Regulus RGMAT E G60 User manual

www.regulus.eu
RGMAT E G60
RGMAT E G60
EN
Installation and Operation Manual
RegulusRGMAT E G60 LOAD UNIT with UPM 3, insulated
for heating systems

1. Introduction
RegulusRGMAT E G60 Load Unit makes boiler installation quicker as it contains all important
components needed for boiler circuit circulation and boiler protection against low-temperature corrosion.
It is designed to be installed directly on a boiler return piping. The min. distance of the pipe axis from a
wall is 100 mm to enable insulation removal if needed.
This Load Unit is intended for hydronic fireplaces and solid-fuel boilers.
2. RGMAT E G60 Description
RGMAT E G60 keeps the temperature at the boiler inlet above the flue gas condensation temperatures,
which prevents so called low-temperature corrosion of the boiler combustion chamber. This limits con-
densation and boiler tarring significantly, the efficiency of fuel combustion increases and service life of
the boiler is extended.
Main Features
Function maintaining a minimum inlet temperature into a boiler (fireplace) through a load
valve
Application Load Unit for solid-fuel boilers and fireplaces; it prevents low-temperature
corrosion and boiler (fire) fouling
Description consists of a UPM3 FLEX AS pump, ball valves with union nuts, TSV3B valve
(with automatic bypass balancing), thermometer, insulation
Working fluid water; water/glycol mixture (max. 1:1) or water/glycerine mix-ture (max. 2:1)
Installation on boiler return piping, min. distance of the pipe axis from a wall is 100 mm
RGMAT E G60 Technical Data
Fluid working temperature 5 - 95 °C
Max. working pressure 6 bar
Min. working pressure 0.5 bar
Max. ambient temperature 5 - 40 °C
Max. relative humidity 80 %, non condensing
Load valve control range tvalve,opening +5 °C
Valve Kvs (A→AB direction) 6.2 m3/h
Valve Kvs (B→AB direction) 4.4 m3/h
Power supply 230 V, 50 Hz
Insulation material EPP RG 60 g/l
Overall dimensions 325 x 140 x 220 mm
Total weight 3.25 kg
Connections 3x G 1" F
Accessories
Bypass with float non-return valve code 16126
Codes max. boiler output
19083 for opening temperature 45 °C max. 46 kW
19090 for opening temperature 50 °C max. 42 kW
19086 for opening temperature 55 °C max. 36 kW
19092 for opening temperature 60 °C max. 32 kW
19089 for opening temperature 65 °C max. 26 kW
19091 for opening temperature 70 °C max. 22 kW

3. RGMAT E G60 Connection Diagram
Install the Load Unit respecting the following instructions:
Connect the boiler inlet piping to the Load Unit outlet marked AB. Connect the return line from the
heating system to the Ainlet, and the outlet pipe from the boiler to the Binlet via a T-piece. Take care
to install shut-off valves and filter where necessary to avoid draining the whole system for valve
cleaning or replacing the thermostatic element.
When the connecting pipes are not arranged or sloped properly, the load valve may get blocked by
air inside. This may hinder or even disable its operation.
Always respect valid rules and boiler manufacturer’s data during installation.
Possible Connection Example I.
The diagram shows a typical connection of a solid-fuel boiler, thermal store and a heating circuit (with
a recommended CSE MIX W pump station - not included in supply). If the boiler is also used for DHW
heating, it is recommended to install also CSE OTS ZV W pump station (not included in supply).
Possible Connection Example II.
The diagram shows a typical connection of a solid-fuel boiler, combination thermal store (permitting
DHW heating) and a heating circuit (with a recommended CSE MIX W pump station - not included in
supply).
RGMAT E G60
RGMAT E G60
Hot water storage tank
Thermal store
Combination thermal store

