BURNER STARTING DIFFICULTIES AND THEIR CAUSES
Signal Problem Possible cause Recommended remedy
2 blinks Once the pre-purg-
ingphaseandsafety
time have passed,
the burner goes into
lockout without the
appearance of the
flame
1 - The operation solenoid lets little gas.
through Increase
2 - One of the two solenoid valves does
not open. Replace
3 - Gas pressure too low . . . . . . . . . . . . Increase pressure at governor
4 - Ignition electrode incorrectly adjusted Adjust
5 - Electrode grounded due to broken . .
insulation Replace
6 - High voltage cable defective . . . . . . . Replace
7 - High voltage cable deformed by high
temperature Replace and protect
8 - Ignition transformer defective . . . . . . Replace
9 - Incorrect valve or transformer . . . . .
electrical wiring Check
10 - Defective control box. . . . . . . . . . . . . Replace
11 - A closed valve upline the gas train . . Open
12 - Air in pipework. . . . . . . . . . . . . . . . . . Bleed air
13 - Gas valves unconnected or with . . .
interrupted coil Check connections or replace
coil
3 blinks The burner does not
switch on, and the
lockout appears
14 - Air pressure switch in operating posi-
tion Adjust or replace
The burner switches
on, but then stops in
lockout
- Air pressure switch inoperative due to
insufficient air pressure:
15 - Air pressure switch incorrectly
adjusted. Adjust or replace
16 - Pressure switch pressure test point .
pipe blocked Clean
17 - Poorly adjusted head. . . . . . . . . . . . . Adjust
18 - High pressure in the furnace. . . . . . . Connect air pressure switch to
fan suction line
Lockout during pre-
purging phase 19 - Defective motor control contactor . . .
(only three-phase version) Replace
20 - Defective electrical motor . . . . . . . . . Replace
21 - Motor lockout (defective electrical
motor) Replace
4 pulses The burner switches
on, but then stops in
lockout
22 - Flame simulation. . . . . . . . . . . . . . . . Replace the control box
Lockout when
burner stops 23 - Permanent flame in the combustion .
head or flame simulation Eliminate persistence of flame
or replace control box
7 blinks Theburnergoesinto
lockout immediately
following the
appearance of the
flame
24 - The operation solenoid lets little gas.
through Increase
25 - Ionisation probe incorrectly adjusted. Adjust
26 - Insufficient ionisation (less than 5 A). Check probe position
27 - Earth probe . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
28 - Burner poorly grounded. . . . . . . . . . . Check grounding
29 - Phase and neutral connections
inverted Invert them
30 - Defective flame detection circuit . . . . Replace the control box
Burner goes into
lockout during oper-
ation
31 - Probe or ionisation cable grounded. . Replace worn parts