Ravel RE 150D Guide

RE – 150D
Fire Alarm Control Panel
Installation, Commissioning & Operating
Manual
RAVEL ELECTRONICS PVT LTD.,
150-A, Electronics Industri l Est te,
Perungudi, Chenn i - 600 096.
Ph.: 91-44-24961004, 24960825.
F x: 91- 44 - 42049599.

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
1

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
2
Fire Alarm System Limitations
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual Call Points, audible warning
devices, and a fire alarm control with remote notification capability–
can provide early warning of a developing fire Such a system,
however, does not assure protection against property damage or loss
of life resulting from a fire The Manufacturer recommends that smoke
and/or heat detectors be located throughout a protected premise
following the recommendations of of IS 2189: 1999 and any other local
codes of practice that are applicable While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a variety
of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors Smoke detectors also may not sense a fire
on another level or floor of a building A second-floor detector, for
example, may not sense a first-floor or basement fire
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls,
or chimneys may inhibit particle or smoke flow
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located
• Smoke particles may be blown away from detectors by
air outlets
• Smoke particles may be drawn into air returns before
reaching the detector
The amount of "smoke" present may be insufficient to alarm smoke
detectors Smoke detectors are designed to alarm at various levels of
smoke density If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
3
Smoke detectors, even when working properly, have sensing
limitations Detectors that have photo electronic sensing chambers
tend to detect smoldering fires better than flaming fires, which have
little visible smoke Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering fires Because
fires develop in different ways and are often unpredictable in their
growth, neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire
Smoke detectors cannot be expected to provide adequate warning
of fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc )
While a fire alarm system may lower insurance rates, it is not a
substitute for fire insurance!
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level Rate-of-rise heat detectors may be
subject to reduced sensitivity over time For this reason, the rate-of-rise
feature of each detector should be tested at least once per year by a
qualified fire protection specialist Heat detectors are designed to
protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as
the control panel and in rooms used by the system for the connection
of alarm transmission wiring, communications, signaling, and/or
power. If detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report a fire
Audible warning de ices such as hooters and bells may not alert
people if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building Any
warning device may fail to alert people with a disability or those who
have recently consumed drugs, alcohol or medication

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
4
Please note that:
• Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy
• Studies have shown that certain people, even when they hear a fire
alarm signal, do not respond or comprehend the meaning of the
signal It is the property owner's responsibility to conduct fire drills and
other training exercise to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss
A fire alarm system will not operate without any electrical power If AC
power fails, the system will operate from standby batteries only for a
specified time and only if the batteries have been maintained
properly
Equipment used in the system may not be technically compatible with
the control panel It is essential to use only equipment listed for service
with your control panel
The most common cause of fire alarm malfunction is inadequate
maintenance To keep the entire fire alarm system in excellent working
order, ongoing maintenance is required as per the manufacturer's
recommendations Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance A maintenance
agreement should be arranged through the local manufacturer's
representative Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be performed
by authorized professional fire alarm installers only Adequate written
records of all inspections should be kept

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
5
NOTES:

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
6
Table of Contents
CHAPTER 1: Introduction …………........…….....................7
1.1: System Design & Planning..............................................7
1.2: General .………...............................................................7
1.3: Fire Alarm Procedure ….................................................8
1. : User Responsibility.........................................................8
1.5: Routine test............….....................................…………..9
CHAPTER 2: Product Description .....................................10
2.1: Product Features ...........................................................10
2.2: Specifications ...........................................................…..11
2.3: Controls and Indicators .................................................12
2.3.1: LED Indication...........................................…………...12
2.3.2: Controls……………………….…..….…………………..13
2. : Mechanical Construction…….……………………………1
CHAPTER 3: Installation ..............................……..........….1
3.1: Installation Precaution……….……………………………15
3.2: Mounting Details ...................................................….…17
3.3: Input Circuits.............................................................….18
3. : Output Circuits .........................................................….19
CHAPTER 4: Operating Instructions...….............….….....20
.1: Switch Functions …………………….............................20
.2: Status LED....................................….........................…21
.3: Operation..................................................................….22
.3.1: Zone Fault Response ................................................22
.3.2: Zone Fault Restoral …...............................................22
.3.3: Zone Fire Response ...........................................….. 22
.3. : Zone Fire Restoral …...........................................…. 23
.3.5: Zone Isolate……….………….………………..............23
CHAPTER : Servicing……………………………..…………24
5.1: Walk test mode… …………………….............................2
5.2: Installation/Replacement of PCB ..............................…25
5.3: Test……....................................................................….25
5. : Lamp Test…..............................................................….26
CHAPTER 6: Power Calculation….….………………………26
CHAPTER 7: Trouble Shooting……….……………………..27
CHAPTER 8: Wire Requirement……….……..………….….28
CHAPTER 9: Abbreviation……..….………………….….…29
General Arrangement diagram……………………………...30

