4 | City Series CV50E Direct Vent Gas Fireplace
Clearances
Note: The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney-related res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this replace and vent system be installed only in accordance with these instructions.
Flue Clearances to Combustibles
Horizontal - Top 3" (76 mm)
Horizontal - Side 2" (51 mm)
Horizontal - Bottom 2" (51 mm)
Vertical 2" (51 mm)
Passing through wall/
floor/ceiling - when
restop is used.
1-1/2" (38 mm)
Note: This appliance uses 5" x 8" (127 mm x 203
mm) venting for the Non Power Vent.
28 | City Series CV60E
installation
Clearances CV60E
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Clearance: single sided Dimension Measured From:
A1: :Mantel Height (min.) ** Top of Fireplace Opening
A: From Floor 10 1/4” (260 mm)" Bottom of Fireplace Opening
B: Sidewall (on one side) 8" (203mm) Side of Fireplace Opening
C: Enclosure width 65 11/16" (1668mm) Side of Fireplace Opening
D: Mantel Depth (max.) **
E: Alcove Width 109.5” (2781mm) Sidewall to Sidewall (Minimum)
F: Alcove Depth 35" (889mm) Front to Unit (Maximum)
H: Convection Air Outlet *180 square inches
G: Convection Air Outlet Opening Oset *0-2" (0-51mm)
K: Minimum clearance to celing 1 3/4” (44 mm)
M:Clearance to Sprinkler Head (Min.) 36" (914mm) Perpendicular
From back wall to chase front
from chase grill
Hearth 0" hearth required
** See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top 3"
Horizontal - Side 2"
Horizontal - Bottom 2"
Vertical 2"
Passing through wall/
floor/ceiling - when 1-1/2"
Note: This appliance uses 5" x 8" venting.
Alcove
F
D
A1
B
A
J
G
H
L
*A minimum of 180 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations
Side view
M
Chase grill
J: Opening Height 18" (457 mm) Bottom/Top of Fireplace Opening
Top of chase to ceiling
20-5/16" (516mm)I: Framing depth
From base of unit to ceiling81 1/4" (2038 mm)L: Ceiling height
E
Alcove
Clearance Dimension Measured From:
A1: Mantel Height (min.) ** Top of Fireplace Opening
A: From Floor (min.) 10-3/16" (462 mm) Bottom of replace opening
B: Sidewall (on one side) min. 5" (127 mm) Side of replace opening
B1: Sidewall (on one side) min. 24" (610 mm) Side air outlet to side wall (min.)
C: Enclosure Width (min.) 54-3/8" (1381 mm) Side of replace opening
D: Mantel Depth (max.) **
E: Alcove Width 92" (2337 mm) Sidewall to sidewall (minimum)
F: Alcove Depth 35" (889 mm) Front to unit (maximum)
G: Convection Air Outlet Opening Oset
(min.)
H: Convection Air Outlet
*0-2" (0-51 mm)
*152 in2(981 cm2)
Max. oset from top of chase enclosure
I: Framing Depth (min.) 20-7/16" (519 mm) From back wall to chase front
J: Opening Height 18" (457 mm) Bottom/top of replace opening
K: minimum clearance to ceiling 1-3/4" (44 mm) Top of chase to ceiling
L: Chase Enclosure (min.) 62-7/8" (1597 mm) From base of unit/oor to top of enclosure
M:Clearance to Sprinkler Head (min.) 36" (914mm) Perpendicular from chase grill
Ceiling Height 81-1/4" (2064 mm) From base of unit/oor to top of alcove
Hearth 0" No hearth required
** See mantel clearances chart in the manual.
28 | City Series CV60E
installation
Clearances CV60E
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Clearance: single sided Dimension Measured From:
A1: :Mantel Height (min.) ** Top of Fireplace Opening
A: From Floor 10 1/4” (260 mm)" Bottom of Fireplace Opening
B: Sidewall (on one side) 8" (203mm) Side of Fireplace Opening
C: Enclosure width 65 11/16" (1668mm) Side of Fireplace Opening
D: Mantel Depth (max.) **
E: Alcove Width 109.5” (2781mm) Sidewall to Sidewall (Minimum)
F: Alcove Depth 35" (889mm) Front to Unit (Maximum)
H: Convection Air Outlet *180 square inches
G: Convection Air Outlet Opening Oset *0-2" (0-51mm)
K: Minimum clearance to celing 1 3/4” (44 mm)
M:Clearance to Sprinkler Head (Min.) 36" (914mm) Perpendicular
From back wall to chase front
from chase grill
Hearth 0" hearth required
** See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top 3"
Horizontal - Side 2"
Horizontal - Bottom 2"
Vertical 2"
Passing through wall/
floor/ceiling - when 1-1/2"
Note: This appliance uses 5" x 8" venting.
Alcove
E
F
D
A1
B
A
J
G
H
L
*A minimum of 180 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations
Side view
M
Chase grill
J: Opening Height 18" (457 mm) Bottom/Top of Fireplace Opening
Top of chase to ceiling
20-5/16" (516mm)I: Framing depth
From base of unit to ceiling81 1/4" (2038 mm)L: Ceiling height
*A minimum of 152 square
inches of open area, not
lower than 0-2" from top
of enclosure, required for
all installations.
L
Chase grill
Sprinkler
Side view
M
Caution Requirements
The top, back and sides of the replace are
dened by standos. The metal ends of
the stando may NOT be recessed into
combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to
combustible materials are not adhered
to. It is of greatest importance that this
replace and vent system be installed only
in accordance with these instructions.
When installed as a power vent, the venting
must be reduced to 4" inner x 6-5/8" outer
(102 mm x 168 mm) in all applications. See
required reducers required in this manual if
using rigid/ex pipe.