Pro-face ST-3400 Series User manual

1
ST-3400 Series
Installation Guide
Package Contents
(1) ST Unit (1)
(2) English and Japanese Installation Guides
(one of each) <This Guide>
(3) Warning/Caution Information (1)
(4) Installation Gasket (1)
(Attached to the ST unit)
(5) Installation Fasteners (Set of 4)
(6) Power Connector (1)
(7) USB Cable Clamp (1 set)
(Holder: 1, Cover: 1)
This unit has been carefully packed, with
special attention to quality. However, should
you find anything damaged or missing,
please contact your local ST distributor
immediately.
About the Manual
For the detailed information on ST3000
series, refer to the following manual.
•ST3000 Series Hardware Manual
•Maintenance/Troubleshooting
ST3000 Series Hardware Manual can be
selected from the help menu of GP-Pro EX or
downloaded from Pro-face Home Page.
URL
http://www.pro-face.com/otasuke/
Caution
Be sure to read the “Warning/Caution
Information” on the attached sheet before
using the product.

2
Part Names and Functions
Name Description
AStatusLED
B CF Card Access LED Lit in green when the CF Card is inserted and the cover
is closed, or when the CF Card is being accessed.
C Power Connector (Socket)
-
D USB Host Interface (USB)
USB1.1 Host I/F
Connector: USB TYPE-A x 1
Power supply voltage: 5VDC±5%
Output current: 500mA (max.)
The maximum communication distance: 5m
E Serial Interface (COM1) Dsub 9-pin plug type. RS232C is supported.
F Serial Interface (COM2) Dsub 9-pin plug type. RS422/RS485*1 is supported.
*1 RS485 is compliant with ST-3400 series units with revision code “A” or later.
Revision (page 11)
GCFCardCover
-
H Dip Switches Located inside the CF Card Cover.
Front Rear Right Side Bottom
(CF Card Cover Open)
A
B
E
F
C
DG
H
LED ST Status
Green (lit) Normal operation (power is ON.) or
OFFLINE operation.
Orange
(blinking) During software startup.
Red (lit) When power is turned ON.
Not lit Power is OFF.
SEE

3
General Specifications
Electrical Specifications
Environmental Specifications
Power Supply
Input Voltage DC24V
Rated Voltage DC19.2 to 28.8V
Allowable
Voltage Drop 10ms (max.)
Power
Consumption 22W (max.)
In-Rush
Current 30A (max.)
Voltage Endurance AC1000V 20mA for 1minute (between charging and FG terminals)
Insulation Resistance DC500V 10MΩ(min.) (between charging and FG terminals)
Physical
Surrounding Air
Temperature 0 to +50°C
Storage
Temperature -20 to +60°C
Ambient Humidity 10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Storage Humidity 10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Dust 0.1mg/m3and below (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment.

4
External Interfaces
• This ST unit’s serial interface is not isolated.When the host (PLC) unit is also not iso-
lated, and to reduce the risk of damaging the RS232C/RS422/RS485 circuit, be sure
to connect pin #5 SG (Signal Ground) terminal.
• Similarly shaped connectors are used for COM1 and COM2 of the ST. Therefore, be
sure to connect the correct connectors. Communication is not available unless the
connectors are connected correctly.
• When isolation is necessary, you can use the RS232C isolation unit (CA3-ISO232-01) on
COM1.
COM1
Recommended Cable Connector XM2D-0901 <made by OMRON Corp.>
Recommended Jack Screw XM2Z-0073 <made by OMRON Corp.>
Recommended Cable Cover XM2S-0913 <made by OMRON Corp.>
Interfit Bracket #4-40 inch screws are used.
Pin # RS232C
Signal Name Meaning
1 CD Carrier Detect
2 RD(RXD) Receive Data
3 SD(TXD) Send Data
4 ER(DTR) Data Terminal Ready
5 SG Signal Ground
6 DR(DSR) Data Set Ready
7 RS(RTS) Request to Send
8 CS(CTS) Clear to Send
9CI(RI)/VCC
Called status display/
+5V±5% Output 0.25A*1
*1 The RI/VCC selection for Pin #9 is switched via software. The VCC output is not protected against
overcurrent. To prevent damage or unit malfunctions, use only the rated current.
Shell FG Frame Ground
(Common with SG)

5
COM2
Recommended Cable
Connector XM2D-0901 <made by OMRON Corp.>
Recommended Jack Screw XM2Z-0073 <made by OMRON Corp.>
Recommended Cable Cover XM2S-0913 <made by OMRON Corp.>
Interfit Bracket #4-40 inch screws are used.
Pin # RS422/RS485*1
*1 RS485 is compliant with ST-3400 series units with revision code “A” or later.
Revision (page 11)
Signal Name Meaning
1 RDA Receive Data A(+)
2 RDB Receive Data B(-)
3 SDA Send Data A(+)
4 ERA Data Terminal Ready A(+)
5 SG Signal Ground
6 CSB Clear to Send B(-)
7 SDB Send Data B(-)
8 CSA Clear to Send A(+)
9 ERB Data Terminal Ready B(-)
Shell FG Frame Ground
(Common with SG)
SEE

