DEL2090 Issue 4 02/11 SB Page 1 of 3 Copyright © Protec Fire Detection plc 2010
6000PLUS/HT/SL Installation, Commissioning and Service Instructions
Overview
The Protec 6000PLUS/HT/SL is a loop powered fire sensor which reports back thermal levels in its installed location to the fire
alarm control panel. The sensor is also equipped with an integrated loop powered programmable electronic sounder, beacon
and an integrated loop Isolator.
Technical Specification
Loop protocol Protec Algo-tec™ 6000PLUS
Loop isolator fitted Yes
Loop voltage range 18 to 27V Algo-tec™ Protocol
Loop average quiescent current (24V loop) 0.4mA
Loop average alarm current (24V loop) 10mA
Analogue values
Thermal
Normal 80 to 180 bits
Fault Low <25 bits
Fault High>250 bits
Indications On-board red indicating LED
Environmental operational limits -10 to 50 degrees C ( 95% RH no condensation or icing )
Sounder Frequencies Continuous 990Hz, Warble 730Hz to 990Hz, Pip 990Hz
IP rating IP21C
Isolator Specification Please see Protec DEL2110 for details
Installation
1. Base options: 6000PLUS/BASE LPCB Approved as part of product approval
6000PLUS/FFBASE LPCB Approved as part of product approval
28-075-01 (Plug and Play Fast Fix) LPCB Approved as part of product approval
28-075-02 (Plug and Play Surface) LPCB Approved as part of product approval
Note: See individual information sheets for base wiring details.
2. Install the detector in the base, turn firmly clockwise.
Commissioning
1. Each 6000PLUS detector has a unique serial number which will be used as part of the commissioning of the fire alarm
system. It is necessary to remove one of the ‘peelable ’ bar code labels present on the product and place it in the
commissioning booklet supplied with each Protec addressable control panel. The bar code sticker should be placed at the
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of
the 6000PLUS/HT/SL will be incorrect when commissioned.
2. Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel
being used.
6000PLUS/HT/SL Certification Details
EN Standards Compliance/ Approvals table
Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT
10
0832-CPD-1183
EN 54 - 3: 2001 + A1 + A2
Alarm devices – Sounder
Type A: For indoor use
6000PLUS/HT/SL
EN 54 - 5
Point type Heat detector
Class A1/A2
6000PLUS/HT/SL
EN 54 - 17: 2005
Short-circuit isolator
6000PLUS/HT/SL
Technical Data included in this datasheet DEL2090 Issue 4
High sensitivity Medium Sensitivity Low Sensitivity
EN 54 - 5: 2000 + A1: 2002 Class A1 EN 54 - 5: 2000 + A1: 2002 Class A2 Not approved.
Equivalent to EN 54 - 5: 2000 + A1: 2002 Class B