Honeywell NOTIFIER N-ANN-80 Series Technical manual

N-ANN-80 Series
Product Installation Document
PN 52986:C3 12/6/2022 ECN: 00028310
12 Clintonville Road
Northford, CT 06472-1610 USA
800-289-3473 • FAX 203-484-7118
www.notifier.com
General
The N-ANN-80 Series Remote Fire Annunciators and Indicators
(N-ANN-80, N-ANN-80-W,N-ANN-80C) are compact, backlit LCD
displays designed for use with compatible FACPs (Fire Alarm Control
Panels). The displays mimic the FACP display and are capable of dis-
playing English-language text of system point status including device
type, independent point alarm, trouble or supervisory zone and custom
labels programmed into the FACP.Refer to the FACP manual installa-
tion section for detailed system information and wiring. The
N-ANN-80C Indicator is intended for use as a replacement part only
per ULC S527-99.
Specifications
TB1 Terminals 1 & 2
Operating Voltage Range: 18.8VDC to 38.2VDC
Maximum Current Consumption:
• Normal/Standby (no activity): 39 mA
• Trouble Condition: 46 mA
• Alarm: 48 mA
• AC Fail (not backlit): 15 mA
TB1 Terminals 3 & 4
ANN-BUS rated at 5.5 VDC and 60 mA max.
Dimensions
6.875”W x 5.375”H x 1.375”D (17.46cm x 13.65cm x 3.49cm)
Mounting
The N-ANN-80 Series plastic enclosures can be surface or semi-flush
mounted in a single, double or 4” (10cm-sized) square electrical box.
To mount the N-ANN-80 Series enclosure:
1. Open the N-ANN-80 Series cover by turning the key switch
counterclockwise to the ON (Unlocked) position.
2. Push in the snap latch tab located on the right side while pulling the
cover open.
3. Pull wire through 7/8” (2.22cm) hole in backplate and feed through
wire channel to lower left corner of backplate before routing to
terminal block (refer to appropriate FACP manual).
4. The cover must remain attached to the backplate while mounting
the annunciator to the electrical box/wall. The cover cannot be
reattached or removed after the annunciator has been mounted.
5. If the cover should become detached from the backplate, reattach as
shown below.
6. Surface or Semi-flush mount the N-ANN-80 to a single, double or
4” (10cm-sized) square electrical box. The ANN-SB80KIT(-R/-B/-
W) is an available kit that contains two plastic backboxes that can
be used to surface mount the N-ANN-80 Series.
Wiring the N-ANN-80 Series to the FACP
Refer to Table 1 and Figure 3 for wiring connections.
NOTE: Installation and wiring must be done in accordance with
NFPA 72 and local wiring codes.
Backplate
Press in latch
and then
Pull open cover
Key switch shown
in OFF position
Cover with
LCD Display
Figure 1 Opening the N-ANN-80 Series
N-ANN-80 Series
Terminals (TB1)
FACP ANN-BUS
Terminals
Terminal 1 (-) (-)
Terminal 2 (+) (+)
Terminal 3 (A) A (ANN-BUS)
Terminal 4 (B) B (ANN-BUS)
N-ANN-80 Series
Terminals (TB2)*
* TB2 is not available on the N-ANN-80C.
FACP ANN-BUS
Terminals
Terminal 1 Earth Ground
Table 1 N-ANN-80 Series to FACP Connections
N-ANN-80
Series
Cover
N-ANN-80
Series
Cover
N-ANN-80
Series
Backplate
N-ANN-80
Series
Backplate
• Position cover behind
backplate.
• Align hinge posts and
holes
• Slide holes down
onto posts.
• Close cover to lock
hinges into place.
Figure 2 Cover Reattachment
2N-ANN-80 Series Installation Document — P/N 52986:C3 12/6/2022
Notes for Figure 3 and Figure 4:
1. All connections/sources must be power-limited and supervised.
2. 12 - 22 AWG (0.33 - 3.31 mm2) wire for N-ANN-80(-W) and 12-
18 AWG (0.75 - 3.25 mm2) for N-ANN-80C is acceptable for the
24 VDC circuit.
3. Power wire distance limitation is set by 1.2 volt maximum line drop
from source to end of circuit.
4. Maximum distance from FACP to last ANN-BUS device must not
exceed 6,000 feet (1,800 m). Refer to the Wiring Distance Table in
the appropriate FACP manual for wire gauge and distance
limitations.
Setting the DIP Switches - N-ANN-80(-W)
Address Setting
Each ANN-BUS device requires a unique address. DIP switches 1-4 on
S1 are used to set the address. This address will be displayed on the LCD
display as the Station ID number.
A maximum of 8 devices can be connected to the FACP ANN-BUS
communication circuit. ANN-BUS device addresses do not need to be
sequential and can be set to any number between 01 and 08. Note that 00
is not a valid address. The following illustrates the DIP switch settings
for each address (ID Number).
Communication Protocol
DIP switch 5 is used to determine the communication protocol of the N-
ANN-80 Series. Set DIP switch 5 to ON for ANN-BUS protocol. Set
DIP switch 5 to OFF for AIO protocol.
End-of-Line Resistor
The end-of-line termination resistor must be enabled at S1 on the last
device on the communication circuit. All other annunciators should have
these switches set to disable.
DIP switches 7 and 8 are unused.
2
B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
-(GND)
Connect to FACP ANN-BUS
and/or next device
Connect to FACP or UL Listed
Power Supply for Protective
Signaling and/or next device
N-ANN-80 Series
Figure 3 Wiring the N-ANN-80(-W) to an FACP
}
}
B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
-(GND)
Connect to FACP ANN-BUS
and/or next device
}
}Connect to FACP or UL Listed
Power Supply for Protective
Signaling and/or next device
N-ANN-80C
Figure 4 Wiring the N-ANN-80C to an FACP
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ID Number
(Address)
(not valid) 00
01
02
03
04
05
06
07
08
DIP Switch S1
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
ANN-BUS protocol AIO protocol
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
termination enabled termination disabled
N-ANN-80 Series Installation Document — P/N 52986:C3 12/6/2022 3
Setting the DIP Switches - N-ANN-80C
Each ANN-BUS device requires a unique address. DIP switch S21 on
the N-ANN-80C is used to set the address. This address will be dis-
played on the LCD display as the Station ID number.
A maximum of 8 devices can be connected to the FACP ANN-BUS
communication circuit. ANN-BUS device addresses do not need to be
sequential and can be set to any number between 01 and 08. Note that 00
is not a valid address. The following illustrates the DIP switch settings
for each address (ID Number):
ID Number
(Address)
(not valid) 00
01
02
03
04
05
06
07
08
DIP Switch S21
N-ANN-80 Series Installation Document — P/N 52986:C3 12/6/2022 1
Changes & Comments for N-ANN-80 Series
Installation Document —52986:C3
pg. 1 11/30/22-wc-added note in first paragraph that -C version is only available as a replacement
part per UL.
pg. 1 11/30/22-wc-added footnote to table 1 that second terminal block is not available on -C mod-
el.
pg. 2 12/6/22-wc-updated wire gauge per attila.
pg. 2 11/30/22-wc-clarified that ANN-80(-W) models have 6 DIP switch settings.
pg. 3 11/30/22-wc-added -C version DIP switch address settings.
Revise to: UL change? ECN: Brief description:
C3 Yes 000xxxxx Plan-C updates

