ProKlima JHS-A030-09KR2/A-W User manual

OPERATING INSTRUCTIONS
Bauhaus No.: 2149996D
JHS-A030-09KR2/A-W
NO
lokalt klimaanlegg

2
Content
I.Attention Matters…............................................................ 3
II.Features and Components….......................................... 7
III.Control Setting…..............................................................8
IV.Protection function….................................................... 12
V.Installation and adjustment…....................................... 13
VI.Drainage Instructions…............................................... 15
VII.Maintenance…..............................................................16
VIII.Out-of-season save….................................................16
IX.Troubleshooting…......................................................... 17
X.Addendum…....................................................................26
The refrigerant used in mobile air conditioners is the environmentally
friendly hydrocarbonR290.This refrigerant is odorless, and compared
to the alternative refrigerant, the R290 is an ozone-free refrigerant,
and its effect is very low.
Please read the instructions before use and repair.The drawings
provided in this manual may not be the same as the physical objects.
Please refer to the physical objects.

3
I.Attention Matters
Warning matters:
1.Do not use means to accelerate the defrosting
process or to clean, other than those recommended by
the manufacturer.
2.The appliance shall be stored in a room without
continuously operating ignition sources (for example:
open flames, an operating gas appliance or an
operating electric heater.)
3.Do not pierce or burn.
4.Be aware that refrigerants may not contain an odour.
5.Appliance shall be installed, operated and stored in a
room with a floor area larger than 12m²
6.Keep any required ventilation openings clear of
obstruction;
7.Servicing shall be performed only as recommended
by the manufacturer.
8.The appliance shall be stored in a well-ventilated area
where the room size corresponds to the room area as
specified for operation.
9.Any person who is involved with working on or
breaking into a refrigerant circuit should hold a current
valid certificate from an industry-accredited assessment
authority, which authorises their competence to handle
refrigerants safely in accordance with an industry
recognised assessment specification.
10.Servicing shall only be performed as recommended
by the equipment manufacturer.Maintenance and repair
requiring the assistance of other skilled personnel shall
be carried out under the supervision of the person

4
competent in the use of flammable refrigerants.
11.All working procedure that affects safety means shall
only be carried by competent persons.
Notes:
*The air conditioning is only suitable for indoor use, and
is not suitable for other applications.
*Follow local grid interconnection rules while installing
the air conditioning and ensure that it is properly
grounded. If you have any question on electrical
installation, follow the instructions of the manufacturer,
and if necessary, ask a professional electrician to install
it.
*Place the machine in a flat and dry place and keep a
distance of above 50cm between the machine and the
surrounding objects or walls.
*After the air conditioning is installed, ensure that the
power plug is intact and firmly plugged into the power
outlet, and place the power cord orderly to prevent
someone from being tripped or pulling out the plug.
*Do not put any object into the air inlet and outlet of the
air conditioning. Keep the air inlet and outlet free from
obstructions.
*When drainage pipes are installed, ensure that the
drainage pipes are properly connected, and are not

5
distorted or bended.
*While adjusting the upper and lower wind-guide strips
of the air outlet, pluck it with hands gently to avoid
damaging wind-guide strips.
*When moving the machine, make sure that it is in an
upright position.
*The machine should stay away from gasoline,
flammable gas, stoves and other heat sources.
*Don't disassemble, overhaul and modify the machine
arbitrarily,otherwise it will cause a machine malfunction
or even bring harm to persons and properties. To avoid
danger, if a machine failure occurs, ask the
manufacturer or professionals to repair it.
*Do not install and use the air conditioning in the
bathroom or other humid environments.
*Do not pull the plug to turn off the machine.
*Do not place cups or other objects on the body to
prevent water or other liquids from spilling into the air
conditioning.
*Do not use insecticide sprays or other flammable
substances near the air conditioning.
*Do not wipe or wash the air conditioning with chemical
solvents such as gasoline and alcohol. When you need
to clean the air conditioning, you must disconnect the
power supply, and clean it with a half-wet soft cloth. If
the machine is really dirty, scrub with a mild detergent.
*The appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities if they have been given
supervision or instruction concerning use of the
appliance in a safe way and understand the hazards
involved.

