Powtier Controls Tactical 310 User manual

TC310VP
TEMPERATURE CONTROLLER
WITH VALVE POSITIONER OUTPUT
INSTRUCTION MANUAL
CONTENTS
DESCRIPTION..........................................................2
INSTALLATION.........................................................2
CONNECTIONS........................................................3
CONTROL ADJUSTMENTS.....................................4
TUNING.....................................................................5
ALARM SETTING.....................................................6
TECHNICAL SPECIFICATION.................................7
ORDERING INFORMATION.....................................8
SUPPLIER INFORMATION......................................8

TC310VP Instruction Manual Powtier Controls Limited
DESCRIPTION
The TC310VP is housed in a durable sheet metal and flame retardent plastic housing with display panel at
the front and wiring connections at the back. The seven segment LED display monitors measured value
continuously and the nine segment error bar shows the proximity to setpoint. Setpoint can be displayed by
depressing the setpoint changeover switch on the front panel. Setpoint adjustment is made by turning the
setpoint thumbwheel which is concealed behind the door on the front panel. Wiring connections are made at
the back by means of screw type connectors. All control adjustments are on the top of the instrument.
Dimensions
INSTALLATION
The instrument requires a 92X92mm panel cut out and is fixed by retainers positioned on the top and bottom
of the instrument. Maximum panel thickness is 10mm.
All external wiring is made to the rear of the instrument via M3 screw terminals.
14 March 1995 - 2 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
CONNECTIONS
Typical TC310VP wiring Schematic.
Terminal connection diagram.
14 March 1995 - 3 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
CONTROL ADJUSTMENTS
Control adjustments.
SID - Switching Integral & Derivative; the use of switches to change integral and derivative time constant
simplifies the procedures in obtaining optimum control.
P1 - Proportional Band of 2.5-15% can be adjusted through this control.
P2 – Not used.
P3 - Manual Reset (optional) can be used to remove the steady state error inherent in PD control.
P10 – Not used.
P11 – Not used.
P12 - High/Low/Band Alarm (optional - only one type on any instrument) can be used to give a warning when
the measured temperature exceeds the alarm limit.
P13 & 14 – Valve open and close respectively. Valve Travel Time governs the speed of the valve motor in
response to small error (or PID) output demands; fully counter clockwise gives the slowest response and fully
clockwise, the fastest response.
14 March 1995 - 4 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
TUNING
PID CONTROL TUNING PROCEDURE
1. Set P13 and P14 fully counter clockwise.
2. Set proportional band to minimum (P1 fully anticlockwise).
3. Set all SID switches to ’ON’ (11111111).
4. Adjust the setpoint to 10% below working temperature.
N.B. If it is undesirable for the system to overshoot the working temperature, perform the test at a further
reduced temperature.
5. Observe:-
a. Time (to) taken for the measured temperature to rise from the setpoint to a maximum.
b. Overshoot temperature (To) = maximum temperature - setpoint temperature.
6. Set the SID switches (see Table 1) to give ti = 4 x to. This will automatically set td = ti/9.
7. From the overshoot temperature, To, calculate the proportional band index PBI as follows:-
PBI = (To / TR) x 100
TR = 200 for -50 to 200 range
TR = 500 for -50 to 500 range
TR = 1000 for 0 to 999 range
and set the proportional band according to table 2.
8. Progressively reset P13 & P14 as far clockwise as possible without the introduction of system hunting.
Table 1. Switch settings for integral and derivative time constant.
SID ti td SID ti td
12345678 (minute) (minute) 12345678 (minute) (minute)
00000000 50 5.5 10001000 23 2.6
00010001 46 5.2 10011001 20 2.2
00100010 43 4.8 10101010 17 1.9
00110011 40 4.4 10111011 13 1.5
01000100 36.5 4.1 11001100 10 1.1
01010101 33 3.7 11011101 7 0.8
01100110 30 3.3 11101110 3 0.4
01110111 27 3.0 11111111 ON/OFF CONTROL
(For SID switch, 0 - off, 1 – on)
Table 2. Proportional band index.
P1 MARKING PBI P1 MARKING PBI P1 MARKING PBI
0 1 4 8.9 – 11.5 8 19.6 – 22.3
1 1 – 3.5 5 11.5 – 14.2 9 22.3 – 25.0
2 3.5 – 6.2 6 14.2 – 17.0 10 25
3 6.2 – 8.9 7 17.0 – 19.6
PD CONTROL (OPTIONAL) TUNING PROCEDURE
1. Turn the manual reset to minimum (P3 fully anticlockwise).
2. Proceed as for PID control tuning procedure, use table 1 to set SID to give td = 0.5 x to.
3. Turn P3 anticlockwise to eliminate any steady state error.
ON-OFF CONTROL (OPTIONAL) TUNING PROCEDURE
No adjustment is required for ON-OFF control.
14 March 1995 - 5 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
ALARM SETTING
PROCEDURE FOR SETTING ALARM ON TC310VP
For alarm setting purposes, the controller may be in either the control or the open loop mode, provided that
the input signal from the sensor to the controller remains steady at any convenient level during the short
period of time that it takes to set the alarm level.
1. STEPS IN SETTING UP A HIGH ALARM LEVEL
1.1 Ensure that the sensor input to the controller is at a steady temperature T1.
1.2 Turn the alarm setting control P12 fully clockwise.
1.3 Decide how many degrees above the set temperature the alarm must operate. Let this be t degrees.
1.4 By means of the thumbwheel, adjust the set temperature of the controller to be t degrees lower than the
sensor input temperature T1.
1.5 Adjust the alarm setting control P12 anti-clockwise until the alarm relay LED just comes on. The high
alarm will now operate at t degrees above any chosen set point temperature.
2. STEPS IN SETTING A LOW ALARM LEVEL
2.1 Ensure that the sensor input to the controller is at a steadytemperature T1.
2.2 Turn the alarm setting control P12 fully clockwise.
2.3 Decide how many degrees below the set temperature the alarm must operate. Let this be t degrees.
2.4 By means of the thumbwheel, adjust the set temperature of the controller to be t degrees higher than the
sensor input temperature T1.
2.5 Adjust the alarm settin congtrol P12 anti-clockwise until the alarm relay LED just comes on.The low alarm
will now operatre at t degrees below any chosen set point temperature.
3. STEPS IN SETTING UP A BAND ALARM
The band alarm operates when the actual temperature is t degrees higher than the set temperature or t
degrees lower than the set temperature. Therefore the band alarm may be set by setting up the high end in
the same manner as section one above or by setting the low end in the same manner as section two above.
14 March 1995 - 6 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
TECHNICAL SPECIFICATION
INPUT
Thermocouple Standard ASTM E230, BS4937, DIN 43710.
Cold junction compensation Automatic.
Thermocouple break protection Upscale fitted as standard, display shows "bbb." (b:blank)
Downscale fitted as an option.
Resistance Thermometer 2 or 3 wire Any lead resistance error is automatically reduced by
using 3 wires.
RTD (Pt 100) BS 1904, DIN 43760.
VALVE POSITION OUTPUT
Motor supply voltage 24Vac to 240Vac (EXTERNAL STEP DOWN
TRANSFORMER REQUIRED).
Output twin triacs rating 2Arms, 24Vac to 240Vac.
Feedback potentiometer 100 to 1000 Ohms.
CONTROL
PID control Proportional, Integral and Derivative.
Proportional band Xp 2.5% to 15% of span.
Integral time ti Switching integral time 5 to 40 minutes.
Derivative time td Switching derivative time 0.5 to 5 minutes.
PD control (option) Proportional and derivative.
Proportional band Xp 2.5% to 15% of span.
Derivative time td 0.5 to 5 minutes.
Manual reset PD control only, 0 to 50% output power at span.
ON/OFF control (option) Hysteretic 0.5% of span.
ALARMS OUTPUTS (option)
Relay Normally energised and de-energised in alarm
conditions. 2Aresistive at 230Vrms.
Alarm LED Flashing LED at fascia.
Low deviation Adjustable +0.5% to -8% of span.
High deviation Adjustable -0.5% to +8% of span.
Band deviation Adjustable 1.5% to 8% of span.
RETRANSMISSION SIGNAL (option)
Analogue signal 5V, 5mA max.m signal linear to span.
ENVIRONMENTAL
Supply voltage 115/230V +/-15% 50/60Hz
100/200V +10% -15% 50/60Hz.
Operating temperature 0 to 50 °C.
Storage temperature -20 to +80 °C.
PERFORMANCE
Indication accuracy Better than 0.5% of span +/-1 digit.
Supply voltage variation Negligible effect within operating range.
GENERAL
Display digit 3 digit 7 segment with negative sign display;
digit size 13mm height by 7.4mm width.
Error indication 9 LED display bar; central LED +/- 0.4% of span
+/-1 degree and +/-0.8% of span +/-1 degree
per LED above and below setpoint.
Dimensions 96x96x190mm.
Weight 2Kg maximum.
Power consumption 6VA maximum.
14 March 1995 - 7 - 310VPIM
Issue 2.0

