EN PIM60.125 Installation Manual Power Supply 1-Phase, 12V, 5A, 60W
DE PIM60.125 Installationsanleitung Stromversorgung 1-Phase, 12V, 5A, 60W
FR PIM60.125 Manuel d'installation Alimentation d'Énergie 1-Phase, 12V, 5A, 60W
ES PIM60.125 Manual de instalación Fuente De Alimentación 1-Phase, 12V, 5A, 60W
Doc. ID: PU-446.015.03-xxB (2020-01-06-MR1)
Read this first! English Vor Inbetriebnahme lesen! Deutsch
Before operating this device, please read this manual thoroughly and retain this
manual for future reference! This device may only be installed and put into operation
by qualified personnel. If damage or malfunction should occur during operation,
immediately turn power off and send device to the factory for inspection. The device
does not contain serviceable parts. The information presented in this document is
believed to be accurate and reliable and may change without notice. For any
clarifications the English translation will be used.
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das
Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das
Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei
Funktionsstörungen oder Beschädigungen schalten Sie sofort die
Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das
Gerät beinhaltet keine Servicebauteile. Die angegebenen Daten dienen allein der
Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im
Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text.
WARNING
Risk of electrical shock, fire, personal injury, or death: WARNUNG
Missachtung nachfolgender Punkte kann einen
elektrischen Schlag, Brände, schwere Unfälle oder
Tod zur Folge haben:
Turn power off before working on the device and protect against inadvertent re-
powering.
Do not open, modify or repair the device.
Use caution to prevent any foreign objects from entering the housing.
Do not use in wet locations or in areas where moisture or condensation can be
expected.
Do not touch during power-on and immediately after power-off. Hot surfaces may
cause burns.
Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder
Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes
Wiedereinschalten.
Führen Sie keine Änderungen oder Reparaturen durch. Gerät nicht öffnen!
Verhindern Sie das Eindringen von Fremdkörpern.
Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei
der mit Betauung oder Kondensation zu rechnen ist.
Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren.
Heiße Oberflächen können Verletzungen verursachen.
A lire avant mise sous tension! Français Lea primero! Español
Veuillez lire ces instructions de montage et d'entretien avant de mettre l'alimentation
sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation
ne doit être installée que par du personnel qualifié et compétent. En cas de
dommage ou dysfonctionnement, coupez immédiatement la tension d’alimentation
et retournez l’appareil à l’usine pour vérification. ! L’alimentation ne contient pas de
pièces échangeables Les données indiquées dans ce document servent
uniquement à donner une description du produit et n'ont aucune valeur juridique. En
cas de divergences, le texte anglais fait foi.
Conserve este manual como referencia para futuras consultas. La fuente de
alimentación solo puede ser instalada y puesta en funcionamiento por personal
cualificado. Por favor lea detenidamente este manual antes de conectar la fuente
de alimentación. Si se produce un fallo o mal funcionamiento durante la operación,
desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo
debe ser inspeccionado en fábrica. La información presentada en este documento
es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin
aviso. En casa de duda, prevalece el texto inglés.
AVERTISSEMENT
Prendre en compte les points suivants, afin
d'éviter toute détérioration électrique,
incendie, dommage aux personnes ou mort:
ADVERTENCIA
Riesgo de descarga eléctrica, incendio,
accidente grave o muerte:
Mettre l’alimentation hors tension avant toute intervention sur celle-ci et s'assurer
qu'il n'y a pas risque de redémarrage.
Ne pas ouvrir, modifier ou réparer l'alimentation.
Veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation
(trombones, pièces métalliques).
Ne pas faire fonctionner l'appareil dans un environnement humide ou dans un
environnement où il peut y avoir de la condensation.
Ne pas toucher le carter pendant le fonctionnement ou directement après la mise
hors tension. Surface chaude risquant d’entraîner des blessures.
Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite
una posible reconexión involuntaria.
No realizar ninguna modificación o reparación de la unidad. No abrir la unidad.