6
Children shall not play with the appliance. Cleaning and
maintenance shall not be made by children without
supervision.
If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
The appliance shall be installed in accordance with
national wiring regulations.
Do not operate your air conditioner in a wet room such
as a bathroom or laundry room.
Transportation, marking and storage for units
1.Transport of equipment containing flammable
refrigerants Compliance with the transport regulations
2.Marking of equipment using signs Compliance with
local regulations
3.Disposal of equipment using flammable refrigerants
Compliance with national regulations
4.Storage of equipment/appliances The storage of
equipment should be in accordance with the
manufacturer’s instructions.
5.Storage of packed (unsold) equipment Storage
package protection should be constructed such that
mechanical damage to the equipment inside the
package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted
to be stored together will be determined by local
regulations.

7
II.Features and Components
1、Features
*Brand new appearance, compact structure, smooth line,
simple and generous shape.
*Functions of refrigeration, dehumidification, air supply
and continuous drainage
*Outdoor interface is set high to facility assembly and
keep the smooth flow of the heat pipe.
*LED displays the control panel, beautiful and
fashionable, with high-quality remote control.It adopts a
user-friendly remote control design.
*Air filtration capability.
*Timing switch function.
*Protection function of automatically restarting the
compressor after three minutes, a variety of other
protection functions.
The Max operation temperature for the air conditioner
Cooling: 35/24℃; heating:20/12℃; Temperature
operation range: 7-35℃.
2、Component

8
Exhaust Pipe Assembly
Window Sealing Plate Assembly
III.Control Setting
1. Control panel operation instructions
1)operation interface:
1.Timer Key 2. Fan Speed Selection Key
3.Up Key 4.Display 5. Down Key
6.Sleep Key 7.Mode Selection Key 8. Power Key

9
When the machine is powered on for the first time, the buzzer will
play power-on music, and then the machine will get into standby
status.
1: Power Key: press the key to turn on and turn off the machine. In the
case of power on, press the key to turn off the machine; in the case of
power off, press the key to turn on the machine.
2: Mode Selection Key: In the case of power on, press the key to switch
between cooling →fan → dehumidifying mode.
3:Sleep Mode:
In the cooling Mode,Press the UP and Fan Key to turn on the sleep
mode,then the unit will work on Energy-Saving and quiet type.
4:Up Key and Down Key: press the two keys to change the setting
temperature or setting time, operate as follows:
While setting temperature, press up key or down key to select the
required temperature (not
available in fan or dehumidifying mode).
While setting time, press up key or down key to select the required
time.
5:Wind Speed Selection Key:
In cooling and fan mode, press the key to select high,low wind speed
operation. But limited by anti-cold conditions,under certain conditions,
it may not run according to the set wind speed.
In dehumidifying mode, pressing the key is invalid, and the fan will
forcibly choose low wind speed operation.
6:Timing Key:
In the case of power on, press the key to close timing; in the case of
power off, press the key to open timing.
Press the key, when the timing symbol flashes, press up and down
key to select the required timing value.
Timing values can be set in 1-24 hours and the timing value is
adjusted up or down by one hour.
7:Auto Swing
In the case of starting up, press this key to operate the automatic
swing on and off.
Note:
1. Can not turn on the sleep mode in the dehumidifying or Fan mode!
2. The waterfull Lamp will turn on and buzzer will alarm for several
second, the compressor will stop to work when the inner unit chassis
water is full.

10
2.operation instructions of remote control
1)The remote control Panel is as follows:
Instructions of key operation of the high-quality remote control are as
follows:
1.Power: Press the key to turn on or turn off the machine.
2.Timer: press the key to set timing.
3.Down: press the key to reduce temperature and timing set
value.
4.Mode: press the key to switch between cooling, fan,
dehumidifying mode.
5.Up: press the key to increase temperature and timing
set value.
6.Fan: press the key to select high, low wind speed.
7.Sleep Mode:Press the key to turn on the sleep mode.
8.℃&℉Change:Press to change ℃and ℉display .