4. Function description of a TSV3B valve
TSV3B TSV5B 6/4Mx5/4F load valve is fitted with an
integrated thermostatic insert that will close the Ainlet
(from a heating system), if the return water temperature
to the boiler (AB outlet) is lower than the opening one. As
soon as the opening temperature is reached, the
thermostat starts opening the Ainlet slowly and mixing
the cold return water with the hot water from the boiler
flow (Binlet) with the aim to reach the opening temperature
in the return pipe (AB outlet).
At the same time, the valve closes the Binlet, limiting so
the hot water flow coming from the bypass till its complete
tight closure. Thanks to this, no balancing valve is needed.
The load valve is made of brass, element and plug seals
are in EPDM, cone seal is made of NBR.
Technical Data
Valve opening temperature depending on the thermostatic element
Control range tvalve,opening + 5 °C
Connections 2x G 1" F, 1x G 6/4“ union nut
Nominal inner diameter DN 25
Materials
Housing, cone and plug brass
Spring stainless steel
Element and plug seal EPDM
Cone seal NBR
Valve Pressure Drop Graph
The valve pressure drop value
moves between the two
curves depending on the
mixing ratio during mixing.
0,0
0,5
1,0
1,5
2,0
2,5
0,0 0,5 1,0 1,5 2,0
Δp [m H2O]
Q [m3/h]
▬AAB, Kvs = 6,2 m
3
/h ▬BAB, Kvs = 4,4 m
3
/h
B
AB A

5. UPM3 FLEX AS 25-60 180 Pump
Design
Wet-running circulation pump with G 6/4” M connection.
Electrical Data
Power supply 230 V, 50 Hz
Power consumption (min./max.) 2/42 W
Current (min./max) 0.04/0.40 A
IP rating IP44
Max. speed 5288 rpm
Weighted average power ≤ 20 W
Energy Efficiency Index ≤ 0,20 by EN 16 297/3
Motor protection not needed
Pump control
The circulation pump can be controlled by an external PWM signal
(prole for use in heating systems) or without a PWM signal by
selecting a pump performance curve.
A maximum curve of a pump working range can be dened.
- with PWM signal the pump speed changes with the signal value up to the maximum of the
selected curve
- without PWM signal the pump runs at the max. speed according to the selected curve
Performance Curves
Curve Max. H Max. P1
(upper
graph)
(lower
graph)
14 m 25 W
25 m 34 W
36 m 42 W

Performance display
DISPLAY - LED MARKING
DISPLAY PERFORMANCE CURVE STATE Max. H (upper graph)
1LOW PERFORMANCE 4 m
2MEDIUM PERFORMANCE 5 m
3HIGH PERFORMANCE 6 m
WARNING: LEDs may be mirrored, depending on the specic pump type.
GREEN LED FLASHING FREQUENCY PWM SIGNAL RECEPTION
1 flash per second NO
12 flashes per second YES
When switched on, the pump runs at factory settings or the last setting. The display shows the current
pump performance.
Setting selection for UPM3
To select your desired setting, press the button repeatedly until you nd the setting you need (see the
gure above). If you pass the desired setting, you have to go one more round until it appears again.
Error Display
DISPLAY CONTROL MODE
Seized pump
Too low power supply voltage
Electric fault
The LED marking is further omitted for better clarity.
Prohibited positions
Permissible and prohibited pump positions

Pump wiring
socket for power supply (A)
and signal transmission (B)
power supply (A)
and signal (B) connectors
N (brown)
L (brown)
PE (yellow-green)
PWM GDN (blue)
PWM out (black)
PWM in (brown)
Permissible positions

SMĚR PROUDĚNÍ
SMĚR PROUDĚNÍ
SMĚR PROUDĚNÍ
6. Installation options
This Load Unit comes in the version for horizontal installation to the right of a boiler. However, it can be
installed also into vertical piping or horizontally to the left of a boiler. When being installed horizontally
to the left of a boiler, the Load Unit needs to be turned by 180° and the TSV3B valve turned as shown
in the pics below.
©2022 We reserve the right to errors, changes and improvements without prior notice.
REGULUS spol. s r.o.
E-mail: [email protected]
Web: www.regulus.eu
v1.0-04/2022
FLOW DIRECTION
FLOW DIRECTION
FLOW DIRECTION
Table of contents
Other Regulus Industrial Equipment manuals

Regulus
Regulus PS 200 N+ User manual

Regulus
Regulus BIO 55 MIX-BP G75 1F User manual

Regulus
Regulus HSK 350 K P-B User manual

Regulus
Regulus RGMAT E W-iPWM User manual

Regulus
Regulus PS 400 K+ User manual

Regulus
Regulus PS2F 300 N+ User manual

Regulus
Regulus PS 500 E+ User manual

Regulus
Regulus PSWF 300 N+ User manual

Regulus
Regulus HSK PV Owner's manual