Evitar la introducción en la carcasa de objetos extraños.
No usar el equipo en ambientes húmedos. No operar el equipo en ambientes
donde se espere la formación de rocío o condensación.
No tocar durante el funcionamiento ni inmediatamente después del apagado. El
calor de la superficie puede causar quemaduras graves.
EN PIM60.125 Installation Manual
Product Description
The PIM60.125 is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV/ES1 output voltage.
The output fulfils the requirements for a limited power source according to NEC Class 2.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as
in industrial control, process control, monitoring, measurement, Audio/Video, information or
communication equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life without additional appropriate safety devices, that are suited for the end-
application.
If this device is used in a manner outside of its specification, the protection provided by the device
may be impaired.
Do not use this device on AC 100V mains with more than 3.6A load when the application is sensitive
to short output voltage dips during mains interruptions even with a length shorter than 20ms.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter),
the device is not suited to supply a local DC power network in residential, commercial and light-
industrial environments. No restrictions apply for local DC power networks in industrial
environments.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. Unused screw
terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The isolation of the device is designed to withstand impulse voltages of overvoltage category III
according to IEC 60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage
between the input terminal and the PE potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) the overvoltage
category is reduced to level II and a reduction in output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 0mm left
and right side. Increase the 0mm to 15mm in case the adjacent device is a heat source.
The device is designed, tested and approved for branch circuits up to 20A without additional
protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or 4A
C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive loads and capacitive loads. Capacitive loads should not be larger
than 2200µF with 5A or 8000µF with 2.5A additional current load.
Do not apply return voltages from the load to the output terminals higher than 16V.
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit.
The green DC-OK LED reports an output voltage above 9V of a running device.
At heavy overloads (when output voltage falls below 8V), the device delivers continuous output
current for 20ms. After this, the output is switched off for 170ms before a new start attempt is
automatically performed. This cycle is repeated as long as the overload exists.
Do not parallel devices for higher output currents.
Same devices can be connected in series for higher output voltages. It is allowed to connect as
many outputs in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 16V. The
output shuts down. To attempt a restart, turn the input power off for at least 90s.
Technical Data
A
ll values are typical figures specified at 230Vac, 50Hz input
voltage, 12V 5A output load, 25°C ambient temperature and after
a 5 minutes run-in time unless otherwise noted.
Output voltage DC 12V Nominal
Adjustment range 12 – 15Vdc Factory setting 12V
Output current 5.0 – 4.0A Below +60°C ambient
3.8 – 3.0A At +70°C ambient
Derate linearly between +60°C and +70°C
Input voltage AC
A
C 100 – 240V ±10%
Mains frequency 50 – 60Hz ±6%
Input current AC 1.0 / 0.6A At 120 / 230Vac
Power factor 0.55 / 0.47 At 120 / 230Vac
Input inrush current 15 / 36A pk At 120 / 230Vac, 40°C,
cold start
Efficiency 90.2 / 90.7% At 120 / 230Vac
Power losses 6.5 / 6.2W At 120 / 230Vac
Hold-up time 23 / 107ms At 120 / 230Vac
Temperature range -10 to +70°C
Max. wire size (litz wire) 4mm²
Wire size AWG
A
WG 20-10
Max. wire diameter 2.8mm
Wire stripping length 7mm / 0.28inch
Tightening torque 1Nm / 9lb.inch
Size (wxhxd) 36x90x91mm Without DIN-rail
Weight 225g / 0.5lb
Functional Diagram
Input
Fuse
&
Input
Filter
L
N
Output Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
Output
Voltage
Regulator
+
+
-
-
Output
Filter
V
OUT
DC-ok
LED
Power
Converter
Output Characteristic
Output voltage
10A
12V
Output current
8V
0V
4A 8A0A
Adjustment range
15V
A
B
2A 6A
A: continuous current
B: intermittent current
5A1A 3A 7A 9A
Temperature Range
Allowed output current at 12V
Ambient temperature
0A
-10
A: continuous
B: short term (max. 60s)
5.0A
+60 +70°C
3.8A
A
B

