Rish Master 3430 User manual

RISH Master 3430
RISH Master 3430
Operating Manual
%THD

Section
Multi-function Digital Meter
Installation & Operating Instructions
Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
INDEX
3.2 Set Up Screens
3.2.1 System Type
3.2.2 Potential Transformer Primary value
3.2.4 Current Transformer Primary value
3.2.5 Current Transformer Secondary value
3.2.6 Reset
3.2.8 Low current noise cutoff
3.2.9 RS 485 Device Address
3.2.10 RS 485 Baud rate
3.2.11 RS 485 Parity Selection
3.2.12 Assignment of Energy to Pulse output-1
3.2.13 Assignment of Energy to Pulse output-2
3.2.7 Auto Scrolling
3.2.3 Potential Transformer Secondary value
1

DMAN-00IM-0647 Rev D - 06/2018
3.2.15 Pulse rate
3.2.16 Parameter setting for Analog output -1
3.2.17 Parameter setting for Analog output -2
3.2.18 Energy update rate
3.2.19 Energy digit reset count.
3.2.20 Energy display on Modbus
3.2.14 Pulse duration
10. Specification
8. Installation
8.1 EMC Installation Requirements
8.2 Case Dimensions and Panel Cut-out
8.3 Wiring
8.4 Auxiliary Supply
8.5 Fusing
8.6 Earth / Ground Connections
9. Connection Diagrams
11. Connection for Optional Pulse output / RS 485 /Analog Ouput
4. Analog output option
Relay Output (optional)
5.
Rs485 MODBUS Output
7. Phaser Diagram
6.
2

1. Introduction
The 3430 is a panel mounted 96 x 96mm DIN Quadratic Digital metering
system for the measurement important electrical parameters like AC voltage,
AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) .
The instrument integrates accurate measurement technology (All Voltages &
Current measurements are True RMS upto 15th Harmonic) with 3 line 4 digits
Ultra high brightness LED display.
3430 can be configured and programmed
at site for the following :
PT Primary, PT Secondary, CT Primary,
CT Secondary (5A or1A) and 3 phase 3W
or 3 Phase 4W system.
Down Up
VRY
KVAr
Sys
V x1000
KVArh
IN
Ph R
KAh
VYB
A
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
Angle
KW
VBR
Max
x1000
P.F.
KWh
Ph B
Down Up
Max
KVAr
V x1000
KVArh
Angle
A
KVA
Min
x1000
Hz
D
kVAh
KW
kAh
x1000
P.F.
kWh
%THD
The screen shown on left is of 3 Phase Meter.
The front panel has two push buttons through
which the user may scroll through the
available measurement readings, reset the
energy (Import/Export) Min/Max (System Voltage
and System Current) and configure the product.
The screen shown further is of 1 Phase Meter.
3

TABLE 1:
Measured Parameters
System Voltage
System Current
Voltage VL1-N(4wire only)
Voltage VL2-N(4wire only)
Voltage VL3-N(4wire only)
Voltage VL1-L2
Voltage VL2-L3
Voltage VL3-L1
Current L1
Current L2
Current L3
Units of
Volts
Amps
Volts
Volts
Volts
Volts
Volts
Volts
Amps
Amps
Neutral Current ( 4 wire only )
Amps
Amps
Measurement
Active Import Energy (8 Digit resolution) kWh
kWh
Active Export Energy (8 Digit resolution)
Active Power (System / Phase (4 wire only) )
Reactive Power (System / Phase (4 wire only))
Apparent Power (System / Phase (4 wire only))
Power Factor (System / Phase (4 wire only))
Phase Angle ( Phase(4 wire only))
Kwatts
KVAr
KVA
Degree
kVArh
Reactive Import Energy (8 Digit resolution)
kVArh
Reactive Export Energy (8 Digit resolution)
kVAh
Apparent Energy (8 Digit resolution)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
4

*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
Measured Parameters Units of
Measurement
I1 THD
I2 THD
V1 THD*
V2 THD*
V3 THD*
%
I3 THD
System Voltage THD
System Current THD
%
%
%
%
%
%
%
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
5

