RAMFAN FlowPath UB20 Series Manual

SM-EFATEX Rev E - Page
FlowPath™ Control
Euramco Group | 2746 Via Orange Way, Spring Valley CA 91978 USA
Ph: +1-619-670-9590 | www.euramco.com
TECHNICAL INFORMATION AND ORIGINAL INSTALLATION
INSTRUCTIONS
SM-EFATEX REV E
Portable Ventilators for
Hazardous Locations UB20xx EFi120xx
EFi75xx EFi150xx
Applicable Models:
The Portable Ventilators described herein are intended
for use in Explosive Atmospheres in accordance
with the limitations of the rating. It is the user’s
responsibility to determine the suitability of equipment
for the intended purpose.
II 2 G Ex db eb IIB T6 Gb
0539 Demko 09 ATEX 0926969X
IECEx UL 13.0062X
0539

SM-EFATEX Rev E - Page 1 of 13
WARNING!
These units are intended for Explosive Atmosphere use in accordance with ATEX Directive
2014/34/EU. It is the user’s responsibility to determine the suitability of this equipment for
the intended purpose.
CAUTION! THESE FANS ARE NOT INTENDED FOR USE IN MINES SUSCEPTIBLE TO
FIREDAMP.
Explosion Proof Fan Rated:
II 2 G Ex db eb IIB T6 Gb
Euramco Safety hereby declares that the equipment listed in this manual conforms to the
relevant Essential Health and Safety Requirements of the European Machinery Directive and
standards listed below.
Council of European Communities Directive:
Directive 2014/34/EU.
Standards to which conformity is declared:
See “Declaration of Conformity”
Category, Group and Zone Classications
According to ATEX Directive (2014/34/EU)
II 2 G Ex db eb IIB T6 Gb
0539 Demko 09 ATEX 0926969X
IECEx UL 13.0062X
Special Conditions for Safe Use:
The unterminated power cable (ying leads) must be terminated by the end user in the eld
according to installation standards, IEC/EN/ABNT NBR IEC 60079-14, to a suitable safe power
location, or under one apparatus or enclosure in one of the protection concepts for use
in hazardous locations. Flying leads consist of a brown “Hot” wire, blue “Neutral” wire and
yellow/green “Ground” wire.
T6 Temperature Classication:
85°C T6 - According to IEC 60079-0 / EN 60079-0 / ABNT NBR IEC 60079-0.
To ensure that there is no risk of ignition due to hot surfaces, the equipment is classied with
regard to the maximum surface temperature of any part of the equipment while in operation
based on the ambient temperature of 40°C. Equipment must be selected with a suitable
temperature classication for the gases and vapors present where the equipment is to be
installed. Ensure that the maximum surface temperature of any parts of the equipment are
below the ignition temperature of the explosive atmosphere concerned.
This equipment is intended for use in ambient temperatures ranging between -20°C and
+40°C.
The letter “X” at the end of the ATEX, IECEx, and INMETRO certicate numbers
indicate a special condition for safe use. This special condition of safe use refers
to the fact that the Hazardous Location Fans referenced herein are supplied
without an AC power plug termination for the power cable.

SM-EFATEX Rev E - Page 2 of 13
Classication: Ex de
According to IEC 60079-1 / EN 60079-1 / ABNT NBR IEC 60079-1
Flame Proof Enclosures with Increased Safety Components
IEC 60079-7 / EN 60079-7 / ABNT NBR IEC 60079-7
RAMFAN SAFETY VENTILATORS ELECTRICAL RATING
Model No. Euramco Part
No.
Input Voltage Frequency Current
UB20xx EF7002
EF8002
115 VAC
230 VAC
50/60 HZ
50/60 HZ
2.3 A
1.2 A
EFi75xx EB7201XX
EB7201XX-230
115 VAC
230 VAC
50/60 HZ
50/60 HZ
8.8 A
4.4 A
EFi120xx EA8120XX-110
EA8120XX
110 VAC
240 VAC
50 HZ
50 HZ
10.8 A
5.5 A
EFi150xx EG8200XX
EG8200XX-230
115 VAC
230 VAC
50/60 HZ
50/60 HZ
15 A
8.1 A
Description of Apparatus
The Portable Ventilator assemblies represented herein consist of an Approved Explosion
Proof Electric Motor Rated: Ex d IIB as listed below.
RAMFAN SAFETY VENTILATORS MOTOR
Model No. Part No. Input Voltage/
Frequency
Impeller Motor part No.
UB20xx EF7002
EF8002
115 VAC, 50/60 HZ
230 VAC, 50/60 HZ
Plastic 1933007415
1933007419
EFi75xx EB7201XX
EB7201XX-230
115 VAC, 50/60 HZ
230 VAC, 50/60 HZ
Metal 1133007405
EFi120xx EA8120XX-110
EA8120XX
110 VAC, 50 HZ
240 VAC, 50 HZ
Plastic 1223007401
EFi150xx EG8200XX
EG8200XX-230
115 VAC, 50/60 HZ
230 VAC, 50/60 HZ
Plastic 1133007417
The Flame Proof Electric Motor
Power Requirements: See chart above.
Ambient Temperature Range: -20°C<Tamb<+40°C
Maximum Inlet Temperature: 40°C
Maximum Temperature Conveyed to Atmosphere: 2°C above air inlet temperature
Maximum Fan Casing Pressure: 12” / 305mm w.g.
Ingress Protection to IEC 529: IP55
Marked: Electric Motor for Hazardous Locations.
Flame Proof Enclosure: Ex d IIB
The electric motor consists of one ameproof enclosure, which contains less than 6%
magnesium by weight. The on/o switch is housed within the motor enclosure, and is
operated by a shaft, extending out from the rear end bell to a lever. The lever is accessible via
an attached push rod.