TC310VP Instruction Manual Powtier Controls Limited
ORDERING INFORMATION
You are welcome to order by description or code.
310VP- - - - - - 00
INPUT......................................................................: : : : : :
SCALE................................................................................: : : : :
SUPPLY VOLTAGE......................................................................: : : :
VALVE POSITIONER OUTPUT............................................................: : :
OPTION...........................................................................................................: :
END OF CODE..........................................................................................................:
INPUT
Iron-Constantan (J) BS -50 to 500.....................1
Iron-Constantan (J) DIN -50 to 500...................30
Chromel Alumel (K) -50 to 500...........................2
Chromel Alumel (K) 0 to 999..............................3
Resistance Thermometer (PT100) -50 to 200...4
(Other range options on application)
SCALE
Degree Celsius.............................................................C
Degree Fahrenheit........................................................F
SUPPLY VOLTAGE
115/230V +/-15% 50/60Hz......................................................1
100/200V +10% -15% 50/60Hz..............................................2
VALVE POSITIONER OUTPUT
Control 24Vac motor........................................................................48
Control 120Vac or 240Vac motor....................................................49
OPTIONS
No option...................................................................................................01
Low deviation alarm...................................................................................21
High deviation alarm..................................................................................22
Band deviation alarm.................................................................................23
Two term PD Control.................................................................................31
On-off control.............................................................................................32
Downscale Thermocouple break protection..............................................61
Retransmission signal 0-5V 5mA max.)....................................................63
END OF CODE.........................................................................................................00
Please consult Sales office for other possible options and scales.
ORDER EXAMPLE:
1. A TC310VP with J-type thermocouple input (BS standard), scaled -50 to 500 °C, operating at 230V, valve
positioner control a motor having a supply voltage of 24Vac with high deviation alarm as option will have the
code:- 310VP-1-C-1-48-22-00.
SUPPLIER INFORMATION
Powtier Controls Limited
Unit 4, Parkland Business Centre
Chartwell Road, Lancing
West Sussex BN15 8UE England
Tel: +44(0)1903 750800
Fax: +44(0)1903 750678
Email: Email@PowtierControls.co.uk
14 March 1995 - 8 - 310VPIM
Issue 2.0
This manual suits for next models
1
Table of contents
Other Powtier Controls Temperature Controllers manuals