manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Puls
  6. •
  7. Power Supply
  8. •
  9. Puls ML30.106 User manual

Puls ML30.106 User manual

Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany, www.pulspower.com
Germany +49 89 9278 0
China +86 512 62881820 France +33 478 668 941
North America +1 630 587 9780 Austria +43 2764 3213
Singapore +65 6684 2310 Switzerland +41 56 450 18 10
United Kingdom +44 1525 841001
The information in this document is believed to be accurate and reliable and may change without notice.
EN ML30.106 Installation Manual Power Supply 1-Phase, ±12V, 2A, 36W
DE ML30.106 Installationsanleitung Stromversorgung 1-Phase, ±12V, 2A, 36W
FR ML30.106 Manuel d'installation Alimentation d'Énergie 1-Phase, ±12V, 2A, 36W
ES ML30.106 Manual de instalación Fuente De Alimentación 1-Phase, ±12V, 2A, 36W
Doc. ID: PU-322.015.yy-xxZ (2018-11-30-MR1)
Read this first! English Vor Inbetriebnahme lesen! Deutsch
Before operating this device, please read this manual thoroughly and retain this
manual for future reference! This device may only be installed and put into operation
by qualified personnel. If damage or malfunction should occur during operation,
immediately turn power off and send device to the factory for inspection. The device
does not contain serviceable parts. The information presented in this document is
believed to be accurate and reliable and may change without notice. For any
clarifications, the English translation will be used.
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das
Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das
Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei
Funktionsstörungen oder Beschädigungen schalten Sie sofort die
Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das
Gerät beinhaltet keine Servicebauteile. Die angegebenen Daten dienen allein der
Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im
Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text.
WARNING Risk of electrical shock, fire, personal injury, or death: WARNUNG Missachtung nachfolgender Punkte kann einen
elektrischen Schlag, Brände, schwere Unfälle oder
Tod zur Folge haben:
Turn power off before working on the device and protect against inadvertent re-
powering.
Do not open, modify or repair the device.
Use caution to prevent any foreign objects from entering the housing.
Do not use in wet locations or in areas where moisture or condensation can be
expected.
Do not touch during power-on and immediately after power-off. Hot surfaces may
cause burns.
Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder
Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes
Wiedereinschalten.
Führen Sie keine Änderungen oder Reparaturen durch. Gerät nicht öffnen!
Verhindern Sie das Eindringen von Fremdkörpern.
Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei
der mit Betauung oder Kondensation zu rechnen ist.
Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren.
Heiße Oberflächen können Verletzungen verursachen.
A lire avant mise sous tension! Français Lea primero! Español
Veuillez lire ces instructions de montage et d'entretien avant de mettre l'alimentation
sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation
ne doit être installée que par du personnel qualifié et compétent. En cas de
dommage ou dysfonctionnement, coupez immédiatement la tension d’alimentation
et retournez l’appareil à l’usine pour vérification. ! L’alimentation ne contient pas de
pièces échangeables Les données indiquées dans ce document servent
uniquement à donner une description du produit et n'ont aucune valeur juridique. En
cas de divergences, le texte anglais fait foi.
Conserve este manual como referencia para futuras consultas. La fuente de
alimentación solo puede ser instalada y puesta en funcionamiento por personal
cualificado. Por favor lea detenidamente este manual antes de conectar la fuente
de alimentación. Si se produce un fallo o mal funcionamiento durante la operación,
desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo
debe ser inspeccionado en fábrica. La información presentada en este documento
es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin
aviso. En casa de duda, prevalece el texto inglés.
AVERTISSEMENT Prendre en compte les points suivants, afin
d'éviter toute détérioration électrique,
incendie, dommage aux personnes ou mort:
ADVERTENCIA Riesgo de descarga eléctrica, incendio,
accidente grave o muerte:
Mettre l’alimentation hors tension avant toute intervention sur celle-ci et s'assurer
qu'il n'y a pas risque de redémarrage.
Ne pas ouvrir, modifier ou réparer l'alimentation.
Veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation
(trombones, pièces métalliques).
Ne pas faire fonctionner l'appareil dans un environnement humide ou dans un
environnement où il peut y avoir de la condensation.