SM-EFATEX Rev E - Page 3 of 13
Motor connections are made through a non-detachable cable, secured to the motor with
an approved Flame Proof cable gland from the company Hawke, model 501/421/0/M20
and complies with International Standards EN 60079-0, EN 60079-1, and EN 60079-7. The
electric motor drives an aluminum or plastic fan blade which is enclosed in a plastic, statically
conductive housing with a conductivity rating of <1 giga ohms. Connection to the motor is
facilitated by a Terminal Block mounted in an Increased Safety/Flame Proof Enclosure rated
II 2 G Ex e II T6, from the company Rose Industries, Part Number 05080806, and covered
under ATEX Certicate No. PTB 00ATEX1063. This box was designed to conform to
International Standards EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0 and EN 61241-1.
The enclosure features stainless steel grounding lugs, with a high heat silicon gasket.
The Flame Proof enclosure has attached, approved, explosion proof cable glands, as
described below.
Rated: II GD Ex e II
Type: Polyamide Ex metric conforms to International Standards EN 60079-0, EN 60079-1, EN
60079-7, EN 61241-0 and EN 61241-1.
Material: Polyamide Color: Black/Blue
Grommet: NBR Protection Classication: IP68
Temperature Range: -4°F to +212°F Approval: PTB 00 ATEX 1063
The power cables are not terminated with power plugs. See Special Conditions for safe use.
The fans are assembled with both Inlet and Outlet Safety Guards that conform to the safety
standards to prevent danger zones being reached by upper limbs in the BS EN ISO 12100
Safety Machinery – Guards Standard.
Installation and Start-Up
During the installation and start-up of the RAMFAN blowers in areas where there is a risk of
explosion:
• Design of the electrical installations must be in accordance with EN/IEC/ABNT NBR
IEC 60079-14.
• Ensure power source is providing an electrical ground.
• Blowers must be integrated into a system in a way to support accessibility for
regular maintenance.
• Blowers are designed for portable, nonxed installation. Blowers have no mount
ing features to support rigid duct or x installations.
• Perform careful inspection of each blower system to ensure ducting is securely
attached to blower. All components of the blower system are made of electrically
conductive material. It is very important to properly and securely attach each component to
maintain a ground path.
• Ensure set-up, installation, operation and maintenance are performed only by
properly trained personnel.
• Operation after a faulty installation or maintenance shall be considered as
unintended use.
INSTRUCTIONS AND CARE

SM-EFATEX Rev E - Page 4 of 13
Before STARTING the FIRST time
DO NOT start operation if there are any signs of shipping damage to the blade, guards or
housing. STOP, call your dealer. USE Ex-Rated receptacles for this equipment. IT IS NOT
recommended to use extension cords for high amperage load. (See power rating label on
limit).
OPERATION
Always ensure the switch is in the “Down/OFF” position prior to connecting the ventilator to a
power source.
Stop the blower if mechanical noise, vibration or other abnormal conditions occur. Any noise
other than turbine-type pitch is not normal.
This unit is equipped with thermal overload protection with automatic reset. Motor will
restart without warning after protector trips. To protect the user, disconnect unit and
determine cause of protector trip.
Conductive RAMFAN Portable Ventilators are made with statically conductive materials.
When ducting is required is required to remote the ventilator from the point of application in
a potentially explosive environment, the ducting must be:
1. Statically Conductive, Surface resistance ≤106 ohms.
2. Flexible.
3. Reinforced with integrated helical steel wire, spaced to prevent duct material
from collapsing, when airow is inadvertently blocked on suction side of duct.
MAINTENANCE
• Disconnect power before inspection, disassembly or cleaning.
• Never immerse or directly spray motor with liquids.
• Clean ventilator with commercially available biodegradable cleaning solutions. Do
not use solvents containing hydrocarbons (i.e. MEK, Acetone).
• Inspect clearance between impeller tips and fan casing for minimum acceptable
clearance with pin gauges as shown in picture below. Minimum acceptable
impeller tip clearance is 0.079” / 2mm.
• Clean fan, impeller, & motor to remove accumulated dust or debris. Clean the
impeller and motor with a damp cloth only, to avoid any possibility of a disruptive
breakdown due to electrostatic charging.
• Inspect impeller & nger guards annually for damage. Replace as necessary.
• There are no user serviceable parts. Contact factory for replacement part
applicability.
• Do not change make or model number of motors for any reason!