6
Installations
1. Installation Requirements
• For easier maintenance, operation, and
improved ventilation, be sure to install the
ST at least 100 mm [3.94 in.] away from
adjacent structures and other equipment.
• Be sure that the ambient operation temper-
ature and the ambient humidity are within
their designated ranges. (Ambient opera-
tion temperature: 0 to 50°C, Ambient
humidity: 10 to 90%RH, Wet bulb temper-
ature: 39°C max.)
When installing the ST on the panel of a cab-
inet or enclosure, “Ambient operation tem-
perature” indicates both the panel face and
cabinet or enclosure’s internal temperature.
• Be sure that heat from surrounding equip-
ment does not cause the ST to exceed its
standard operating temperature.
2. ST Installation
(1) Create a Panel Cut following the dimen-
sions in the table below.
(2) Confirm that the installation gasket is
attached to the ST unit and then place the
ST unit into the Panel from the front.
• It is strongly recommended that you
use the installation gasket, since it
absorbs vibration in addition to repel-
ling water.
For the procedure for replacing the
installation gasket, refer to “ST3000
Series Hardware Manual”.
(3) The following figures show the four (4)
fastener insertion slot locations. Insert
each fastener’s hook into the slot and
tighten it with a screwdriver. Insert the
installation fasteners securely into the
insertion slot recess.
100
[3.94]
100
[3.94]
100
[3.94] 100
[3.94]
Unit:mm[in.]
100
[3.94]
100
[3.94]
100
[3.94]
Panel Face Inside Cabinet
X Y Panel thickness
204.5
[8.05 ]
159.5
[6.28 ]
1.6[0.06]
to
10.0[0.39]
Unit: mm [in.]
XUnder
4-R3[0.12] Panel
thickness
ST
Y
+1
-0
+0.04
-0
+1
-0
+0.04
-0
Top
Bottom
Insertion
Slots

7
• Tightening the screws with too much
force can damage the ST unit’s plastic
case.
• The necessary torque is 0.5N•m.
Wiring
yTo avoid an electric shock, prior to
connecting the ST unit’s power cord
terminals to the power terminal block,
confirm that the ST unit’s power supply is
completely turned OFF, via a breaker, or
similar unit.
yAny other power level can damage both
the ST and the power supply.
yWhen the FG terminal is connected, be
sure the wire is grounded.
1. Wiring the DC type power supply
cable
Power Cord Specifications
Use copper conductors only.
Power Connector (Plug) Specifications
• The power connector (plug) is CA5-
DCCNM-01 made by Pro-face or
MSTB2,5/3-ST-5,08 made by Phoenix
Contact.
Insertion Slot Recess
Hook the fastener on the
Recess,
Panel Installation Fastener
ST Hook and secure the fastener
on the panel with a
screw.
Power Cord
Diameter 0.75 to 2.5mm2
[0.0009 to 0.0097 inch2]
(18 - 12 AWG)
Conductor
Type Simple or Stranded Wire*1
*1 If the Conductor’s end (individual) wires are
nottwistedcorrectly, theendwiresmayeither
short against each other, or against an
electrode.
Conductor
Length
+ 24V
-
0V
FG
Grounding
Terminal
connected
to the ST
chassis
7 mm
[0.28in]
Insertion
Direction
+
-
FG

8
When connecting the Power Cord, use the
following items when performing wiring.
(Items are made by Phoenix Contact.)
Connecting the ST Power Cord
(1) Confirm that the ST unit’s Power Cord is
unplugged from the power supply.
(2) Strip the power cord, twist the
conductor’s wire ends, insert them into
the pin terminal and crimp the terminal.
Attach the terminal to the power
connector.
• Use a flat-blade screwdriver (Size 0.6
X 3.5) to tighten the terminal screws.
The torque required to tighten these
screws is 0.5 to 0.6 N•m [5-7Lb•In.].
• Do not solder the cable connection.
(3) Attach the Power connector(Plug) to the
Power Connector.
2. Power Supply Cautions
• Input and Output signal lines must be sepa-
rated from the power control cables for
operational circuits.
• To improve the noise resistance, be sure to
twist the ends of the power cord wires
before connecting them to the Power con-
nector (Plug).
• The ST unit’s power supply cord should
not be bundled with or kept close to main
circuit lines (high voltage, high current), or
input/output signal lines.
• To reduce noise, make the power cord as
short as possible.
• If the supplied voltage exceeds the ST
unit’s range, connect a voltage transformer.
• Between the line and the ground, be sure to
use a low noise power supply. If there is an
excess amount of noise, connect a noise
reducing transformer.
• The temperature rating of field installed
conductors: 75°C only.
• Use voltage and noise reducing trans-
formers with capacities exceeding
Power Consumption value.
• Must be used with a Class 2 Power Supply.
(24VDC)
• Connect a surge absorber to handle power
surges.
• Be sure to ground the surge absorber
(E1) separately from the ST unit (E2).
Select a surge absorber that has a
maximum circuit voltage greater then
that of the peak voltage of the power
supply.
Recommended
Driver SZF 1-0.6x3.5
(1204517)
Recommended
Pin Terminals
AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)
Recommended
Pin Terminal
Crimp Tool CRIMPFOX ZA 3
(1201882)
Power Connector (Socket)
Power Connector (Plug)
FG
+
-
Lightening Surge Absorber
E1 E2
FG
ST

