RDZ 1057230 Instruction Manual

230 V ELECTROTHERMAL HEAD
TESTINA ELETTROTERMICA 230 V
TECHNICAL SHEET
SCHEDA TECNICA
0,5 mm
ab
FIRST-OPEN FUNCTION / FUNZIONE FIRSTOPEN
ADAPTION CHECK / CONTROLLO DELLA POSIZIONE
INSTALLATION - INSTALLAZIONE
The thermo-electric actuator performs the shut-o function on each
circuit with control by the room thermostat. It can be installed in any
position, even upside-down. The function display of the actuator allows
identifying the operating condition (open/closed). Easy slot assembly
thanks to the adapter (supplied as standard). Voltage: 230V with or
without micro-switch or 24V with micro-switch. Protection class: IP54
(all assembly positions). It can be used with b!klimax, TOP COMPOSIT,
CONTROL, High-temperature outlets for KIT and MTR units.
The wide selection of valve adapters guarantees a perfect
match of the actuator to almost any valve bottom or manifold
available on the market. Simply snap-on the actuator to the
manually pre-installed valve adapter. Preferred installation
position of the actuator is vertical or horizontal. An upside
down position may reduce product life through special
circumstances (e.g. contaminated water).
1. First the valve adapter is screwed on the valve manually.
2. The actuator is placed vertically on the valve adapter.
3. The actuator snaps onto the valve adapter with a “click” when pressed
down vertically by hand.
1. Avvitare manualmente l’adattatore sulla valvola.
2. Posizionare verticalmente la testina sull’adattatore.
3. Agganciare la testina sull’adattatore e premere con la mano verso
il basso no a che un“click” indicherà il ssaggio.
Operazione di smontaggioDisassembly operation
L’ampia selezione di adattatori garantisce un perfetto
accoppiamento dell’attuatore con la maggior parte delle
filettature di valvole e collettori disponibili sul mercato.
Agganciare la testina all’adattatore installato in precedenza
manualmente sulla valvola. Collocare preferibilmente
l’attuatore in posizione orizzontale o verticale. L’installazione
in posizione capovolta potrebbe ridurre la durata di vita del
prodotto in particolari circostanze (es. acqua contaminata).
In its delivery condition, the
actuator is kept open when de-
energised due to the First-Open
function. This enables heating
operation during the carcass
construction phase even when
the electric wiring of the individual
room control is not yet complete.
During the laterelectrical start-up, the First-Open function is automatically
unlocked by applying the operating voltage for more than 6 minutes. The
valve drive is now fully operable.
Nella sua impostazione da
fabbrica l’attuatore rimane
aperto quando diseccitato
grazie alla funzione First-Open.
Questo consente il riscaldamento
durante la fase di costruzione
strutturale, anche quando il
cablaggio elettrico del singolo
controllo ambiente non è ancora
stato completato.
Durante il successivo avviamento elettrico, la funzione First-Open si
sblocca automaticamente fornendo la tensione di esercizio per più di 6
minuti. L’azionamento della valvola è ora completamente funzionante .
Testina elettrotermica per comando del singolo circuito tramite
termostato ambiente. Può essere installata anche capovolta.
Visualizzazione dello stato di funzionamento (aperta/chiusa), facilità di
montaggio grazie al sistema di aggancio rapido tramite adattatore
(compreso). Funzionamento: 230V con e senza micro di ne corsa e
24V con micro di ne corsa. Grado di protezione IP54 (in tutte le
posizioni). Utilizzabile con i collettori: b!klimax - TOP COMPOSIT -
CONTROL - Alta Temperatura KIT e MTR.
DESCRIPTION / DESCRIZIONE
Description - Descrizione Type - Tipo Cod.
Electrothermic Head for Underoor Systems
Testina elettrotermica RDZ per sistemi a pavimento e a sotto
230 V 1057230
230 V c/micro 1057240

