Application Note
This product is designed to replace induction motors (shaded pole or
PSC) in direct-drive fan propeller applications. Do not use this motor
to replace OEM ECM outdoor fan motors or belt drive motors. OEM
ECM outdoor fan motors must be replaced with OEM equivalent.
Operation Note
Evergreen OM will delay on approximately 5 seconds after 24vac or PWM
is applied to one of the speed wires, then ramp up to speed. The Orange
and Yellow speed/PWM wires dictate the on/off command to the motor
control.
Replacing the Evergreen OM
If the motor does not operate with proper Line Voltage measured
between the Red wire and the Black wire, AND proper 24vac or PWM to
a signal wire and common (see wiring diagram), it is failed and will require
replacement. Before replacing the motor, please call the Contractor
Hotline to confirm your diagnostics if possible. The Evergreen OM is
a single component replacement.The control cannot be replaced
separately from the motor. Contact the distributor where the motor was
purchased or any authorized Evergreen distributor for replacement.
Contractor Hotline 1-866-503-8566
STOCK
NO. HP VOLTAGE FLA ROTATION RPM FRAME
6903 1/3 460 1. 6 CCW/CW 850/1100 NEMA 48
6905 1/2 460 2.5 CCW/CW 850/1100 NEMA 48
6907 3/4 460 3.1 CCW/CW 850/1100 NEMA 48
Specifications
Voltage: 460 (allowable voltage range 414-552) VAC, single-phase input,
50-60 Hz
Horse Power: 1/3HP (replaces 1/3-1/4), 1/2HP (replaces 1/2-1/4), 3/4HP
(replaces 3/4-1/4)
Speeds: 2 operating speeds using 24vac or 300-1200 RPM using PWM
(Constant Speed)
• 1100 RPM (6-pole) replaces motors rated 1000-1100 RPM,
850 RPM (8-pole) replaces motors rated 800-850 RPM
• 300-1200 RPM operating range with PWM input (PWM Signal
specifications 15-23 VDC at 67-93Hz or 127-199Hz / 10% Guaranteed
On and 5% Guaranteed Off Duty Cycle)
Rotation: CCW or CW by reversing plug (factory set to CCW)
• As viewed from lead end
Bearing: Permanently lubricated ball bearing
Ambient Rating: -40° C to +60° C (-40° F to 140° F)
Enclosure: Totally Enclosed Air Over (TEAO), NEMA 48-frame
Shaft: Single, ½” diameter, 6” length, 5.5” single flat
Mounting: Horizontal or vertical shaft-down (VSD), belly band or rear
extended clamp bolts
Leads: 54” length, bare wire strip, ground wire #10 eyelet
UL and CSA recognized component
Safety Considerations
The following definitions are used as safety considerations on the
Evergreen OM motor and in this manual. Please read and observe all of
these safety concerns.
Safety Symbols
WARNING! Warning indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Caution indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
Installation and service of this motor should be performed only by
trained service technicians familiar with the Evergreen OM motor.
This motor should be installed in accordance with accepted practices
and installation instructions, and in compliance with all national and
local codes.
WARNING! Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock, or other
conditions which may cause personal injury, death, or property damage.
Consult a qualified installer, service agency, or your distributor or branch
for information or assistance. The qualified installer or agency must use
the supplied or recommended parts when installing or servicing this
product.
WARNING! Always disconnect the main power from the unit being
serviced before making any wiring connections to the Evergreen OM. It
is also a good practice to confirm that the power is off with an electric
voltmeter.
Terms & Conditions of Sale & Limited Warranty
Sales of the products described in this Installation Manual are subject to
the “Regal Beloit Terms and Conditions of Sale”current at the time of sale.
They are accessible on RegalBeloit.com – http://www.regalbeloit.com/
what-we-do/products-brands/ (click “Regal Terms and Conditions of Sale”).
The full Limited Warranty, including the scope and period, remedies,
exclusions and disclaimers current is described in Section 10 “Limited
Warranty” of the Regal Terms and Conditions of Sale.
The following is the “Scope and Period” (Section 10(a)(1)) portion of the
Limited Warranty applicable to the products described in this Installation
Manual:
Seller warrants that the Products shall be delivered free from defects
in material, workmanship and title and shall conform to Seller’s written
specification agreed upon by Buyer and Seller in written and signed
agreement, if applicable, for the Products. This warranty shall expire
twenty-four (24) months from the fist use of the Product or thirty (30)
months from date of shipment of the Product, whichever occurs first.
Regal and Genteq are trademarks of Regal Beloit Corporation or one of its affiliated companies.
©2016 Regal Beloit Corporation, All Rights Reserved. MCIM16020E • Form G1150E • SFM-2525 • Printed in USA