Adjustment
channel Description Adjustment range/selection Factory setting
Fluid type Heat transfer uid Tyfocor LS, Ethyl., Propyl.,
Water Water
Concentr.
Glycol concentration in the heat
transfer uid (only if uid type =
propylene glycol or ethylene glycol)
20 … 70 % 40 %
Metering Selection of quantity to be
metered Combined, Heat, Cold Heat
Alternative
unit Alternative unit option Yes, No No
Unit Alternative display unit Coal, Gas, Oil, CO2, €CO2
Factor Conversion factor 0.0000001 … 100.0000000 0.5000000
S0 output Switch input selection - -
Duration Impulse duration 30 … 120 ms 100 ms
Break Impulse break 30 … 120 ms 30 ms
Imp/kWh Impulse rate 1 … 1000 100
Reset back to factory setting Yes, No No
Funct. Activation / Deactivation Activated, Deactivated Activated
S1 is the ow sensor S2 is the return sensor (only if VFS has been selected as the
ow rate sensor, will the temperature be measured via the VFS sensor).
Depending on the ow rate sensor selected further adjustment channels appear,
see page 10.
In the adjustment channel Fluid type the heat transfer uid must be selected.
If either propylene glycol or ethylene glycol is selected, the adjustment channel
Concentration is indicated in which the antifreeze ratio of the heat transfer uid
can be adjusted.
For measurements below 0 °C a heat transfer uid with antifreeze has to be se-
lected.
The Metering channel is used for selecting whether heat quantity, cold quantity or
both are to be metered.
When the Alternative unit option is activated, the device will convert the en-
ergy quantities into the quantity of fossil fuels (coal, oil or gas) saved, or the CO2
emission saved respectively.The alternative Unit can be selected.A factor must be
adjusted for the calculation.The conversion factor depends on the arrangement in
use and has to be determined individually.
In the S0 output menu, a digital impulse output can be adjusted for each calorim-
eter, in order to issue the energy metered in form of pulses.The impulse duration,
break and rate can be adjusted.
In order to reset the settings of a calorimeter, select Reset and conrm the secu-
rity enquiry with Ye s .
With the menu item Function, a calorimeter already adjusted can be temporarily
deactivated or re-activated respectively. In this case, all adjustments will remain
stored. If a calorimeter is deactivated, energy metering does not take place by this
one. Sensor faults are ignored for the deactivated HQM.