TECHNICAL SPECIFICATIONS / DATI TECNICI
ELECTRICAL CONNECTION / COLLEGAMENTO ELETTRICO
Brown - MarroneBlue - Blu
Thermostat 230 V
Termostato 230 V
Actuator 230 V
Attuatore 230 V
230 V AC
LN
ELECTROTHERMALHEAD 230 V TESTINA ELETTROTERMICA 230V
Operating voltage: 230 V AC, +10%...–10%, 50/60 Hz
Max. inrush current: < 550 mA during 100 ms max.
Operating power: 1 W *
Stroke (actuator travel): 4.0 mm
Actuating force: 100 N ±5%
Fluid temperature: 0 to +100°C **
Storage temperature: -25°C to +60°C
Ambient temperature: 0 to +60°C
Type of protection: IP 54 *** / II
CE conformity according to: EN 60730
Casing:
material: Polyamide, colour: light grey (RAL 7035)
Connection line:
type: 2 x 0.75 mm² PVC, colour: light gray (RAL 7035), length: 1 m
Weight with connecting cable (1 meter): 100 g
Surge protection according to EN 60730-1: min. 2.5 kV
* measured with precision reference instrument LMG95
** or higher, depending on the adapter length
*** in all installation positions
Tensione di alimentazione: 230 V AC, +10%...–10%, 50/60 Hz
Max. corrente di spunto: < 550 mA in 100 ms max.
Potenza assorbita a regime: 1 W *
Corsa attuatore: 4.0 mm
Forza di azionamento: 100 N ±5%
Temperatura uido: da 0 a +100°C **
Temperatura di stoccaggio: da -25°C a +60°C
Temperatura ambiente: da 0 a +60°C
Grado di protezione: IP 54 *** / II
Conformità CE secondo: EN 60730
Guscio protettivo:
materiale: Poliammide, colore: grigio chiaro (RAL 7035)
Cavo di alimentazione:
tipo: 2 x 0.75 mm² PVC, colore: grigio chiaro (RAL 7035), lunghezza: 1 m
Peso con cavo di alimentazione (1 metro): 100 g
Protezione contro sovratensione secondo EN 60730-1: min. 2.5 kV
* misurazione fatta con strumento di precisione LMG95
** o superiore, in base all’altezza dell’adattatore
*** installata in tutte le posizioni
Cod. 1057230
FUNCTION MODE / MODALITA’ FUNZIONAMENTO
The function display of the actuator
(all-around display) allows identifying
the operating condition (valve open) at
a glance.
Il display della testina (display a tutto
tondo) consente in modo rapido
la visualizzazione dello stato di
funzionamento (valvola aperta).
The actuator mechanism uses a PTC resistor-heated wax element and a
compression spring. The wax element is heated by applying the operating
voltage and moves the integrated ram. The force generated by the
movement is transferred on the valve lifter and thus opens and closes the
valve. The valve is opened steadily by the ram motion upon switching on
the operating voltage and after expiry of the dead time.
After the operating voltage is cutand after expiry ofthe hold time, thevalve
is closed evenly by the closing force of the compression spring.
The closing force of the compression spring is matched to the closing force
of commercially available valves and keeps the valve normally closed.
Il motore di azionamento dell’attuatore impiega una termoresistenza
elettrica di tipo PTC che attiva un elemento di cera contrastato da una
molla di compressione. L’elemento di cera riscaldato dalla tensione di
alimentazione muove il pistone integrato. La forza generata da questo
movimento viene trasferita al pistone che apre o chiude la valvola.
Questa si apre in modo uniforme e permanente con il movimento
del pistone se viene applicata la tensione di esercizio e dopo che è
trascorso il tempo morto. Una volta sospesa la tensione di esercizio e
dopo che è trascorso il tempo di attesa, la valvola viene chiusa in modo
uniforme con la forza della molla di compressione. La forza di chiusura
della molla di compressione corrisponde alla forza esercitata dalle
valvole disponibili in commercio e mantiene la valvola normalmente
chiusa.

