
REC Indovent AB, Box 37, 431 21 Mölndal | tel.031-675500 |www.rec-indovent.se
OPERATION & CONTROL
Ventilation unit RT 700/1000S-EC-RS
2.16.1. Analog inputs
UI1 Not active ☐Room sensor, ☐Frost protection sensor, ☐TG-R4,
☐Duct heater sensor, ☐Option temp 1,
☐Option temp 2, ☐Option temp 3, ☐Option temp 4,
☐Temp after Exch, ☐SAF Pressure, ☐EAF Pressure,
☐Exch. Pressure, ☐CO2, ☐Humidity
UI2 Not active ☐Room sensor, ☐Frost protection sensor, ☐TG-R4,
☐Duct heater sensor, ☐Option temp 1,
☐Option temp 2, ☐Option temp 3, ☐Option temp 4,
☐Temp after Exch, ☐SAF Pressure, ☐EAF Pressure,
☐Exch. Pressure, ☐CO2, ☐Humidity
UI3 Not active ☐Room sensor, ☐Frost protection sensor, ☐TG-R4,
☐Duct heater sensor, ☐Option temp 1,
☐Option temp 2, ☐Option temp 3, ☐Option temp 4,
☐Temp after Exch, ☐SAF Pressure, ☐EAF Pressure,
☐Exch. Pressure, ☐CO2, ☐Humidity
UI4 Not active ☐Room sensor, ☐Frost protection sensor, ☐TG-R4,
☐Duct heater sensor, ☐Option temp 1,
☐Option temp 2, ☐Option temp 3, ☐Option temp 4,
☐Temp after Exch, ☐SAF Pressure, ☐EAF Pressure,
☐Exch. Pressure, ☐CO2, ☐Humidity
2.16.1.4. CO2 (is displayed if CO2 is selected on any analog input)
0.0 V –>0 ppm __________ V -> __________ ppm
10.0 V –>1200 ppm __________ V -> __________ ppm
2.16.1.5. Humidity (is displayed if Humidity is selected on any analog input)
0.0 V –>0.0 %RH __________ V -> __________ %RH
10.0 V –>100.0 %RH __________ V -> __________ %RH
2.16.2. Digital inputs (*the function must be activated from the factory to be selected)
DI1 AHU On/Off ☐Not active, ☐Min flow, ☐Boost flow, ☐Max flow,
☐Kitchen mode*, ☐ECO*, ☐Stove mode*,
☐Fire input*, ☐Fire damper*, ☐Normal,
☐Filter guard fire, ☐Smoke detector error*,
☐T (connected to timer)
DI2 Not active ☐Min flow, ☐Boost flow, ☐Max flow, ☐Kitchen mode*,
☐ECO*, ☐Stove mode*, ☐Fire input*, ☐Fire damper*,
☐AHU. On/Off, ☐Normal, ☐Filter guard fire,
☐Smoke detector error*, ☐T (connected to timer)
DI3 Not active ☐Min flow, ☐Boost flow, ☐Max flow, ☐Kitchen mode*,
☐ECO*, ☐Stove mode*, ☐Fire input*, ☐Fire damper*,
☐AHU. On/Off, ☐Normal, ☐Filter guard fire,
☐Smoke detector error*, ☐T (connected to timer)
DI6 Not active ☐Min flow, ☐Boost flow, ☐Max flow, ☐Kitchen mode*,
☐ECO*, ☐Stove mode*, ☐Fire input*, ☐Fire damper*,
☐AHU. On/Off, ☐Normal, ☐Filter guard fire,
☐Smoke detector error*, ☐T (connected to timer)
DI7 (is only displayed if a heat
source other than electricity is
selected)
Not active ☐Min flow, ☐Boost flow, ☐Max flow, ☐Kitchen mode*,
☐ECO*, ☐Stove mode*, ☐Fire input*, ☐Fire damper*,
☐AHU. On/Off, ☐Normal, ☐Filter guard fire,
☐Smoke detector error*, ☐T (connected to timer)
DI4 TF omr. ☐SA fan EC
DI5 TF omr. ☐EA fan EC, ☐Not active
Alarm delay SA 30 sec __________ sec
Alarm delay EA 30 sec __________ sec
2.16.2.1. Timer
Time 0 hour, ☒0 min ________ h (0 –24 h), ________ min (0 –59 min)
Edge Hi ☐Low
2.16.2.1.1.Stove timer (is displayed if "Stove mode" is configured on any digital output)
Ignite time 15 min __________ min (0 –30 min)
After time 12 hours __________ h (0 –24 h)
2.16.3. Digital outputs (*the function must be activated from the factory to be selected)
DO3 (only displayed if heater
"water 0-10V" or "no heater" is
selected)
Not active ☐KAVK, ☐ULS, ☐Sum alarms, ☐CP heater,
☐CP chiller, ☐Normal flow, ☐Fire damper, ☐Stove,