ECOMBO34 RED/GREEN EXIT/EMERGENCY LIGHT
ECOMBO34-RG
MI PORTANT
CAREFULLY BEFORE INSTALLING FIXTURE. R TAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.READ E
IMPORTANT SAFEGUARDS:
When using electrical equipment, basic safety precautions should always be followed including the following:
IMPORTANT:
The battery in this unit may not be fully charged. After electricity is connected to the unit for at least (24) hours, normal operation of
unit should
turn on.
In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90
minutes. Refer to your local codes for any additional requirements that may apply.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Note: UL recommended maximum mounting height is 19.8-ft.
1. Do not use outdoors.
2. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
3. Do not mount near gas or electric heaters.
4. Cap unused wires with enclosed wire nuts or other approved method.
5. Do not use this equipment for other than its intended use.
6. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
7. Disconnect AC power before servicing and installation.
8. Consult local building code for approved wiring and installation.
9. Use caution when servicing batteries.
11. Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
Wall Mount Installation
Fig: 1
Fig: 2
1. De-energize the circuit at the junction box where the exit sign is to be
installed.
2. Remove the exit sign stencil and set aside. Remove the hardware and LED
Lamp heads and set aside. Included plastic canopy and mounting plate are
not required for this installation and can be discarded.
3. Drill out the appropriate mounting pattern and the wire pass hole in the EXIT
back plate to fit the junction box being used.
4. Feed the red, black and white wires through the wire pass hole.
5. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes (Fig 1). Attach first lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing (Fig 2).
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard. Repeat to install the second lamp head.
6. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
7. Reference Wiring Diagram section and make proper electrical connections at
the junction box in the metal housing.
8. Fasten back plate to junction box cover.
9. Connect battery only after continuous AC power can be provided to the unit.
10. Remove proper Chevron(s) on the Exit face plate as required.
11. Secure face plate to housing.
Insert in Slots
Click Down
10. Any service on this equipment should be performed by qualified personnel only.
ECOMBO34 RED/GREEN EXIT/EMERGENCY LIGHT
Ceiling Mount Installation
Easy Answers
EXNY3-IN-0323
Cranbury, New Jersey 08512 USA
1. De-energize the circuit at the junction box where the exit sign is to be installed.
2. Remove the exit sign stencil and set aside.
3. Remove the canopy kit, hardware pack, mounting plate and LED lamp heads
from inside the EXIT and set aside.
4. Remove the mounting hole plug on the top of the frame.
5. Place the canopy nose through the mounting hole until the side of the frame
touches the canopy. Lock the frame onto the canopy by sliding the frame in a
direction parallel to the canopy length toward the narrow end of the mounting
hole. Slide the frame until both snaps engage the canopy nose preventing any
motion back out of the hole.
6. Feed the red, black and white wires through center of mounting canopy hole.
7. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes (Fig 1). Attach first lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing (Fig 2).
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard. Repeat to install the second lamp head.
8. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
9. Reference Wiring Diagrams section and make proper electrical connections at
the junction box in the metal housing.
10. Secure the EXIT canopy to the steel mounting plate using the screws
provided and fasten to junction box.
11. Connect battery only after continuous AC power can be provided to the unit.
12. Remove proper Chevron(s) on the Exit face plate as required.
13. Secure face plate(s) to housing.
NOTE: Unused input lead must be properly insulated with wire nut or other
approved method.
WIRING DIAGRAMS
1. Remove the faceplate(s) from the unit’s housing.
2. Gently pop out the red diffuser lens from the faceplate(s). Replace the green
diffuser lens onto the faceplate(s).
3. Toggle the dip switch from R to G on the RED/GREEN switchable LED board.
4. Replace the faceplate(s) on the housing to finish installation.
RED-to-Green Conversion
1. Remove the faceplate from the unit’s housing.
2. Remove the backplate by pushing out the two locking clips on the inside of
the unit’s housing.
3. Attach the two EXIT faceplates to the housing to complete the conversion.
Single-to-Double Face Conversion
1. Apply AC power to the unit. The LED indicator will be RED.
2. After the battery has been left to charge for 24 hours, test the unit by pushing
the switch. The LED indicator turns OFF, the LED board stays ON and the
lampheads should turn ON at this time.
3. When the switch is released, the LED indicator turns back to RED, the LED
board stays ON and the lampheads should turn OFF at this time.
OPERATION
Caution: Always turn off AC power to the equipment before servicing. Servicing
should be performed only by a qualfied service technician. Use only
MANUFACTURER supplied replacement parts.
MAINTENANCE
Fig: 3
2023
BLUE(-)
YELLOW(+) LAMP
To Remote lamp
DIP SWITCH
RED/GREEN switchable LED board
STANDARD
REMOTE CAPABLE
RED BLACK
RED BLACK
BLUE(-)
YELLOW(+) LAMP POWER
LAMP
GREEN RED
DIP SWITCH
GREEN RED
RED 277VAC
BLACK 120VAC
WHITE COMM
RED 277VAC
BLACK 120VAC
WHITE COMM
YELLOW(+)
BLUE(-)
BATTERY
POWER
RED BLACK
LAMP
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
RED BLACK
BATTERY
RED/GREEN switchable LED board
BATTERY: The battery supplied with the Battery Backup model requires no
maintenance. However, it should be tested periodically and replaced when it no
longer operates the connected fixtures for the duration of a 30-second or
90-minute test. The battery supplied in this equipment has a life expectancy of
5 years when used in a normal ambient temperature of 72°F.
1. De-energize the circuit at the junction box where the exit sign is to be installed.
2. Remove the exit sign stencil and set aside.
3. Remove the canopy kit, hardware pack, mounting plate and LED lamp heads
from inside the EXIT and set aside.
4. Remove the mounting hole plug on the right side of the frame.
5. Place the canopy nose through the mounting hole until the side of the frame
touches the canopy. Lock the frame onto the canopy by sliding the frame in a
direction parallel to the canopy length toward the narrow end of the mounting
hole. Slide the frame until both snaps engage the canopy nose preventing any
motion back out of the hole.
6. Feed the red, black and white wires through the center of mounting
canopy hole.
7. For single face, left side end mount, remove and switch back plate and face
plate before installing the side mounted LED lamp head.
8. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes (Fig 1). Attach lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing (Fig 2).
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard.
9. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
10. Reference Wiring Diagrams section and make proper electrical connections at
the junction box in the metal housing.
11. Secure the EXIT canopy to the steel mounting plate using the screws
provided and fasten to junction box.
12. Connect battery only after continuous AC power can be provided to the unit.
13. Remove proper Chevron(s) on the Exit face plate as required.
14. Secure face plate(s) to housing.
End Mount Installation (with one lamp head)

