manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. red lion
  6. •
  7. Cash Counter
  8. •
  9. red lion CUB7W Series Instruction Manual

red lion CUB7W Series Instruction Manual

1
!COUNT INPUT FROM 10 to 300 VAC/DC
!LCD, POSITIVE IMAGE REFLECTIVE OR NEGATIVE IMAGE
TRANSMISSIVE WITH YELLOW/GREEN OR RED LED
BACKLIGHTING (9 to 28 VDC power supply required for versions
with LED backlighting)
!0.35" (8.90 mm) HIGH DIGITS
!REPLACEABLE INTERNAL LITHIUM BATTERY PROVIDES UP TO
7 YEARS OF UNINTERRUPTED OPERATION
!NEMA 4X/IP65 SEALED FRONT BEZEL
!FRONT PANEL RESET OR REMOTE RESET
!WIRE CONNECTION MADE VIA SCREW CLAMP TYPE
TERMINALS
!FITS DIN STANDARD CUT-OUT 1.77" (45 mm) x 0.874" (22.2 mm)
DESCRIPTION
The CUB7W is an 8-digit miniature counter with large 0.35 inch (8.90 mm)
high digits. It has an LCD read-out available in Positive Image Reflective
(CUB7W000), Negative Image Transmissive with yellow/green backlighting
(CUB7W010) or red backlighting (CUB7W020). The backlight versions
require an external 9 to 28 VDC power supply.
The CUB7W accepts most machine control voltage signals. The input
accepts AC (50/60 Hz) or DC control voltages from 10 to 300 V at count speeds
up to 30 counts per second (cps).
The CUB7W counters use a CMOS LSI counter circuit chip, mounted on a
gold-plated substrate, that is electrically connected by ultrasonic wire-bonding.
Proven micro-electronic assembly and manufacturing techniques provide these
units with the reliability and dependability required for industrial service.
The CUB7W series is housed in a lightweight, high impact plastic case with
a clear viewing window. The sealed front panel with the silicone rubber reset
button meets NEMA 4X/IP65 specifications for wash-down and/or dusty
environments, when properly installed.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. DISPLAY: 8-digit LCD, 0.35" (8.90 mm) high digits.
2. POWER SOURCE: Replaceable Internal 3.0 V lithium battery to provide
up to 7 years of continuous operation. (Battery life is dependent upon usage.
Reset contacts that remain closed for long periods of time reduce battery life.)
3. BACKLIGHT POWER REQUIREMENTS: 9 to 28 VDC; 35 mA. typical,
50 mA max. Above 26 VDC, derate max. operating temperature to 40°C.
4. L. S. INPUT: 10 to 300 VAC/DC, 50/60 Hz, 30 cps max. 150 V max. for
backlight versions. VIL = 0.5 VDC max. Unit counts on the positive going
edge.
Note: For triac inputs, use the standard CUB7 with a TCM module.
5. REMOTE RESET: 15 msec min. pulse width (active low) from 3.0 V
bipolar output, an open collector transistor, or a switch contact to common.
VIH = 2.0 V min. (3 V max), VIL = 0.5 V max.
6. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C. Derate max. operating
temperature to 40°C above 26 VDC (Backlight versions).
Storage Temperature: -30 to 80°C
Operating and Storage Humidity: 85% max.relative humidity (non-
condensing) from 0°C to 50°C.
Altitude: Up to 2000 meters
MODEL CUB7W - MINIATURE ELECTRONIC 8 DIGIT COUNTER w/VOLTAGE INPUT
DIMENSIONS In inches (mm) Note: Recommended minimum clearance (behind the panel) for mounting
clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Bulletin No. CUB7W-G
Drawing No. LP0384
Released 10/01
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com
PANEL CUT-OUT
2
L. S. INPUT, 30 CPS MAX.
The CUB7W accepts most machine control voltage signals. The input
accepts AC (50/60 Hz) or DC control voltages from 10 to 300 V at count
speeds up to 30 cps. The unit counts on the positive going edge of the input
signal.
WARNING: Any lead may be at hazardous live input potential.
External wiring and devices connected to the unit must be rated
the same as applied signal input voltage and be properly
isolated from Class 2 or SELV circuitry.
RESET OPTIONS
Connecting a wire from the RST. EN. (Reset Enable) Input terminal to
Common will enable the front panel Reset button.
Pulling the “RST.” input low causes the counter to reset. The “RST.” can
be pulled low by either a mechanical switch or solid-state transistor switch.
The Switch load is 15 µA (max. voltage drop 0.5 V) when ON. The OFF-state
leakage current must be less than 2 µA.
Note: The RC protection circuit on the “RST.” Input causes a delay of
approximately 15 msec in Reset response.