TECHNICAL SPECIFICATIONS / DATI TECNICI
ELECTRICAL CONNECTION / COLLEGAMENTO ELETTRICO
Brown - Marrone
Consumers, pump, etc.
Utenze, circolatore, etc.
Max 230 V
5 A resistive load
1 A inductive load
Max 230 V
5 A carico resistivo
1 A carico induttivo
Blue - Blu
Black - Nero (micro)
Grey - Grigio (micro)
230 V Actuator with micro
Attuatore 230 V con micro
230
V AC
LN
Thermostat 230 V
Termostato 230 V
ELECTROTHERMIC HEAD WITH MICRO TESTINA ELETTROTERMICA CON MICRO
Operating voltage: 230 V AC, +10%...–10%, 50/60 Hz
Max. inrush current: < 550 mA during max. 100 ms
Operating power: 1 W *
Stroke (actuator travel): 4.0 mm
Actuating force: 100 N +5 %
Switching current for micro switch: 230 V AC: 5 A resistive load, 1 A
inductive load
Switching point of micro switch NC: approx. 2 mm
Fluid temperature: 0 °C to +100 °C **
Storage temperature: -25 °C to +60 °C
Ambient temperature: 0 °C to +60 °C
Degree of protection: IP 54 ***
Class of protection: II
CE conformity according to: EN 60730
Casing:
material: Polyamide, colour: light grey (RAL 7035)
Connection line:
type: 4 x 0.75 mm² PVC, colour: light gray (RAL 7035), length: 1 m
Weight with connecting cable (1 m): approx. 150 g
Surge protection according to EN 60730-1: 2.5 kV
* measured with precision reference instrument LMG95
** or higher, depending on the adapter length
*** in all installation positions
Tensione di alimentazione: 230 V AC, +10%...–10%, 50/60 Hz
Max. corrente di spunto: < 550 mA in max. 100 ms
Potenza assorbita a regime:1 W *
Corsa attuatore: 4.0 mm
Forza di azionamento: 100 N +5 %
Corrente di commutazione micro di ne corsa: 230 V AC: 5 A carico
resistivo, 1 A carico induttivo
Switching point of micro switch NC: circa 2 mm
Temperatura uido: da 0 °C a +100 °C **
Temperatura di stoccaggio: da -25 °C a +60 °C
Temperatura ambiente: da 0 °C a +60 °C
Grado di protezione: IP 54 ***
Classe di protezione: II
Conformità CE secondo: EN 60730
Guscio protettivo:
materiale: Poliammide, colore: grigio chiaro (RAL 7035)
Cavo di alimentazione:
tipo: 4 x 0.75 mm² PVC, colore: grigio chiaro (RAL 7035), lunghezza: 1 m
Peso con cavo di alimentazione (1 m): circa 150 g
Protezione contro sovratensione secondo EN 60730-1: 2.5 kV
* misurazione fatta con strumento di precisione LMG95
** o superiore, in base all’altezza dell’adattatore
*** installata in tutte le posizioni
Cod. 1057240
FUNCTION MODE / MODALITA’ FUNZIONAMENTO
The function indicator of the actuator
(all around view) allows identifying the
operating condition (valve open) at a
glance. It is also possible to feel the current
operating state when it’s dark.
L’indicatore della testina (vista a tutto
tondo) consente in modo rapido
la visualizzazione dello stato di
funzionamento (valvola aperta) anche
al buio.
The actuator mechanism with end switch uses a PTC resistor-heated wax
element and a compression spring. The wax element is heated by applying
the operating voltage and moves the integrated ram. The force generated
by this movement is transferred on the valve lifter and opens and closes
the valve. The integrated micro switch allows the use of its switching
signal depending on the opening of the valve. The valve is opened steadily
by the ram motion upon switching on the operating voltage and after
expiry of the dead time. The integrated micro switch is switched with a
travel path of approx. 2 mm. After the operating voltage is cut and after
expiry of the hold time the valve is closed evenly by the closing force of
the compression spring. The integrated switch is closed after an actuator
travel of approx. 2 mm.
The closing force of the compression spring is matched to the closing
force of commercially available valves and keeps the valve closed when
de-energised.
Il motore di azionamento dell’attuatore con micro di ne corsa impiega
una termoresistenza elettrica di tipo PTC che attiva un elemento di cera
contrastato da una molla di compressione. La forza generata da questo
movimento viene trasferita al pistone che apre o chiude la valvola.
Il micro di fine corsa incorporato permette l’uso del segnale in
base all’apertura della valvola. Questa si apre in modo uniforme
e permanente con il movimento del pistone se viene applicata la
tensione di esercizio e dopo che è trascorso il tempo morto. Il micro
di ne corsa incorporato viene quindi attivato con una corsa di circa 2
mm. Una volta sospesa la tensione di esercizio e dopo che è trascorso
il tempo di attesa, la valvola viene chiusa in modo uniforme con la
forza della molla di compressione. Il micro di ne corsa incorporato
si chiude dopo che l’attuatore ha percorso un tragitto di circa 2 mm.
La forza di chiusura della molla di compressione corrisponde alla forza
esercitata dalle valvole disponibili in commercio e mantiene la valvola
chiusa quando diseccitata.