Other Puls Power Supply manuals

Puls Dimension QS3 Series User manual

Puls

Puls Dimension QS3 Series User manual

Puls CPS20.121 User manual

Puls

Puls CPS20.121 User manual

Puls CT10.241-C1 User manual

Puls

Puls CT10.241-C1 User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls FPT500.245-062-117 User manual

Puls

Puls FPT500.245-062-117 User manual

Puls DIMENSION CS Series User manual

Puls

Puls DIMENSION CS Series User manual

Puls DIMENSION UF Series User manual

Puls

Puls DIMENSION UF Series User manual

Puls QT40.241 User manual

Puls

Puls QT40.241 User manual

Puls QS5.DNET User manual

Puls

Puls QS5.DNET User manual

Puls POE.8AT-AC1 User manual

Puls

Puls POE.8AT-AC1 User manual

Puls Fiepos FPS300.245-034-105 User manual

Puls

Puls Fiepos FPS300.245-034-105 User manual

Puls PIANO Series User manual

Puls

Puls PIANO Series User manual

Puls MiniLine ML90 User manual

Puls

Puls MiniLine ML90 User manual

Puls CT5.241 User manual

Puls

Puls CT5.241 User manual

Puls PIANO Series User manual

Puls

Puls PIANO Series User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls CS10.244 User manual

Puls

Puls CS10.244 User manual

Puls QS20.481 User manual

Puls

Puls QS20.481 User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Puls QS20.481 User manual

Puls

Puls QS20.481 User manual

Puls CP10 Series User manual

Puls

Puls CP10 Series User manual

Puls Dimersion CP10.481 User manual

Puls

Puls Dimersion CP10.481 User manual

Puls Dimension CP20.481 User manual

Puls

Puls Dimension CP20.481 User manual

Puls Dimension CP Series User manual

Puls

Puls Dimension CP Series User manual

Popular Power Supply manuals by other brands

LiteOn PF-2123-1LD Series Startup guide

LiteOn

LiteOn PF-2123-1LD Series Startup guide

Radio Shack 22-508B user guide

Radio Shack

Radio Shack 22-508B user guide

Texas Instruments UCC28C56EVM-066 user guide

Texas Instruments

Texas Instruments UCC28C56EVM-066 user guide

EKSMA OPTICS PS-170 quick start guide

EKSMA OPTICS

EKSMA OPTICS PS-170 quick start guide

Peavey 4-AC operating instructions

Peavey

Peavey 4-AC operating instructions

Kenwood PS-33 instruction manual

Kenwood

Kenwood PS-33 instruction manual

GE LED 55 CC 1.4A ESRDL 1-10V 220-240 installation guide

GE

GE LED 55 CC 1.4A ESRDL 1-10V 220-240 installation guide

WAI PPS-400 Quick start manual

WAI

WAI PPS-400 Quick start manual

PowerBox Systems Champion SRS instruction manual

PowerBox Systems

PowerBox Systems Champion SRS instruction manual

Matsusada Precision R4GT Series instruction manual

Matsusada Precision

Matsusada Precision R4GT Series instruction manual

amig AMIG-LST Series Quick instructions

amig

amig AMIG-LST Series Quick instructions

Chroma 61601 quick start guide

Chroma

Chroma 61601 quick start guide

PIKO 35000 Installation and operating instructions

PIKO

PIKO 35000 Installation and operating instructions

nextys PSH150 user manual

nextys

nextys PSH150 user manual

Kodiak X2 user guide

Kodiak

Kodiak X2 user guide

Cisco 3600 Series Configuration note

Cisco

Cisco 3600 Series Configuration note

Honeywell HPTV2408UL Product installation document

Honeywell

Honeywell HPTV2408UL Product installation document

Siemens SITOP manual

Siemens

Siemens SITOP manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.