
S8910U UNIVERSAL HOT SURFACE IGNITION MODULE
69-0845—03 14
Safety Shutdown
One Trial Selection Tabs (A and C)
If flame is not sensed by the end of the timed trial for
ignition, the gas control closes and the module locks out.
It must be manually reset by removing power or setting
the thermostat below the room temperature for at least
30 seconds.
If the burner lights and flame is proved but goes out
during the run cycle, the gas control closes and the
module initiates a warmup period followed by one trial
for ignition. If flame is not established, the gas control
closes and the module locks out, requiring manual reset.
Three Trial Selection Tabs (B and D)
If flame is not sensed by the end of the first timed trial for
ignition, the gas control closes and the module initiates a
second 96 seconds between trial purge cycle, followed by
igniter warmup and a second trial for ignition. If flame is
not established, the between trial purge, warmup, trial for
ignition cycle is repeated a third time. If flame is still not
established following the third trial, the gas control
closes and the module locks out. It must be manually
reset by removing power or setting the thermostat below
the room temperature for at least 30 seconds.
If the burner goes out during the run cycle, the gas
control closes and the module checks for the number of
ignition trials performed during the current call for heat. If
the number is less than three, the module initiates a
between trial purge, warmup and trial for ignition. After
the third trial during a single call for heat, the module
locks out. The module must be manually reset following
the lockout.
MAINTENANCE
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
Do not attempt to take apart the module or to
clean it. Improper assembly and cleaning can
cause unreliable operation.
Regular preventive maintenance is important in
applications that place a heavy load on system controls
such as those used in the commercial cooking and
agricultural and industrial industries because:
• In many such applications, particularly commercial
cooking, the equipment operates 100,000 to 200,000
cycles per year. Such heavy cycling can wear out the
gas control in one to two years.
• Exposure to water, dirt, chemicals and heat can
damage the gas control and shut down the control
system. A NEMA 4 enclosure can reduce exposure to
environmental contaminants. See Electronic Ignition
Service manual, form 70-6604.
The maintenance program should include regular check-
out of the system as outlined in the Startup and
Checkout section, and checkout of the control system as
described in the appliance manufacturer literature.
Maintenance frequency must be determined individually
for each application. Some considerations are:
•Cycling frequency. Appliances that may cycle 20,000
times annually should be checked monthly.
•Intermittent use. Appliances that are used seasonally
should be checked before shutdown and again before
the next use.
•Consequence of unexpected shutdown. Where the
cost of an unexpected shutdown would be high, the
system should be checked more often.
•Dusty, wet, or corrosive environment. Because these
environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.
Any control should be replaced if it does not perform
properly on checkout or troubleshooting. In addition,
replace any module if it is wet or looks like it has ever
been wet. Protective enclosures, as described in the
Planning the Installation section, are recommended
regardless of checkout frequency.
TROUBLESHOOTING
IMPORTANT
1. The following service procedures are provided
as a general guide. Follow appliance manufac-
turer service instructions if available.
2. Meter readings between gas control and ignition
module must be taken within the trial for igni-
tion period. Once the ignition module shuts off,
wait for retry or reset at the thermostat.
3. If any component does not function properly,
make sure it is correctly installed and wired
before replacing it.
4. The ignition module cannot be repaired. If it
malfunctions, replace it.
5. Only trained, experienced service technicians
should service hot surface ignition systems.
6. After servicing, verify proper system operation.
Perform the checkout steps in the Startup and Checkout
section as the first step in troubleshooting. Then check
the troubleshooting sequence (Fig. 8) to pinpoint the
cause of the problem.
After troubleshooting, perform the checkout procedure
again to be sure the system is operating normally.
Status LED used to Troubleshoot
The LED can be used to check the appliance status. A
description of the LED signals follows.
IMPORTANT
The LED shows system status for the current
call for heat. When the call for heat is inter-
rupted (thermostat satisfied or system power
switched off), the LED goes off and the status
information is lost.
• Pulsing heartbeat is the normal operating mode
during a call for heat (24V terminal is powered). The
system can be in any of the normal operating modes
including prepurge, warmup, ignition trial, between
trial purge, or normal run.
• One flash indicates the S8910U is in an ignition
lockout mode. The most probable cause is the main
burner failing to light or failure to detect the flame.
Run the appliance through a call for heat and if the
burner does not light, check the:
— gas supply
— input voltage
— hot surface igniter
— gas control
— wiring