This manual suits for next models

1

Other Honeywell Touch Terminal manuals

Honeywell TemaKey TK C03 User manual

Honeywell

Honeywell TemaKey TK C03 User manual

Honeywell TemaLine TemaKey User manual

Honeywell

Honeywell TemaLine TemaKey User manual

Honeywell VM3AL0N User manual

Honeywell

Honeywell VM3AL0N User manual

Honeywell Dolphin 75e User manual

Honeywell

Honeywell Dolphin 75e User manual

Honeywell SP5600-C OptimusR User manual

Honeywell

Honeywell SP5600-C OptimusR User manual

Honeywell Marathon User manual

Honeywell

Honeywell Marathon User manual

Honeywell Notifier TAD-FTT User manual

Honeywell

Honeywell Notifier TAD-FTT User manual

Honeywell Dolphin 70e Black User manual

Honeywell

Honeywell Dolphin 70e Black User manual

Honeywell temaserver TS TA series User manual

Honeywell

Honeywell temaserver TS TA series User manual

Honeywell JetWave MCS-8562 Manual

Honeywell

Honeywell JetWave MCS-8562 Manual

Honeywell TemaKey User manual

Honeywell

Honeywell TemaKey User manual

Honeywell T80 User manual

Honeywell

Honeywell T80 User manual

Honeywell VISTA Series User manual

Honeywell

Honeywell VISTA Series User manual

Honeywell ADEMCO 6271 Series Assembly instructions

Honeywell

Honeywell ADEMCO 6271 Series Assembly instructions

Honeywell CT40 HomeBase User manual

Honeywell

Honeywell CT40 HomeBase User manual

Popular Touch Terminal manuals by other brands

PAR EverServ 600 user manual

PAR

PAR EverServ 600 user manual

HIK VISION DS-K1T342 Series user manual

HIK VISION

HIK VISION DS-K1T342 Series user manual

ELCOM Uniq 150 Service manual

ELCOM

ELCOM Uniq 150 Service manual

Festo IFB-03 Series Pneumatics Manual

Festo

Festo IFB-03 Series Pneumatics Manual

Omron NT600M Series Operation manual

Omron

Omron NT600M Series Operation manual

Beckhoff KL4011 operating instructions

Beckhoff

Beckhoff KL4011 operating instructions

Sony PCS-6000 operating instructions

Sony

Sony PCS-6000 operating instructions

Phoenix Contact 27 41 40 6 user manual

Phoenix Contact

Phoenix Contact 27 41 40 6 user manual

Samyung SN-100 Service manual

Samyung

Samyung SN-100 Service manual

AT&T 730 MTG user guide

AT&T

AT&T 730 MTG user guide

GE D20 Installation and operation guide

GE

GE D20 Installation and operation guide

Beckhoff EL3101 Documentation

Beckhoff

Beckhoff EL3101 Documentation

Pilz PX 30 operating manual

Pilz

Pilz PX 30 operating manual

DSPPA POE6401 user manual

DSPPA

DSPPA POE6401 user manual

EchoStar Hughes 45 Series install guide

EchoStar

EchoStar Hughes 45 Series install guide

Nortel Millennium M1000 manual

Nortel

Nortel Millennium M1000 manual

Casio DT-X10 series user guide

Casio

Casio DT-X10 series user guide

Cascade GP4116 user manual

Cascade

Cascade GP4116 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.