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
7
Chapter 1: Introduction
This manual is intended as a complete guide to the RE 150D model
Conventional Fire Control Panel User operating Instructions are
provided in the first part of this manual This is followed with sections
describing installation and commissioning procedures and full
technical details are provided
1.1 System Design and Planning
It is assumed that the system, of which this control panel is a part,
has been designed by a competent fire alarm system designer in
accordance with the requirements of IS 2189: 1999 and any other
local codes of practice that are applicable The design drawings
should clearly show the positions of the field devices and the control
equipment
1.2 General
The panel is self-contained with integral power supply and space
provision for two sealed lead-acid standby batteries and comply with
the requirements of IS 2189: 1999 The panel functions are
microprocessor controlled and test and isolate functions are included
Provision is made for a repeater function of panel status output The
panel can accept, per zone, automatic detectors with a total
maximum loading of 2 4mA quiescent current rating (refer to chapter
2 2), and an unlimited number of manual call points
End of Line (EOL) de ices
The panels can continue to monitor manual call points with
detectors removed, providing the detectors are fitted with a Schottky
diode and an a EOL device is used
Installation
The panel is easy to install and operate The panel fascia is retained by
tamper-proof screws

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
8
1.3 Fire Alarm Procedures
In accordance with IS 2189: 1999, written procedures should be laid
down for dealing with alarms of fire, fault warnings, and the isolation of
any part of the system The responsible person should ensure that users
of the system are instructed in its proper use and are familiar with the
procedures
On hearing the fire alarm:
CARRY OUT THE PRESCRIBED PROCEDURE Subsequent actions will
depend on the circumstances, and may include silencing the audible
alarms and resetting the system, as described later
Fault Indication:
If the control panel indicates a Fault condition, make a note of all
illuminated indicators, refer to the chart on Page 27, and call the
service engineer
1.4 User Responsibility
In addition to the routine testing described on routine test, the user has
a responsibility for ensuring certain actions are taken following a fire or
fault, and for implementing remedial action following a specified
incidence of false alarms As a minimum, the user shall record any
incident and inform the service organization, who may be required to
retest the system The user's responsibilities are described fully in IS
2189: 1999

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
9
1.5 Routine Testing
In order to ensure that the system is fully operational, and to comply
with the requirements of IS 2189: 1999, the following routine attention is
recommended:
Daily - Check the panel to ascertain that it indicates normal
operation If any fault is indicated check that it has been recorded
and that the appropriate actions have been taken, e g informing the
maintaining company
Weekly - Test at least one detector or call point to confirm the
operation of the panel and the audible alarms Test a different zone
each week and, if possible, a different device Keep a record of the
device and zone tested each week Record and report any
malfunction
Quarterly - The responsible person should ensure that every three
months the system is checked by a competent person Check the
standby batteries and the charger voltage Test at least one device in
each zone to check the panel functions Check the operation of the
audible alarms and any link to a remote manned centre, Central
Station, etc Carry out a visual inspection of the installation to check
for alterations or obstructions and issue a certificate of testing
Annually - The responsible person should ensure that, in addition to
the quarterly checks, each device on the system is tested and that a
visual inspection is made of the cable fittings and equipment
Note: The control panel case should be cleaned periodically by
wiping with a soft, damp cloth Do not use any solvents