11
Information on the App “Smart Life - Smart Living”
The Smart Life - Smart Living app is available for android and iOS.
Scan the corresponding QR code to get directly to the download.
NOTE:
Depending on the provider, there may be costs involved in
downloading the app.
Google Play App Store
Information on How to Use the App
This appliance allows you to operate the appliance via your home
network. A prerequisite is a permanent Wi-Fi connection to your router
and the free app “Smart Life - Smart Living”.
You can easily access all functions of the appliance via the app. Since
the app constantly improved, we cannot provide a more detailed
description here.
We recommend disconnecting the appliance from the power supply
when you are away from home to prevent unintentional switching on
while you are on the road!
System Requirement for Use of the App
• iOs 8.0 or higher
• Android 4.4 or higher
Commissioning via the App
1.Install the “Smart Life - Smart Living” app. Create a user account.
2.Activate the Wi-Fi function in the settings of your appliance.
3.Place the air-conditioning appliance within a distance of around 5
meters of your router.
4.Press and hold the button for about 3 seconds. The Wi-Fi
indicator light flashes rapidly.
5.Launch the app and select “+”.

12
6.Select the “air conditioner” menu and follow the instructions on the
display.
7.Once the appliance has been connected successfully, the Wi-Fi
indicator light will be solid. Now you can operate the appliance using
the app.
NOTE:
• The appliance can only be operated with 2.4 GHz routers. 5 GHz
routers are not supported.
• The appliance is equipped with only one network connection. It
cannot be turned off.
IV.Protection function
3.1 Frost Protection Function:
In cooling, dehumidifying or economic power saving mode, if the
temperature of the exhaust pipe is too low, the machine will
automatically enter protection status; if the temperature of the exhaust
pipe rises to a certain temperature, it can automatically revert to
normal operation.
3.2 Overflow Protection Function:
When water in the water pan exceeds the warning level, the machine
will automatically sound an alarm, and the "FULL" indicator light will
flash. At this point, you need to move the drainage pipe connectingthe
machine or the water outlet to sewer or other drainage area to empty
the water (details see DrainageInstructions at the end of this chapter).
After the water is emptied, the machine will automatically return to the
original state.
3.3 Automatic Defrosting (cooling models have this function):
The machine has automatic defrosting function.Defrosting can be
achieved through four - way valve reversing.
3.4 Protection Function of the Compressor
To increase the service life of the compressor, it has a 3-minute delay
booting protection function after the compressor is turned off.

13
V.Installation and adjustment
1.Installation:
Warning: before using the mobile air conditioning, keep it upright forat
least two hours. The air conditioning can be easily moved in the room.
1)take out the outer connector assembly and the exhaust pipe
assembly, and remove the plastic bags;
2)insert the heat pipe assembly (the end of the exhaust joint) into
the back panel vent slot (push to the left) and complete the assembly
(as shown in figure 1).
1.2 Installation of window sealing plate components
1)Half open the window,and mount the window sealing plate
assembly to the window (as shown in Fig.2 and Fig.3).Components
can be placed in horizontal and vertical direction.
2)Pull various components of the window sealing plate assembly
open, adjust their opening distance to bring both ends of the assembly
into contact with the window frame, and fix various components of the
assembly.
1.2 Install the window sealing plate assembly.
Notes:1)the flat end of the exhaust pipe joints must be snapped into
place.
2)The pipe cannot be distorted nor has substantial turning
(greater than 45 ° ).
Keep the ventilation of the exhaust pipe not blocked.
Figure 2 Figure 3

14
1.3 Install the body
1)Move the machine with installed heat pipe and fittings before the
window, and the distance between the body and walls or other objects
shall be least 50 cm (as shown in Fig.4).
Figure4
2)Elongate the exhaust pipe and snap the flat end of the exhaust
pipe joints into the hole of the window sealing plate assembly (as
shown in Fig.5 and Fig.6) .
Notes:
1.The flat end of the exhaust pipe joints must be snapped into place.
2.The pipe cannot be distorted nor has substantial turning (greater
than 45 °). Keep the ventilation of the exhaust pipe not blocked.
Figure 5 Figure 6
Important notice:
The length of the exhaust hose shall be 280~1,500mm, and this
length is based on the specifications of the air conditioning. Do not
use extension tubes or replace it with other different hoses, or this
may cause a malfunction. Exhaust host must be not blocked;
otherwise it may cause overheating.