2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading
screens out of several screens. These screens may be scrolled through one
at a time in incremental order by pressing the “ Up key” and in decremental
order by pressing “ Down key”.
Parameter Screens 1 Phase
System Voltage
System Current
System Active Power
Phase Angle
Frequency
System Power Factor
Reactive Power
Apparent Power
Active Power
Active
Energy
Import
Min. System Voltage
Min. System Current
Active
Energy
Export
Reactive
Energy
Import
Reactive
Energy
Export
Apparent
Energy
Max. System Voltage
Max. System Current
System Voltage
Current % THD
6

Parameter Screens 3 Phase
System Voltage
System Current
System Active Power
R Phase V L-N*
Y Phase V L-N*
B Phase V L-N*
R Phase Current
Y Phase Current
B Phase Current
Neutral Current*
Frequency
System Power Factor
Reactive Power
Apparent Power
Active Power
Active
Energy
Import
Min. System Voltage
Min. System Current
Active
Energy
Export
Reactive
Energy
Import
Reactive
Energy
Export
Apparent
Energy
Max. System Voltage
Max. System Current
R Phase Reactive Power*
R Phase Apparent Power*
R Phase Active Power*
Y Phase Reactive Power*
Y Phase Apparent Power*
Y Phase Active Power*
B Phase Reactive Power*
B Phase Apparent Power*
B Phase Active Power*
Phase Angle R*
Phase Angle Y*
Phase Angle B*
Phase Power Factor R*
Phase Power Factor Y*
Phase Power Factor B*
Voltage %
THD
Current %
THD
System Voltage
Current % THD
VRY V L-L
VYB V L-L
VBR V L-L
A
A
NOTE: SCREENS MARKED WITH * ARE AVAILABLE
ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
7

Setup Parameter Screens
SYS*
(System Type)
PtPr
(PT Primary)
PtSc
(PT Secondary)
CtPr
(CT Primary)
CtSc
(CT Secondary)
rsEt
(reset parameter)
Auto
(Auto Scrolling)
n.Cut
(Noise Current Cutoff)
Addr
(Modbus address)
bAUd
(baud rate)
Prty
(Parity
bits)
none (No Parameter)
ALL (All Parameter)
E (Energy)
hi (Max Values)
Lo(Min Values)
Select any one option
using down key
rl1
(Relay 1 )
rl2
(Relay2)
puls
(Pulse Duration)
rAtE
(Pulse Divisor)
codE
(Password)
AnL1
(Analog1 Parameter
Selection)
AnL2
(Analog1 Parameter
Selection)
Enrt
(Energy update rate)
Edrc
(Energy digit reset
count)
En.OP
(Energy Output on
Modbus)
*Note :Sys type selection screen is not available in 1 phase.
8

3.1. Password Protection
Password protection can be enabled to prevent unauthorized access to
set-up screens, by default password protection is not enabled.
Password protection is enabled by selecting a four digit number other than
0000, setting a password of 0000 disables the password protection.
3. Programming
The following sections comprise step by step procedures for configuring the
3430 for individual user requirements.
To access the set-up screens press and hold the “
Key simultaneously for 5 seconds. This will take the User into the Password
Protection Entry Stage (Section 3.1).
Down” and “ Up”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
9

VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Enter Password, second digit entered, prompt for third
digit.
(* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the third
digit from 0 through to 9, the value will wrap from 9
round to 0.
Press the “ Up” key to advance to next digit.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Enter Password, third digit entered, prompt for fourth
digit.
(* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the fourth
digit from 0 through to 9, the value will wrap from 9
round to 0.
Press the “ Up” key to advance to verification of the
password.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
10

Enter Password, fourth digit entered, awaiting
verification of the password.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Pressing the “ Up” key will advance to the
Password confirmed.
Pressing “ Down” key will advance to the “New /
change Password” entry stage.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Password Incorrect.
The unit has not accepted the
Password entered.
Pressing the " Down" key will return to
the Enter Password stage.
Pressing the “ Up” key exits the
Password menu and returns operation
to the measurement reading mode.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Menu selection
11