SPECIFICATIONS (Cont’d)
7. CERTIFICATIONS AND COMPLIANCES:
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
1. No loss of performance during EMI disturbance at 8 Vrms.
Permissible loss of performance during EMI disturbance at 10 Vrms:
Segments may turn on and off.
For operation without loss of performance:
Install power line filter, RLC#LFIL0000 or equivalent.
Refer to EMC Installation Guidelines section of this bulletin for additional
information.
8. CONSTRUCTION: High impact plastic case with clear viewing window.
The front panel meets NEMA 4X/IP65 requirements for indoor use when
properly installed. Installation Category I, Pollution Degree 2. Panel gasket
and mounting clip included.
9. WEIGHT: 2 oz. (57 grams) [with battery]
ENVELOPE PACKAGING APPLICATION
A customer has 18 envelope packaging machines to be upgraded. These
machines have existing preset counters for batching purposes. The customer
now wants to add totalizing capabilities. The CUB7W000’s low cost, battery
power operation, and 10 to 300 VAC/VDC input capabilities are perfect for
the upgrade. The existing photo-electric sensor’s 24 VDC signal, for the batch
counter, is paralleled to the CUB7W. Battery power is an advantage due to
the fact that no additional power supply lines are required. At the end of each
shift, the count is reset by a key switch RLC PT# (PKS10000) connected to
the Remote Reset input (5-RST).
BACKLIGHT OPTION
Optional backlight versions of the CUB7W require an external 9 to 26
VDC power supply. The external supply is connected between the V+ and
common terminals as shown in the drawing.
WARNING: When connecting the wiring for a backlit CUB7W
measuring an AC input voltage, the neutral of the single phase
AC signal is connected to Terminal 1 (COM), and line (hot) is
connected to Terminal 4 (LS). The DC supply for the
backlighting is connected as shown in the drawing. Three phase
AC applications require an isolation transformer.
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms 1
150 KHz - 80 MHz
Simulation of cordless telephone ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
200 Hz, 50% duty cycle
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
3
LAUNDRY FACILITIES APPLICATION A family owned coin operated laundry installed a CUB7W000 (Positive
Image Reflective) on each of the 25 industrial washing machines in one of
their laundry facilities. The CUB7W000 was wired into the washing
machine’s 230 VAC power relay and increments one count each time the
machine begins a washing cycle. The count is recorded and reset at the end
of each month. Reset is accomplished with an external key switch. The
count value is used to compare the number of
times the machine was used against the money
collected for that machine. In addition, the usage
data collected is invaluable in determining the
location of the high traffic areas because of tables
or door locations. Rotating the machines within
the facility maximized the mechanical life of all
machines.
BATTERY INSTALLATION
1. Remove all power to the unit before removing battery cover.
2. To remove the battery cover, push upward in the direction of the arrow on
the rear cover (See drawing at right), until the cover unlatches. Pull the
cover straight out from unit to fully remove.
3. Remove old battery* and replace it with an RLC battery (BNL10000).
Observe proper polarity when replacing the battery as shown in the
drawing.
4. Replace the cover. The battery cover is keyed so that it cannot be placed
upside down. The arrow on the rear of the cover should point toward the
top of the CUB7W when properly installed.
* - Dispose of properly.
WARNING: Lithium battery may explode if incinerated.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging process of
the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate
the keypad of the unit.
Installation
The CUB7W meets NEMA 4X/IP65 requirements, for indoor use when
properly installed. The units are intended to be mounted into an enclosed
panel. The viewing window and reset button are factory sealed for a
washdown environment. A sponge rubber gasket and mounting clip are
provided for installing the unit in the panel cut-out.
The following procedure assures proper installation:
1. Cut panel opening to specified dimensions. Remove burrs and clean around
panel opening.
2. Carefully remove and discard the center section of the gasket.
3. Slide the panel gasket over the rear of the counter body to the back of the
bezel. Install CUB7W unit through the panel cut-out.
4. Insert the mounting screws onto both sides of mounting clip. Tip of screw
should NOT project from hole in mounting clip.
5. Slide the mounting clip over the rear of the unit until the clip is against the
back of the panel. The mounting clip has latching features which engage
into mating features on the CUB7W housing.
Note: It is necessary to hold the unit in place when sliding mounting clip
into position.
6. Alternately tighten each screw to ensure uniform gasket pressure.
Visually inspect the front panel gasket. The gasket should be compressed to
about 75 to 80% of its original thickness. If not, gradually turn mounting
screws to further compress gasket.
7. If the gasket is not adequately compressed and the mounting screws can no
longer be turned, loosen mounting screws, and check that the mounting clip
is latched as close as possible to the panel.
8. Repeat from step #5 for tightening mounting screws.
ORDERING INFORMATION
WIRING CONNECTIONS
The electrical connections are made via screw-clamp terminals located
on the back of the unit. All conductors should meet voltage and current
ratings for each terminal. Also cabling should conform to appropriate
standards of good installation, local codes and regulations. It is
recommended that power supplied to the unit be protected by a fuse or
circuit breaker. When wiring the unit, use the battery cover to identify the
wire position with the proper function. Strip the wire, leaving
approximately 1/4" bare wire exposed (stranded wires should be tinned with
solder). Insert the wire under the screw-clamp and tighten down the screw
until the wire is clamped in tightly. Each terminal can accept up to two #14
AWG wires.
Warning: Lithium battery may explode if incinerated.
Caution: All leads will be at the same line potential as the input leads.
TROUBLESHOOTING
For further technical assistance, contact technical support at the appropriate
company numbers listed.
EMC INSTALLATION GUIDELINES
Although this unit is designed with a high degree of immunity to
ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. In extremely high EMI environments, additional
measures may be needed. The unit becomes more immune to EMI with fewer
I/O connections. Cable length, routing and shield termination are very
important and can mean the difference between a successful or a troublesome
installation. Listed below are some EMC guidelines for successful installation
in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
3. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
4. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through
the core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to one year from the
date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability
under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company
disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising
out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths,
property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including
without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to
the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The
Customer acknowledges the disclaimers and limitations contained hererin and relies on no other warranties or affirmations.
BNL100003 V Lithium BatteryBNL
CUB7W020Counter w/Red Backlighting
CUB7W010Counter w/Yel-Grn Backlighting
CUB7W000Counter Positive Image Reflective
* CUB7W
PART NUMBERSDESCRIPTIONMODEL NO.
For more information on Pricing, Enclosures & Panel Mount Kits
refer to the RLC Catalog or contact your local RLC distributor.
Red Lion Controls
20 Willow Springs Circle
York PA 17402
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion UK Ltd
Tapton Park
Chesterfield S41 OTZ
Tel +44 (1246) 22 21 22
Fax +44 (1246) 22 12 22
Red Lion Controls France
56 Boulevard du Courcerin, Batiment 21,
ZI Pariest F-77183 Croissy Beaubourg
Tel +33 (64) 80 12 12
Fax +33 (64) 80 12 13
* Battery is included with unit.