Popular Safety Equipment manuals by other brands

fadini SEMIAUTOMATIC TALOS instructions

fadini

fadini SEMIAUTOMATIC TALOS instructions

PMI Chest Roller instructions

PMI

PMI Chest Roller instructions

Hiltron security KBSS Installation

Hiltron security

Hiltron security KBSS Installation

TEUFELBERGER tripleA Manufacturer's information and instructions for use

TEUFELBERGER

TEUFELBERGER tripleA Manufacturer's information and instructions for use

TEUFELBERGER OP LOOP Manufacturer's information and instructions for use

TEUFELBERGER

TEUFELBERGER OP LOOP Manufacturer's information and instructions for use

ORTEMA INUTEQ-H20 instruction manual

ORTEMA

ORTEMA INUTEQ-H20 instruction manual

Southwire Triggers TSS-01 operating instructions

Southwire

Southwire Triggers TSS-01 operating instructions

CAME DFWN2000 installation manual

CAME

CAME DFWN2000 installation manual

ABB PrimEvo XT100E Instruction leaflet

ABB

ABB PrimEvo XT100E Instruction leaflet

CMC Rescue Patient Tie-In System manual

CMC Rescue

CMC Rescue Patient Tie-In System manual

Husqvarna 5791167-03 Operator's manual

Husqvarna

Husqvarna 5791167-03 Operator's manual

Capital Safety DBI SALA KD1TALTWIN Specific instructions

Capital Safety

Capital Safety DBI SALA KD1TALTWIN Specific instructions

Otto Bock 17PA1 Series Instructions for use

Otto Bock

Otto Bock 17PA1 Series Instructions for use

Performance Variable Omega manual

Performance Variable

Performance Variable Omega manual

ABS ABS-Lock X-Solar installation manual

ABS

ABS ABS-Lock X-Solar installation manual

CRESTO BASELINE 1231 user guide

CRESTO

CRESTO BASELINE 1231 user guide

E2S BExCP3C-BG instruction manual

E2S

E2S BExCP3C-BG instruction manual

La Siesta TREE ROPE TR-H3 quick start guide

La Siesta

La Siesta TREE ROPE TR-H3 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.