15
VI.Drainage Instructions
This machine has two drainage methods: manual drainage and
continuous drainage.
1. Manual drainage:
1)When the machine stops after the water is full, turn off the machine
power and unplug the power plug.
Notes:Please move the machine carefully, so as not to spill the
water in the water pan at the bottom of thebody.
2)Place the water container below the side water outlet behind the
body.
3)Unscrew the drainage cover and unplug the water plug, the water
will automatically flow into the water container.
Notes:
1)Keep the drainage cover and the water plug properly.
2)During drainage, the body can be tilted slightly backwards.
3)If the water container cannot hold all the water, before the water
container is full, stuff the water outlet with the water plug as soon as
possible to prevent water from flowing to the floor or the carpet.
4)When the water is discharged, stuff the water plug, and tighten the
drainage cover.
2. Continuous drainage (Optional) (only applicable to dehumidifying
mode), as shown in figure:
1)Unscrew the drainage cover, and unplug the water plug.
2)Set the drainage pipe into the water outlet.
3)Connect the drainage pipe to the bucket.

16
VII.Maintenance
Cleaning: before cleaning and maintenance, turn off the machine and
unplug the plug.
1. Clean the surface
Clean with surface of machine with a wet soft cloth. Don't use
chemicals,such as benzene,alcohol, gasoline,etc; otherwise, the
surface of the air conditioning will be damaged or even the whole
machine will bedamaged.
2. Clean the filter screen
If the filter screen is clogged with dust, and the effectiveness of the air
conditioning is reduced, be sure to clean the filter screen once every
two weeks.
3. Clean the upper filter screen frame
1) Unscrew one screw fixed by EVA filter net and back shell with
screwdriver, and take out EVA filter net.
2) Put the EVAfilter screen into warm water with neutral detergent
(about 40℃/ 104℉) and dry it in the shade after rinsing clean.
VIII.Unit Storage:
1:Unscrew the drainage cover, unplug the water plug, and discharge
the water in the water pan into other water containers or directly tilt the
body to discharge the water into other containers.
2:Turn on the machine, adjust it to low-wind ventilation mode, and
maintain this state until the drainage pipe becomes dry, so as to keep
the inside of the body in a dry state and prevent it from mildewing.
3:Turn off the machine, unplug the power plug, and wrap the power
cord around the wrapping post; install the water plug and the drainage
cover.
4:Remove the exhaust pipe and keep it properly.
5:Cover the air conditioning with a plastic bag. Put the air conditioning
in a dry place, keep it out of the reach of children, and take dust

17
control measures.
6:Remove batteries of the remote control and keep them properly.
Note: ensure that the body is placed in a dry place and keep all
machine components properly.
IX.Troubleshooting
1.Information on servicing
1)Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For
repair to the refrigerating system, the following precautions shall be complied
with prior to conducting work on the system.
2)Work procedure
Work shall be undertaken under a controlled procedure so as to
minimise the risk of a flammable gas or vapour being present while
the work is being performed.
3)General work area
All maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out. Work in confined
spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been
made safe by control of flammable material.
4)Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector
prior to and during work, to ensure the technician is aware of
potentially flammable atmospheres. Ensure that the leak detection
equipment being used is suitable for use with flammable refrigerants,
i.e. non- sparking, adequately sealed or intrinsically safe.
5)Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or
any associated parts,appropriate fire extinguishing equipment shall be
available to hand. Have a dry powder orCO2 fire extinguisher adjacent
to the charging area.
6)No ignition sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained
flammable refrigerant shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing

18
and disposal, during which flammable refrigerant can possibly be
released to the surrounding space. Prior to work taking place, the area
around the equipment is to be surveyed to make sure that there are
no flammable hazards or ignition risks. “No Smoking” signs shall be
displayed.
7)Ventilated area
Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work. A degree
of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere.
8)Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for
the purpose and to the correct specification. At all times the
manufacturer’s maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer’s technical department for
assistance.
The following checks shall be applied to installations using flammable
refrigerants:
–The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
–The ventilation machinery and outlets are operating adequately and
are not obstructed;
–If an indirect refrigerating circuit is being used, the secondary circuit
shall be checked for the presence of refrigerant;
–Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected;
–Refrigeration pipe or components are installed in a position where
they are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being
corroded or are suitably protected against being so corroded.
9)Checks to electrical devices
Repair and maintenance to electrical components shall include initial
safety checks and component inspection procedures. If a fault exists
that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used. This shall be
reported to the owner of the equipment so all parties are advised.

19
Initial safety checks shall include:
•That capacitors are discharged: this shall be done in a safe manner
to avoid possibility of sparking;
•That there no live electrical components and wiring are exposed
while charging, recovering or purging the system;
•That there is continuity of earth bonding.
2.Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall
be disconnected from the equipment being worked upon prior to any
removal of sealed covers, etc. If it isabsolutely necessary to have an
electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a
way that the level of protection is affected. This shall include damage
to cables, excessive number of connections, terminals not made to
original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that
they no longer serve the purpose of preventing the ingress of
flammable atmospheres. Replacement parts shall be in accordance
with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of
some types of leak detection equipment. Intrinsically safe components
do not have to be isolated prior to working on them.
3.Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the
circuit without ensuring that this will not exceed the permissible
voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on
while live in the presence of a flammable atmosphere. The test
apparatus shall be at the correct rating. Replace components only with
parts specified by the manufacturer. Other parts may result in the
ignition of refrigerant in the atmosphere from a leak.
4.Cabling
Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental
effects. The check shall also take into account the effects of aging or
continual vibration from sources such as compressors or fans.

20
5.Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in
the searching for or detection of refrigerant leaks. A halide torch (or
any other detector using a naked flame) shall not be used.
6.Leak detection methods
The following leak detection methods are deemed acceptable for
systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or may need re-
calibration. (Detection equipment shall be calibrated in a refrigerant-
free area.) Ensure that the detector is not a potential source of ignition
and is suitable for the refrigerant used. Leak detection equipment shall
be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed and the appropriate percentage
of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but
the use of detergents containing chlorine shall be avoided as the
chlorine may react with the refrigerant and corrode the copper pipe-
work.
If a leak is suspected, all naked flames shall be removed/
extinguished. If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the system, or
isolated (by means of shut off valves) in a part of the system remote
from the leak. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
7.Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any
other purpose – conventional procedures shall be used. However,
it is important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to:
•Remove refrigerant;
•Purge the circuit with inert gas;
•Evacuate;
•Purge again with inert gas;
•Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery
cylinders. The system shall be “flushed” with OFN to render the unit
safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task. Flushing
shall be achieved by breaking the vacuum in the system with OFN and
This manual suits for next models
1
Table of contents
Languages:
Other ProKlima Air Conditioner manuals

ProKlima
ProKlima JHS-A018 -12KR2/C-W User manual

ProKlima
ProKlima 23.651.66 User manual

ProKlima
ProKlima KLW-018A1 User manual

ProKlima
ProKlima GPC12AJ User manual

ProKlima
ProKlima SPLIT 850 C User manual

ProKlima
ProKlima 28964490 User manual

ProKlima
ProKlima ALASKA 110 User manual

ProKlima
ProKlima GPC10AL User manual

ProKlima
ProKlima AC120-16AR User manual

ProKlima
ProKlima A018A-09C-PLUS-W User manual