SM-EFATEX Rev E - Page 5 of 13
CAUTIONS
Do not move ventilator while fan is in operation. Use good lifting practices when moving
ventilator to prevent bodily injury.
Blower should be operated and repaired by trained personnel only.
Do not operate if there is any physical damage to cord, plug or receptacle.
Keep ngers and hands clear of fan blade. Keep fan guard securely in place. Do not operate
with damaged or missing fan guards.
Use properly grounded power receptacle in potentially explosive atmospheres, and for
operation safety. Ensure continuity to the earth.
Fatal electrical shock may result if motor frame and adjacent metal are not grounded in
compliance with electrical code.
Keep area clear of rock and debris.
Keep away from children.
WARRANTY
Positive Pressure Ventilators Turbo Ventilators and portable blowers, excluding motor
and wear items, are warranted for one year from date of original purchase, to be free of
defects in material and workmanship. Electric motors are warranted by their respective
manufacturers. Wear items include feet, fasteners, handles, wheels, and paint are not
covered under the warranty. Fan impellers and shrouds are warranted to be free of defects
in material and workmanship for ve years. Components exposed to salt water service are
warranted for a period of one year from date of original purchase. Duct is not warranted due
to its intended use.
Authorization for warranty repairs must be obtained from the factory. There are no
other warranties expressed or implied.

SM-EFATEX Rev E - Page 6 of 13
Fan Performance Characteristics
Fan performance is characterized as airow as a function of backpressure. Backpressure is
typically a function of the length of exible duct attached to the fan.
Maximum airow also referred to as free air occurs at 0 mm/ 0” w.g.
The rst chart shows 4 performance curves for all four ATEX fans running on 50Hz AC power.
The second chart show 3 performance curves for three of the ATEX fans, running on 60Hz.
Please note that the EFi120xx is not designed to run eciently on 60Hz AC power and does
not appear on the 60Hz chart for this reason.
Fan Performance Characteristic for Fans Running on 50Hz AC power

SM-EFATEX Rev E - Page 7 of 13
Fan Performance Characteristic for Fans Running on 60Hz AC power

SM-EFATEX Rev E - Page 8 of 13
TYPICAL VENTILATOR EXPLODED VIEW ACCESSORIES
FOR ATEX, IECEx AND INMETRO HAZARDOUS LOCATION FANS
Euramco Group has several optional antistatic / conductive airow duct accessories designed
explicitly for use with our Hazardous Location Fans to support various end user applications
as identied in the list below.
ACCESSORY LIST
Fan Model Accessory P/N Description
UB20xx EF7004CS Quick-Couple Canister with 8” x 15’ Duct, Antistatic
EF7004CL/DS Quick-Couple Canister with 8” x 5’ & 8” x 15’ Duct,
Antistatic
EF7004CL/DL Quick-Couple Canister with 8” x 5’ & 8” x 25’ Duct,
Antistatic
EF7004CL Quick-Couple Canister with 8” x 25’ Duct, Antistatic
FDT-0815CBB Duct, 8” x 15’, Antistatic with Belt and Belt
FDT-0825CBB Duct, 8” x 25’, Antistatic with Belt and Belt
EF0304X Duct Adapter, 8” / 20cm
DC8 Duct Coupler, 8”, Stainless Steel
MED189XX Manhole Entry Device, Conductive
MED90XX MED 90˚ Elbow, Conductive
MED5100XX Manhole Entry Device (MED), Conductive,
Assembly
MEDIUM MED Universal Mount
EFi75xx FDT-1215CBB Duct, 12” x 15’, Antistatic with Belt and Belt
FDT-1225CBB Duct, 12” x 25’, Antistatic with Belt and Belt
EC0301 Duct Adapter, 12”/30cm to 8”/20cm
DC12 Duct Coupler, Stainless Steel
EFi120xx & EFi150xx FDT-1615CBR Duct, 16” x 15’, Antistatic with Belt and Ring
FDT-1625CBR Duct, 16” x 25’, Antistatic with Belt and Ring
FDT-1625CBB Duct, 16” x 25’, Antistatic with Belt and Belt
EA7106 Duct Adapter, 16” / 40cm
DC16 Duct Coupler, Stainless Steel