Ne pas toucher le carter pendant le fonctionnement ou directement après la mise
hors tension. Surface chaude risquant d’entraîner des blessures.
Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite
una posible reconexión involuntaria.
No realizar ninguna modificación o reparación de la unidad. No abrir la unidad.
Evitar la introducción en la carcasa de objetos extraños.
No usar el equipo en ambientes húmedos. No operar el equipo en ambientes
donde se espere la formación de rocío o condensación.
No tocar durante el funcionamiento ni inmediatamente después del apagado. El
calor de la superficie puede causar quemaduras graves.
EN ML30.106 Installation Manual
Product Description
The ML30.106 is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV ± dual output voltage with a common return line.
The output of the device fulfils the requirements for a limited power source according to NEC Class
2.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as
in industrial control, process control, monitoring and measurement equipment or the like. Do not use
this device in equipment where malfunction may cause severe personal injury or threaten human
life.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to
+70°C. Ensure that all strands of a stranded wire enter the terminal connection.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The housing of the device provides a degree of protection of IP20. The housing does not provide
protection against spilled liquids.
The isolation of the device is designed to withstand impulse voltages of overvoltage category II
according to IEC 60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage
between the input terminals and the PE terminal must not exceed 300Vac.
The input can also be powered from batteries or similar DC sources. The continuous voltage
between the supply voltage and the PE/ground potential must not exceed 375Vdc.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 2000m (6560ft).
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 0mm left
and right side. Increase the 0mm to 15mm in case the adjacent device is a heat source.
The device is designed, tested and approved for branch circuits up to 16A (IEC) or 15A (UL) without
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than
10A B- or 6A C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive and capacitive loads.
The +/– output voltage is generated by one converter. The sum of both voltages is regulated. The
total power of 36W can be drawn asymmetrically or only from one output. It is recommended that
the other output should draw a minimum load of 4% of the total load.
Do not apply return voltages from the load to the output terminals higher than ±20V.
A range selection can be done with the jumper on the output terminal block. An inserted jumper sets
the output voltage to ±15V. An open connection sets the output voltage to ±12V.
The green DC-OK LED reports a voltage on the output terminals above 19V (sum of both output
voltages).
Do not parallel devices for higher output currents.
Do not connect outputs of devices in a series connection for higher output voltages.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 50V (sum of
both output voltages). The output shuts down and automatically attempts to restart.
Technical Data
All values are typical figures specified at 230Vac, 50Hz input
voltage, ±12V 1.5A output load, 25°C ambient temperature and
after a 5 minutes run-in time unless otherwise noted.
Output voltage DC ±12V Nominal
Adjustment range ±12V – 15Vdc Factory setting ±15V
Output current ±2A, max 36W Below +60°C ambient
±1.5A, max 27W At +70°C ambient
Derate linearly between +60°C and +70°C
Input voltage AC AC 100 – 240V -15% / +10%
Mains frequency 50 – 60Hz ±6%
Input current AC 0.58 / 0.39A At 120 / 230Vac
Power factor 0.56 / 0.47 At 120 / 230Vac
Input voltage DC DC 110-300V -20% / +25%
Input current DC 0.38 / 0.14A At 110 / 300Vdc
Input inrush current 15 / 32A pk At 120 / 230Vac, 40°C,
cold start
Efficiency 86.0 / 87.0% At 120 / 230Vac
Power losses 5.9 / 5.4W At 120 / 230Vac
Hold-up time 54 / 236ms At 120 / 230Vac
Temperature range -10 to +70°C
Max. wire size (litz wire) 2.5mm²
Max. wire size with ferrules 1.5mm²
Wire size AWG AWG 26-12
Max. wire diameter 2.3mm
Wire stripping length 6mm / 0.25inch
Size (wxhxd) 45x75x91mm Without DIN-rail
Weight 240g / 0.53lb
Functional Diagram
Link: ±15V
Open: ±12V
Input
Fuse
&
Input
Filter
L
N
Output Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
Output
Voltage
Regulator
Common
+
Output
Filter
V
OUT
DC-ok
LED
Power
Converter
-
Output Characteristic
Output voltage
±12V
Output current
0V 0A
Adjustment range
±15V
±0.5A ±1A ±1.5A ±2A ±2.5A
A
B
A: for 100-120Vac mains
B: for 230Vac mains
Temperature Range
Allowed output power
Ambient temperature
0A
-10
36W
+60 +70°C
27W