In base a quanto previsto dalle seguenti direttive
europee 2011/65/UE, 2012/19/UE e 2003/108/CE,
relative alla riduzione dell’uso di sostanze pericolose
nelle apparecchiature elettriche ed elettroniche,
nonché allo smaltimento dei riuti.
Il simbolo del cassonetto barrato riportato sull’apparecchiatura indica
che il prodotto alla ne della propria vita utile deve essere raccolto
separatamente dagli altri riuti.
Al termine del ciclo di vita dell’unità, in previsione di una sua rimozione,
andranno seguiti una serie di accorgimenti:
La struttura ed i vari componenti, se inutilizzabili, vanno demoliti
e suddivisi a seconda del loro genere merceologico. Tutto ciò per
agevolare i centri di raccolta, smaltimento e riciclaggio e per ridurre
al minimo l’impatto ambientale che tale operazione richiede.
L’adeguata raccolta differenziata per l’avvio successivo
dell’apparecchiatura dismessa al riciclaggio, al trattamento e allo
smaltimento ambientale compatibile contribuisce ad evitare possibili
eetti negativi sull’ambiente e sulla salute e favorisce il riciclo dei
materiali di cui è composta l’apparecchiatura.
Lo smaltimento abusivo del prodotto da parte dell’utente comporta
l’applicazione delle sanzioni previste dalla vigente normativa in
materia.
In accordance with the provisions of the following
European directives 2011/65/EU, 2012/19/EU and
2003/108/EC, regarding reducing the use of hazardous
substances in electrical and electronic equipment, in
addition to waste disposal.
The crossed-out rubbish bin symbol shown on the equipment indicates
that, at the end of its useful life, the product must be collected separately
from other waste.
At the end of the life cycle of the unit, before its removal, the following
precautions must be taken:
The structure and the various components, if they can no longer be used,
must be demolished and divided up according to the type of product.
All this helps collection, disposal and recycling centres reduce the
environmental impact this operation requires.
Appropriate separate waste collection for subsequent sending of
the disused equipment for recycling, treatment and compatible
environmental disposalcontributes to preventing possible negative eects
on the environment and favours recycling of the materials of which the
equipment is composed.
The abusive disposal of the product by the user leads to the application
of the penalties envisaged by current regulations regarding the matter.
ATTENZIONE: L’installazione e la manutenzione vanno
eseguiti solo da personale qualicato.
Gli impianti idraulici, elettrici ed i locali di installazione
delle apparecchiature devono rispondere alle norme di sicurezza,
antinfortunistiche e antincendio in vigore nel Paese di utilizzo.
• Se dopo aver disimballato il componente si nota una qualsiasi
anomalia non utilizzare l’apparecchiatura e rivolgersi ad un Centro
di Assistenza autorizzato dal Costruttore.
• Alla ne dell’installazione smaltire gli imballi secondo quanto previsto
dalle normative in vigore nel Paese di utilizzo.
• Esigere solo ricambi originali: la mancata osservazione di questa
norma fa decadere la garanzia.
• Il Costruttore declina ogni responsabilità e non ritiene valida la
garanzia nei casi seguenti:
- Non vengano rispettate le avvertenze e le norme di sicurezza sopra
indicate, comprese quelle vigenti nei paesi di installazione.
- Mancata osservanza delle indicazioni segnalate nel presente
manuale.
- Danni a persone, animali o cose, derivanti da una errata installazione
e/o uso improprio di prodotti e attrezzature.
- Inesattezze o errori di stampa e trascrizione contenuti nel presente
manuale.
• Il Costruttore, inoltre, si riserva il diritto di cessare la produzione in
qualsiasi momento e di apportare tutte le modiche che riterrà utili
o necessarie senza obbligo di preavviso.
CAUTION: Installation and maintenance must only be carried
out by qualied personnel.
The hydraulic and electrical systems and the places where
the equipment is to be installed must comply with the safety,
accident prevention and re prevention standards in force in the
country of use.
• If, after having unpacked the component, any anomaly is noted, do not
use the equipment and contact an Assistance Centre authorised by the
manufacturer.
• After installation, dispose of the packaging in accordance with the
provisions of the regulations in force in the country of use.
• Use original spare parts only: disregarding this rule invalidates the
warranty.
• The manufacturer declines all responsibility and considers the warranty
invalid in the following cases:
- The aforementioned warnings and safety regulations, including those
in force in the country of installation, are not respected.
- The information given in this manual is disregarded.
- There is damage or injury to people, animals or objects, resulting
from incorrect installation and/or improper use of the products and
equipment..
- Inaccuracies or printing and transcription errors are contained in this
manual.
• The manufacturer also reserves the right to cease production at any time
and to make all the modications which it considers useful or necessary
without any obligation to give notice.
48,4 mm
52,2 mm
44,3 mm
50,3 mm
+ 7 mm
Dimensions - Dimensioni Installation height - Quota in funzionamento
56 mm
Dimensions - Dimensioni Installation height - Quota in funzionamento
44,3 mm
50,7 mm
7 mm
52,6 mm
DIMENSIONS / DIMENSIONI DIMENSIONS / DIMENSIONI
DISPOSAL / SMALTIMENTO
Cod. 1057230 Cod. 1057240
GENERAL WARNINGS / AVVERTENZE GENERALI
rdz.it/qr?r=00000
02/2020FAC0EB020AB.00
This manual suits for next models
1
Other RDZ Controllers manuals
Popular Controllers manuals by other brands

Saswell
Saswell SEA801-Tuya Zigbee instructions

Aqua Environment Inc
Aqua Environment Inc 415-1500 Operation and maintenance

Danfoss
Danfoss AME 110 NL datasheet

NI
NI PXI-8105 installation guide

Airzone
Airzone AZXCSMASTER Installation and user manual

Ricoh
Ricoh Interactive Whiteboard Controller Type 1 Read me first