New / Change Password, first digit entered, prompting for
second digit. (*Decimal point indicates that this will be
flashing).
Pressing the “ Down” key will scroll the value of the
second digit from 0 through to 9, the value will wrap from
9 round to 0.
Pressing the “ Up” key to advance the operation to the
next digit and sets the second digit, in this case to “1”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
New / Change Password
(*Decimal point indicates that this will be flashing).
Pressing the “ Down” key will scroll the value of the
first digit from 0 through to 9, the value will wrap from 9
round to 0.
Pressing the “ Up” key to advance the operation to
the next digit and sets the first digit, in this case to “2”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
New / Change Password, second digit entered,
prompting for third digit. (*decimal point indicates that
this will be flashing).
Pressing the “ Down” key will scroll the value of the
third digit from 0 through to 9, the value will wrap from 9
round to 0.
Pressing the “ Up” key to advance the operation to
the next digit and sets the third digit, in this case to “5”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
12

type confirmation menu.
New / Change Password, third digit entered, prompting
for fourth digit. (* denotes that decimal point will be
flashing).
Pressing the “ Down” key will scroll the value of the
fourth digit from 0 through to 9, the value will wrap from
9 round to 0.
Pressing the “ Up” key to advance the operation to
the “New Password Confirmed” and sets the fourth digit,
in this case to “3”.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
New Password confirmed.
Pressing the “ Down” key will return to the
“New/Change Password”.
Pressing the “ Up” key will advances to the
Menu selection screen.(see section 3.2).
3.2 Set up Screens
3.2.1 System Type
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
This screen is used to set the system type .
System type ”3” for 3 phase 3 wire & “4” for 3 phase
4 wire system.
Pressing the “ Up” key accepts the present
primary value Edit” menu (see section 3.2.2)
value and advances to the “Potential transformer
Pressing the “ Down” key will enter the system type
edit mode and scroll the values through values available .
Pressing the “ Up” key advances to the system
13

This screen will only appear following the edit of
system type. If system type is to be Downed again,
Pressing the “ Down” key will return to the system type
edit stage by blanking the bottom line of the display
Pressing the “ Up” key sets the displayed value and
will advance to “Potential Transformer Primary Value
Edit” menu. (See section 3.2.2)
System Type Confirmation
Pressing the “ Up” key accepts the present value
and advances to the “potential Transformer secondary
Value edit” menu. (See Section 3.2.3)
Pressing the “ Down” key will enter the “Potential
Transformer Primary Value Edit” mode.
Initially the “multiplier must be selected, pressing the “
Down” key will move the decimal point position to the
right until it reaches # # # .# after which it will return to
#. # # #.
Pressing the “ Up” key accepts the present
multiplier (decimal point position) and advances to the
“potential Transformer primary Digit Edit” mode.
3.2.2 Potential Transformer Primary Value
The nominal full scale voltage which will be displayed as the Line to Line voltages for all
system types. The values displayed
represent the voltage in kilovolts (note the x1000 enunciator).
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
14

Potential Transformer primary Digit Edit
Pressing the “ Down” key will scroll the value of
the most significant digit from 0 through to 9 unless
the presently displayed Potential Transformer Primary
Value together with the Current Transformer Primary
Value, previously set, would result in a maximum power
of greater than 666.6 MVA per phase in which case
the digit range will be restricted.
Pressing the “ Up” key accepts the present value
at the cursor position and advances the cursor to the
next less significant digit.
The PT Primary value can be set from 100V L-L to 692.8 kV L-L.
Note : the flashing decimal point indicates the cursor position, a steady decimal point will
be present to identify the scaling of the number until the cursor position coincides with the
steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the “ Up” key will advance to the
“Potential Transformer Primary Value Confirmation” stage.
Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor
flashing at the “hundreds of volts” position.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
15

VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
L-L
Note : 0.120 kV i.e. 120 V
Potential Transformer Primary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Primary Value.
If the scaling is not correct, pressing the “ Down”
key will return to the “Potential Transformer Primary
Value Edit” stage.
Pressing the “ Up” key sets the displayed value
and will advance to the Potential Transformer
secondary Value (See Section 3.2.3)
3.2.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from
the Transformer when the potential transformer(PT)primary is supplied with the voltage
defined in 3.2.1.2. potential transformer primary voltage. The ratio of full scale primary to full
scale secondary is defined as the transformer ratio.
The Valid range of instrument is from 100 to 600V
Transformer Secondary Value Edit” mode.
“Down” key will scroll the value of the most significant
digit from available range of PT secondary value
Pressing the “ Down” key will enter the “Potential
Pressing the “ Up” key accepts the present value
and advances to the “Current Transformer Primary
Value edit” menu. (See Section 3.2.4)
Pressing the “ Up” key accepts the present value
at the cursor position and advances the cursor to the
next less significant digit.
L-L .
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
16

Note : the flashing decimal point indicates the cursor position, a steady decimal point will be
present to identify the scaling of the number until the cursor position coincides with the
steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the “ Up” key will advance to the
“Potential Transformer secondary Value Confirmation” stage.
3.2.4 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen
enables the user to display the Line currents inclusive of any transformer ratios, the values
displayed represent the Current in Amps.
Pressing the “ Up” key accepts the present value and advances to the Current Transformer
Secondary Value (See Section 3.2.5)
Potential Transformer Secondary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Secondary Value.
If the scaling is not correct, pressing the “ Down”
key will return to the “Potential Transformer Secondary
Value Edit”
Pressing the “ Up” key sets the displayed value
and will advance to the current Transformer Primary
Value (See Section 3.2.4)
Pressing the “ Down” key will enter the “Current Transformer Primary Value Edit” mode.
This will scroll the value of the most significant digit from 0 through to 9,unless the presently
displayed Current Transformer Primary Value together with the Potential Transformer
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
17

range will be restricted, the value will wrap.
Example: If primary value of PT is set as
692.8kV L-L (max value) then primary value
Pressing the “ Up” key will advance to the next
less significant digit. (* Denotes that decimal
point will be flashing).
Primary Value results in a maximum power of
greater than 666.6 MVA in which case the digit
when the “ Up” key is pressed.
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120%
of nominal voltage, i.e, 462.96 MVA nominal power per phase.
When the least significant digit had been set, pressing the “ Up” key will advance to the
“Current Transformer Primary Value Confirmation” stage.
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero
of Current is restricted to 1157A.
Current Transformer Primary Value Confirmation.
This screen will only appear following an edit of the
.
If the scaling is not correct, Pressing the “ Down”
key will return to the “ Current Transformer Primary
Value”Edit stage with the most significant digit
highlighted (associated decimal point flashing)
and the bottom line of the display will be blanked.
Pressing the “ Up” key sets the displayed value and
will advance to the “Current Transformer Secondary
Value Edit” menu. (See Section 3.2.5)
Current Transformer Primary Value.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
18

3.2.5 Current Transformer Secondary Value
This screen is used to set the secondary value for
Current Transformer. Secondary value “5” for 5A or
“1” for 1A can be selected. Pressing “ Up” key
accepts the present value and advances to the
Reset parameter screen (See Section 3.2.6)
Pressing the “ Down” key will enter the CT
Secondary value edit mode and scroll the value
through the values available.
Pressing the “ Up” key will advance to the CT
Secondary value confirmation.
CT Secondary value confirmation
This screen will only appears following an edit of CT
secondary value .
If secondary value shown is not correct, pressing the
Down key will return to CT secondary edit stage by
blanking the bottom line of the display.
Pressing “ Up” key sets the displayed value and
will advance to reset parameter menu.
(See Section 3.2.6)
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
19
Other manuals for Master 3430
1
Table of contents
Other Rish Measuring Instrument manuals