9
3. Grounding Cautions
• Be sure to create an exclusive ground for
the Power Cord’s FG terminal. Use a
grounding resistance of 100Ω, a wire of
2mm2or thicker, or your country’s applica-
ble standard.
• The SG (signal ground) and FG (frame
ground) terminals are connected internally
in the ST unit.
When connecting the SG line to another
device, be sure that the design of the sys-
tem/connection does not produce a short-
ing loop.
• The grounding wire should have a cross
sectional area greater then 2mm2. Create
the connection point as close to the ST unit
as possible, and make the wire as short, as
possible. When using a long grounding
wire, replace the thin wire with a thicker
wire, and place it in a duct.
4. Input/Output Signal Line Cautions
• All ST Input and Output signal lines must
be separated from all operating circuit
(power) cables.
• If this is not possible, use a shielded cable
and ground the shield.
To prevent the USB cable
from coming off
Attaching the USB Holder
(1) Before starting the procedure, lift up the
tab on both sides of the USB Holder and
remove the USB Cover.
(2) Attach the USB holder to the USB Host
Interface part of the main unit. Hook the
lower pick of the USB holder to the
attachment hole of the main unit and
then insert the upper pick as shown
below to fix the USB holder.
(3) Insert the USB cable into the USB Host
Interface.
ST unit Other
Equipment
Exclusive Grounding
(BEST)
ST unit Other
Equipment
Common Grounding (OK)
ST unit Other
Equipment
Common Grounding
(Not OK)
Tab
USB Cable

10
(4) Attach the USB cover to fix the USB
cable. Insert the USB cover into the tab
of the USB holder.
• Check the up/down orientation of the
USB cover to ensure that the USB
cable is secured properly.
Removing the USB Holder
(1) Lift up the tab of the USB holder and
then remove the USB cover as shown
below.
(2) After removing the USB cable, remove
the picks pushing the USB holder from
both top and bottom.
UL/c-UL Approval
The ST-3400 Series units are UL/c-UL listed
products.
(UL File No.E220851)
These products conform to the following
standards:
UL508
Industrial Control Equipment
CSA-C22.2 No.142-M1987
(c-UL Approval)
Process Control Equipment
<Cautions>
Be aware of the following items when
building the ST into an end-use product:
• The ST unit’s rear face is not approved as
an enclosure. When building the ST unit
into an end-use product, be sure to use an
enclosure that satisfies standards as the
end-use product’s overall enclosure.
• The ST unit must be used indoors only.
• Install and operate the ST with its front
panel facing outwards.
• If the ST is mounted so as to cool itself
naturally, be sure to install it in a vertical
panel. Also, it’s recommended that the ST
should be mounted at least 100mm away
from any other adjacent structures or
machine parts. The temperature must be
checked on the final product in which the
ST is installed.
• For use on a flat surface of a Type 4X
(Indoor Use Only) and/or Type 13 Enclo-
sure.
USB Holder
Tab USB Cover
USB Holder
Tab USB Cover
Product Model No. UL/c-UL
Registration Model No.
AST3401-T1-D24 3580206-01

11
CE Marking
• The AST3401-T1-D24 unit is CE marked,
EMC compliant product. This unit also
conform to EN55011 Class A, EN61131-2
directives.
Revision
The revision code of the ST is shown in the
label affixed to the ST. In the example shown
below, an asterisk "*" is displayed in the
position where "A" should be, meaning "Rev.
A".
Digital Electronics Corporation
8-2-52 Nanko-higashi
Suminoe-ku, Osaka 559-0031
JAPAN
TEL: +81-(0)6-6613-3116
FAX: +81-(0)6-6613-5888
http://www.pro-face.com/
© Copyright 2007 Digital Electronics
Corporation. All rights reserved.
085893E .AST3400-MT01E-BTH
2007.6. JM/C
Inquiry
Do you have any questions about
difficulties with this product?
Please access our site anytime that
you need help with a solution.
http://www.pro-face.com/otasuke/
Please be aware that Digital Electronics
Corporation shall not be held liable by the
user for any damages, losses, or third
party claims arising from the uses of this
product.
Note
Table of contents
Other Pro-face Touch Terminal manuals

Pro-face
Pro-face GP2500-TC41-24V User manual

Pro-face
Pro-face GP2501-TC41-24V User manual

Pro-face
Pro-face AST-3501T User manual

Pro-face
Pro-face HTB User manual

Pro-face
Pro-face GP2501-LG41-24V User manual

Pro-face
Pro-face FP2500-T42-24V User manual

Pro-face
Pro-face GLC2300-LG41-24V User manual

Pro-face
Pro-face GLC100-LG41-24V User manual

Pro-face
Pro-face GP2301H-LG41-24V User manual