This manual suits for next models

4

Other red lion Cash Counter manuals

red lion CUB5 Series User manual

red lion

red lion CUB5 Series User manual

red lion CUB2L8 User manual

red lion

red lion CUB2L8 User manual

red lion CUB2L User manual

red lion

red lion CUB2L User manual

red lion CUB3L User manual

red lion

red lion CUB3L User manual

red lion CUB2L User manual

red lion

red lion CUB2L User manual

red lion CUB5-J User manual

red lion

red lion CUB5-J User manual

red lion GEMINI 1000 User manual

red lion

red lion GEMINI 1000 User manual

red lion CUB4L Instruction manual

red lion

red lion CUB4L Instruction manual

red lion CUB4L User manual

red lion

red lion CUB4L User manual

red lion PAX Lite PAXLCR User manual

red lion

red lion PAX Lite PAXLCR User manual

red lion CUB7W3 User manual

red lion

red lion CUB7W3 User manual

red lion CUB7P100 User manual

red lion

red lion CUB7P100 User manual

red lion LNXC1 User manual

red lion

red lion LNXC1 User manual

red lion CUB7P User manual

red lion

red lion CUB7P User manual

red lion CUB7P3 User manual

red lion

red lion CUB7P3 User manual

red lion LIBC Series User manual

red lion

red lion LIBC Series User manual

red lion CUBC Series Service manual

red lion

red lion CUBC Series Service manual

red lion CUB70 User manual

red lion

red lion CUB70 User manual

red lion CUB 1 User manual

red lion

red lion CUB 1 User manual

red lion CUB2L800 User manual

red lion

red lion CUB2L800 User manual

red lion C48C User manual

red lion

red lion C48C User manual

red lion PAXLC User manual

red lion

red lion PAXLC User manual

red lion CUB7 Series Instruction Manual

red lion

red lion CUB7 Series Instruction Manual

red lion CUB 3 User manual

red lion

red lion CUB 3 User manual

Popular Cash Counter manuals by other brands

Omron H7E-P Series quick start guide

Omron

Omron H7E-P Series quick start guide

LoRa Alliance YO Pulse Quick installation guide

LoRa Alliance

LoRa Alliance YO Pulse Quick installation guide

RAPA L-BK user manual

RAPA

RAPA L-BK user manual

Contec N Series Reference manual

Contec

Contec N Series Reference manual

MPFiltri LPA2 Operator's guide

MPFiltri

MPFiltri LPA2 Operator's guide

Glas Craft Probler P2 user manual

Glas Craft

Glas Craft Probler P2 user manual

BLACK STAR APOLLO Series Service manual

BLACK STAR

BLACK STAR APOLLO Series Service manual

Cassida Cube user manual

Cassida

Cassida Cube user manual

Royal Sovereign RBC-100N owner's manual

Royal Sovereign

Royal Sovereign RBC-100N owner's manual

Trumeter 7010 manual

Trumeter

Trumeter 7010 manual

Mitutoyo EH Series USER'S MANUAL / INSTRUCTIONS FOR USE

Mitutoyo

Mitutoyo EH Series USER'S MANUAL / INSTRUCTIONS FOR USE

Eaton Durant Courier 5330 403 Series Installation and operation

Eaton

Eaton Durant Courier 5330 403 Series Installation and operation

microSYST MS8202 user manual

microSYST

microSYST MS8202 user manual

Hengstler tico 731.4 operating instructions

Hengstler

Hengstler tico 731.4 operating instructions

Philips PM 6650 operating manual

Philips

Philips PM 6650 operating manual

Omron H7CX-R11D1 manual

Omron

Omron H7CX-R11D1 manual

Polar Electro U Series instruction manual

Polar Electro

Polar Electro U Series instruction manual

Olympia NC-350A Series user guide

Olympia

Olympia NC-350A Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.