SM-EFATEX Rev E - Page 9 of 13
UB20XX
EF7002 / EF8002
1
2
3
4
5
6
9
10
11
12
1
7
8
1. E7205K – DUCT ADAPTER KIT 8. EZ-16/3-E POWER CABLE
2. EF7019 – PULL ROD 9. EF7105AC – HOUSING, CONDUCTIVE
3. EM-F.33-60XPEX – EF7002 ATEX MOTOR 10. ST010 - STATOR
4. EM-F.33-230VXP – EF8002 ATEX MOTOR 11. ED0170 – MOTOR MOUNTING RING
5. ED0170 – MOTOR MOUNTING RING 12. BL011 - IMPELLER
6. EX-312-RWB – CORD STRAP
7. EZ-080305003CE – JUNCTION BOX

SM-EFATEX Rev E - Page 10 of 13
TYPICAL VENTILATOR EXPLODED VIEW
1
2
34
56
10
911 1
7
8
1. EB7006K -12”/30 cm DUCT ADAPTER KIT 7. EZ-14/3E – POWER CABLE
2. EB7018 - EFi75xx SWITCH ROD 8. EA7007 - ADAPTER CASTING, C-FACE
3. EZ-CAP-A027 – PUSH CAP 9. EB7201XXHA - 12” BLOWER HOUSING ASSY
4. EM-F.75-60XPEX - MOTOR 10. EZ-312-RWB CORD STRAP
5. EA7004 – FLANGE 11. BL008 – IMPELLER
6. EZ-080305002CE – JUNCTION BOX
EFi75XX
EB7201XX / EB7201XX-230

SM-EFATEX Rev E - Page 11 of 13
TYPICAL VENTILATOR EXPLODED VIEW
EFi120XX
EA8120XX / EA8120XX-110
12
34
57
8
6 9
10
11
1. EA7116 - 16”/40 cm DUCT ASSY (INLET) 7. EZ-312-RWB - CORD STRAP
2. EC7018 - SWITCH ROD 8. EG8200XXHA - HOUSING ASSY
3. EM-F1.5-60/50XPEX - MOTOR 9. EA7007 - ADAPTER CASTING, C-FACE
4. EA7004 - FLANGE 10. BL914 - IMPELLER
5. EZ-080305002CE - JUNCTION BOX 11. EA7117- 16”/40 cm DUCT ASSY (EXHAUST)
6. EZ-14/3 AWG - POWER CABLE

SM-EFATEX Rev E - Page 12 of 13
TYPICAL VENTILATOR EXPLODED VIEW
EFi150XX
EG8200XX/ EG8200XX-230
12
3
457
8
10 11
9
6
1. EA7116 - 16”/40 cm DUCT ASSY (INLET) 7. EZ-312-RWB - CORD STRAP
2. EC7018 - SWITCH ROD 8. EG8200XXHA - HOUSING ASSY
3. EM-F1.5-60/50XPEX - MOTOR 9. EA7007 - ADAPTER CASTING, C-FACE
4. EA7004 - FLANGE 10. BL914 - IMPELLER
5. EZ-080305002CE - JUNCTION BOX 11. EA7117- 16”/40 cm DUCT ASSY (EXHAUST)
6. EZ-14/3 AWG - POWER CABLE

SM-EFATEX Rev E - Page 13 of 13
WIRING DIAGRAM
MOTOR LEADS LINE CORD
Ground Screw
Yellow/Green wire from Motor Cord
Black Wire #1 from
Motor Cord
Black Wire #2 from
Motor Cord
Ground Screw
Yellow/Green wire from Power Cord
Brown Wire from Power
Cord
Blue Wire from Power Cord
Other manuals for FlowPath UB20 Series
1
This manual suits for next models
3
Table of contents
Other RAMFAN Fan manuals
Popular Fan manuals by other brands

Vortice
Vortice M 10/4 Instruction booklet

Euromatic
Euromatic TNLF6 instruction manual

Greenheck
Greenheck 100 Series Installation, operation and maintenance manual

Sulion
Sulion NATI L manual

Vent-Axia
Vent-Axia MVDC-MS Installation and wiring instructions

Helios
Helios VDD T120 Series Installation and operating instructions