Other Puls Power Supply manuals

Puls PIANO Series User manual

Puls

Puls PIANO Series User manual

Puls MiniLine ML60 Instructions for use

Puls

Puls MiniLine ML60 Instructions for use

Puls DIMENSION QS5.241-60 User manual

Puls

Puls DIMENSION QS5.241-60 User manual

Puls UZB12.071 User manual

Puls

Puls UZB12.071 User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls DN4011 User manual

Puls

Puls DN4011 User manual

Puls FPT500.241-001-102 User manual

Puls

Puls FPT500.241-001-102 User manual

Puls DIMENSION CT5 Series User manual

Puls

Puls DIMENSION CT5 Series User manual

Puls PIM90.241 User manual

Puls

Puls PIM90.241 User manual

Puls Dimension Q-Series User manual

Puls

Puls Dimension Q-Series User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls Fiepos FPS300.245-034-105 User manual

Puls

Puls Fiepos FPS300.245-034-105 User manual

Puls QS10.241-A1 User manual

Puls

Puls QS10.241-A1 User manual

Puls DIMENSION CP10.248 User manual

Puls

Puls DIMENSION CP10.248 User manual

Puls CP20.242 User manual

Puls

Puls CP20.242 User manual

Puls QS5.DNET User manual

Puls

Puls QS5.DNET User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls QS10.481 User manual

Puls

Puls QS10.481 User manual

Puls QT40.481 User manual

Puls

Puls QT40.481 User manual

Puls CS10.244 User manual

Puls

Puls CS10.244 User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls PIANO Series User manual

Puls

Puls PIANO Series User manual

Puls FPS300.241-002-101 User manual

Puls

Puls FPS300.241-002-101 User manual

Puls Dimension Q-Series User manual

Puls

Puls Dimension Q-Series User manual

Popular Power Supply manuals by other brands

NewMar Commander II Series manual

NewMar

NewMar Commander II Series manual

Hama 200008 operating instructions

Hama

Hama 200008 operating instructions

BKE JS-30- /DIN_KK Series Installation and user guide

BKE

BKE JS-30- /DIN_KK Series Installation and user guide

Pulsar PSCC10350 quick start guide

Pulsar

Pulsar PSCC10350 quick start guide

Ametek Sorensen XPF Series Operation manual

Ametek

Ametek Sorensen XPF Series Operation manual

Kikusui PAD500-1.2A instruction manual

Kikusui

Kikusui PAD500-1.2A instruction manual

Datcon DT2500 Series operating manual

Datcon

Datcon DT2500 Series operating manual

Fadisel cebek FE-77 manual

Fadisel

Fadisel cebek FE-77 manual

ADJ POW-R BAR LINK Use guide

ADJ

ADJ POW-R BAR LINK Use guide

Stanley PS161-6 installation instructions

Stanley

Stanley PS161-6 installation instructions

Horizont farmer AN1000 Solar instruction manual

Horizont

Horizont farmer AN1000 Solar instruction manual

Agilent Technologies 66309B/D Specifications

Agilent Technologies

Agilent Technologies 66309B/D Specifications

Pepperl+Fuchs PS1550 instruction manual

Pepperl+Fuchs

Pepperl+Fuchs PS1550 instruction manual

Pts E-Kit PRC-117F user guide

Pts

Pts E-Kit PRC-117F user guide

ENERMAX REVOLUTION85PLUS user manual

ENERMAX

ENERMAX REVOLUTION85PLUS user manual

Rockwell Automation Allen-Bradley 1606-XLE480ERZ installation instructions

Rockwell Automation

Rockwell Automation Allen-Bradley 1606-XLE480ERZ installation instructions

Scame LIBERA Series quick start guide

Scame

Scame LIBERA Series quick start guide

COUGAR GEX1050 quick start guide

COUGAR

COUGAR GEX1050 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.