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
10
Chapter 2: Product Description
The RE – 150D is a 2 zone microprocessor based conventional Fire
Alarm Control Panel The Panel accepts water flow devices,
conventional input devices like 2 wire smoke detectors, pull stations
and other normally open contact devices The Outputs include
Notification Appliance Circuits (sounders), Three Form – C relays for
alarm It supervises all wiring, AC voltage and Battery level
2.1 Product Features
Fully confirms IS 2189: 1988
16SWG Rugged CRCA with powder coated finish
Modular construction
Operates on 230V, A C supply
Battery backup with built in charging
16x2 LCD Dot matrix Display
Fire / Fault status in unambiguous coloured LED indication
Low battery / battery fail warning audio / visual indication
A C fail audio / visual warning
Charger fail audio / visual warning
System on, AC on, Battery on & Charger on indications
Potential Free Relay Contacts for actuators
Lamp test facility
One man walk test facility
Compatible to all types of conventional detectors
Twin RED LED indication for fire
Zone Isolation facility with loop voltage cut off
Earth Fault with Audio and Visual Indications
Supervised Sounder 24v DC output for External notification
devices (Sounder, Bell, etc )

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
11
2.2 Specification
AC Power
220-240 VAC, 50 Hz
Wire size: 1 5 Sq mm with 600V insulation
Battery (Lead Acid only)
Charging: Constant Voltage – 27 6v @ 0 5A
Charging Capacity: 26 Amp Hour Battery Max
System Quiescent Current: 70mA + (4 4 – 6 8mA per zone)
Initiating De ice Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage: Nominal 24 VDC
Alarm Current: 15 – 35mA threshold
Short Circuit Current: 42mA Maximum
Loop resistance: 50 ohms Maximum
End-Of-Line Resistor: 4 7K, 1/4watt
Standby Current: 6 8mA (2 4mA for Detectors)
Notification Appliance Circuits (Sounder Circuit)
Class – B wiring
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output: 0 2A X No of zone
End-Of-Line Resistor: 4 7K, 1/4watt
Three Form – C Relays
Relay Contact Rating: 2Amps @ 30 VDC, 2Amps @ 30VAC (Fire – 3
No’s)
24 VDC Power – For remote de ices
Operating Voltage: 24VDC, 500mA Max

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
12
2.3 Controls and Indication
2.3.1 LED Indication
System On – Green
A C Power On – Green
Battery On – Green
Charger On – Green
AC Power Fail – Yellow
Battery Fail – Yellow
Earth Fault – Yellow
Battery Low – Yellow
Common Hooter Fault – Yellow
AUX Isolate – Yellow
Walk Test – Yellow
Silence – Yellow
Zone Fire – Red
Zone Fault – Yellow
Zone Isolate – Yellow

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
13
Local Buzzer
A piezo buzzer provides separate and distinct sounds for
alarm and trouble conditions:
Alarm – steady
Fault – pulse 0 5sec ON and 0 5sec OFF
2.3.2 Controls
SELECT, TEST and ISOLATE Keys: The SELECT is used to select any
particular zone for isolation or for test When it is pressed, zone 1
will be selected first with the identification of ISOLATE LED
blinking; consecutive SELECT key presses can change the zone
selection to 2 The particular zone can be isolated by pressing
ISOLATE key or tested by pressing TEST key
When pressing the ISOLATE by selecting the zone, the
previous status of isolate LED will be interchanged, i e it may go
from ON to OFF or OFF to ON The ON status indicates that the
zone has been isolated By the time, no voltage will be there in
the isolated zone loop And the OFF status indicates that the
zone has been normalized
After the selection of particular zone, if the TEST key is
pressed, that particular selected zone is tested with buzzer
sound
Note:
a. We strongly recommend to avoid isolating any particular
zone unless it is essential for maintenance purpose.
b. For zone isolation and their normalization, use IS LATE key.
ACK Key: During fire/fault condition, ACK key is used to silence
the external Sounders (NAC) and the internal buzzer tone
RESET Key: This key is pressed to reset the entire system and
While in reset condition, all detector loop voltages are cut off
up to 3 seconds for Detectors and MCPs, Then voltages are put
on to the loop
Note: The zone loop voltage will cut off only in fire
condition during reset.

