potter PFC-6200 User manual

Potter
Potter PFC-5000 Series User manual

Potter
Potter PFC-3005T User manual

Potter
Potter PFC-6800 Owner's manual

Potter
Potter PFC-6075 Owner's manual
Popular Control Panel manuals by other brands

CSI Controls
CSI Controls Fusion Single Phase Simplex Installation and operation manual

HST
HST HST-HP201-2AB product manual

Helo
Helo Easy product manual

schmersal
schmersal SEPK 02.0 operating instructions

Bosch
Bosch Radionics D8024 Operation and installation guide

Azbil
Azbil Infilex AC Series Specifications & instructions