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
14
WALK TEST Key: For testing of detector or MCP, we can go for
walk test mode by pressing this key This mode can identify by
walk test LED ON / OFF And this same key is used to quit from
walk test mode
Note: During in walk test mode, if there is no more operation
in the testing, automatically it will quit from walk test mode after
10 minutes.
2.4 Mechanical Construction
The enclosure of the Panel is constructed by CRCA sheet
with powder coated finish and it’s designed to afford the degree
of protection as per IP-54 The
∅19
mm knock outs are given for
cable entry at the top of the cabinet
The panel also has a built in battery provision to
accommodate 2 Nos of 12v, 7Ah batteries (Up to 12 Zone)
The front side of the panel consists of the following,
a Tactile switches
b LED indications

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
15
Chapter 3: Installation
3.1 Installation Precaution
Installation Precautions
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect
all sources of power before servicing Control unit and
associated equipment may be damaged by
removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized Do
not attempt to install, service, or operate this unit until
this manual is read and understood
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72
after any programming operation or change in site-
specific software Reacceptance testing is required
after any change, addition or deletion of system
components, or after any modification, repair or
adjustment to system hardware or wiring All
components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested In addition, to ensure that other
operations are not inadvertently affected, at least 10%
of initiating devices that are not directly affected by
the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F and at a relative
humidity of 93 ±2% RH (non-condensing) at 32 ±2°
C/90 ±3° F However, the useful life of the system's
standby batteries and the electronic components
may be adversely affected by extreme temperature
ranges and humidity Therefore, it is recommended
that this system and all peripherals be installed in an
environment with a nominal room temperature of 0-
50° C/32-120° F

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
16
Verify that wire sizes are adequate for all initiating and Indicating
device loops Most devices cannot tolerate more than a 10% I R drop
from the specified device voltage
Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid-state electronic de ices, this system may operate
erratically or can be damaged when subjected to lightning-induced
transients Although no system is completely immune from lightning
transients and interferences, proper grounding will reduce
susceptibility verhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes. Consult
with the Technical Services Department if any problems are
anticipated or encountered
Disconnect AC power and batteries prior to removing or inserting
circuit boards Failure to do so can damage circuits
Remo e all electronic assemblies prior to any drilling, filing, reaming,
or punching of the enclosure When possible, make all cable entries
from the sides or rear Before making modifications, verify that they will
not interfere with battery, transformer, and printed circuit board
location
Do not tighten screw terminals more than 9 in-lbs
Over-tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal
Though designed to last many years, system components
can fail at any time This system contains static-sensitive
components Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed from the
body Use static-suppressive packaging to protect electronic
assemblies removed from the unit
Follow the instructions in the installation, operating, and programming
manuals These instructions must be followed to avoid damage to the
control panel and associated equipment FACP operation and
reliability depend upon proper installation by authorized personnel

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
17
3.2 Mounting Details
Note: For Higher zones and apart from standard zone the size on
request.
Place the panel in its mounting position and fix the panel to the
wall using the slots of the four screws Ensure the enclosure and the
inner parts of the panel are given sufficient protection during
installation All external cables are to be entered via the
∅19
mm
preformed knockouts located at the top of the panel
When the installation of all the cables has been completed, clean
the interior of the enclosure ensuring all masonry debris and drilling
swords are removed

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
18
3.3 Input Circuits
The control panel has 2 zone input circuits depending on the
variant The maximum loop resistance limit for each input circuit is
50 ohms All field wiring of each zone is supervised for opens and
ground faults Both conditions are visually and audibly (toggle tone)
annunciated
Each zone is a Class B Initiating Device Circuit (IDC – Zones)
designed to accept any normally open contact devices and
conventional 2-wire, 24 volt smoke detectors
It is allowable to mix an assortment of device types (i.e. smoke
detectors, heat detectors, pull stations, etc.) on any zone.
Zone Circuit – Class B

6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1
19
3.4 Output Circuits
Sounder Circuits: The RE – 150D provides Notification Appliance
Circuits standard as Class B The total load capacity of this circuit is
capacity of this O/P may be calculated as no of zones X 0 2Amps
Sounder Circuit – Class B
Note: If the non polarized devices are used, connect the device as
mentioned in page 27.
Standard Relay
The control panel provides three Form-C relays rated for 2 0 amps @
30 VDC and 2 0 amps @ 30 VAC
Relay connections may be power-limited or nonpower-limited,
provided that a minimum of 0 25" is maintained between conductors
of power-limited and nonpower-limited circuits
Table of contents
Other Ravel Control Panel manuals