Rish ED 1100 User manual

RISH ED 1100
Operating Manual
DMAN-00IM-1073

Section Contents
1. Introduction
2. LCD Display
2.1 Introduction
LCD Display Symbols and Indications 2.2
2.2.1 SO Output Indication
2.2.2 Communication Indication
2.2.3 Tariff Energy Indication
2.3 Setup Screens Navigation Map
3. Programming
3.1 Password Protection
3.2 Setup Menu Selection
3.2.1 Communication Parameter Selection
3.2.1.1 Address Setting
3.2.1.2 RS 485 Baud Rate
3.2.1.3 RS 485 Parity & Stop Bit
3.2.2 Output Parameter Selection
3.2.2.1 Pulse Output Parameter Selection
3.2.2.2 Pulse Rate
3.2.2.3 Pulse Duration
3.2.2.4 Demand Integration Time
3.2.2.5 Reset Parameter Selection 3.2.2.3 Pulse Duration
3.2.2.6 Auto Scroll
3.2.2.7 New / Change Password
3.2.2.8 Quite Setup Menu
4. Digital Input
4.1 Digital Input and Tariff Selection
5. SO Output
5.1 Pulse Output
Index

7. Installation
7.1 EMC Installation Requirements
7.2 Case Dimensions
7.3 Nameplate
7.4 Wiring
7.5 Auxiliary Supply
7.6 Fusing
8. Connection Diagrams
9. Specification

1. INTRODUCTION
The Direct Connected Energy Meter is a DIN Rail mounted Digital Meter, primarily for
bidirectional Active, Reactive and Apparent Energy measurement intended for use in
industrial, commercial and residential electrical energy metering. It also accurately measures
important electrical parameters like TRMS Voltage, TRMS Current, Frequency, Active /
Reactive and Apparent Power, and Power Factor in Single Phase Networks. The meter is
engineered using advanced microcontroller technology and is suitable for electrical parameter
measurement and monitoring in 1 Phase 2 Wire Networks. It supports maximum 100 A current
measurement on direct connection. It displays parameters on bright intuitive LCD and also has
Pulse Outputs and Impulse LED for energy monitoring. It supports Tariff Counters selectable
via Digital Input or MODBUS Communication. It has inbuilt industry standard MODBUS RTU
for remote monitoring.
Measurement and
Energy / Counter
Screen
Impulse LED
Scroll Key Enter Key
4

2. LCD Display
The meter displays more than 80 measurement parameters including Total Energies, Tariff, Partial
and also other important electrical parameters like Max Demand, Voltage, Current, Frequency,
Active, Power, Reactive Power, Apparent Power and Power Factor on individual screens. The
user can easily scroll and See System Parameter By Pressing Scroll key and By Pressing and
Holding Scroll key for 5 Seconds the user can see Tarrif & Demand Parameters on screen2. again
Pressing and Holding Scroll key for 5 Seconds it back to the Main Parameter Screen1. Refer Table
1 & Table 2 for list all the Measurement Parameters available on Display and MODBUS.
The LCD has bold seven segment digits with bright white backlit for display of measurement
parameters. Special symbols, units and bar graph are provided for effective display and easy
onsite configuration. Indications for current reversal, communication status, active tariff, digital
inputs and pulse outputs status are continuously available on screen. Measurement screen can
be set as automatic scrolling or manual scrolling.
2.2. LCD Display Symbols and Indications
2.1. Introduction
2.2.1 SO Output Indication
The meter has two opto-isolated pulse outputs that can be configured for any one of the Active, Reactive and
Apparent Energy parameter.
2.2.2 Communication Indication
The meter provides communication based on MODBUS protocol for remote data acquisition of measurement data
and configuration. If meter is properly communicating with host than it is indicated by symbol as shown:
This symbol indicates that the meter is communicating.
This symbol indicates that SO1 is energized.
This symbol indicates that SO2 is energized.
5

2.2.3 Tariff Energies Indication
This Instrument comes with 2 tariff based on Digital Input In the
image given here, it indicates that the instrument is currently
displaying the selected energy parameter (Import Active Energy)
of Tariff 2.
These Tariff energies and Demand parameters are available on
display screen 2, For opening the Screen 2 Press and hold the
Scroll Key for 5 Seconds
TABLE 1 : Measurement Parameters:
No. Parameters On Display On Modbus
Import Active Energy
Export Active Energy
Total Active Energy
Import Reactive Energy
Export Reactive Energy
Total Reactive Energy
Total Apparent Energy
Partial Import Active Energy
Partial Export Active Energy
Partial Total Active Energy
Partial Import Reactive Energy
Partial Export Reactive Energy
Partial Total Reactive Energy
Partial Total Apparent Energy
Voltage
Current
Power
Reactive Power
Active Power
Power Factor
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Parameter
6

TABLE 1 : Measurement Parameters (contd.):
No. Parameters On Display On Modbus
Frequency
T1 Import Active Energy
T1 Export Active Energy
T1 Total Active Energy
T1 Import Reactive Energy
T1 Export Reactive Energy
T1 Total Reactive Energy
T1 Total Apparent Energy
T2 Import Active Energy
T2 Export Active Energy
T2 Total Active Energy
T2 Import Reactive Energy
T2 Export Reactive Energy
T2 Total Reactive Energy
T2 Total Apparent Energy
Import KW Max Demand
Export KW Max Demand
Import KVAr Max Demand
Export KVAr Max Demand
Import KVA Max Demand
Export KVA Max Demand
Current Max Demand
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Parameter
7

2.3 Setup Parameters Screens Navigation Map
CodE (PassWord)
Add 001
(Modbus Address)
(Sec 3.2.2.1)
bd 9600
(Baud Rate)
(Sec 3.2.2.2)
Prtyn-1
(Parity and Stop Bits)
(Sec 3.2.2.3)
(Pulse Output 1 Para Selection)
(Sec 3.2.3.1.1.2)
PLS1out
(Pulse Output 2 Para Selection)
(Sec 3.2.3.1.1.2)
PLS2out
(Pulse Rate)
Cst 1000
(Pulse Duration)
PLSt 200
(Demand Integration Time)
dit 15
(Reset Parameter)
rSt non
(Auto Scroll)
SCrL no
(Set Password)
Set PASS
(exit setup)
quit no
8

3.1 Password Protection
Password protection can be enabled to prevent unauthorized access to set-up screens, when default
password protection is not enabled. Password protection is enabled by selecting a four digit number other
than 0000, setting a password of 0000 disables the password protection.
3. PROGRAMMING
The following sections comprise step by step procedures for configuring the Energy Meter according to
individual user requirements. To access the set-up screens press and hold “ ”enter key for 5 seconds. This
will take the User into the Password Protection Entry Stage (Section 3.1).
Enter Password, prompt for first digit. Press the “ ” scroll key to scroll the value of first digit
from 0 through to 9, Press the “ ” enter key to advance to next digit.
Enter Password, first digit entered, prompt for second digit..
Press the “ ” scroll key to scroll the value of first digit from 0 through to 9
Press the “ ” enter key to advance to next digit.
Enter Password, second digit entered, prompt for third digit.
Press the “ ” key to scroll the value of first digit from 0 through to 9.
Press the “ ” enter key to advance to next digit.
Enter Password, third digit entered, prompt for fourth digit. .
Press the “ ” scroll key to scroll the value of first digit from 0 through to 9.
Press the “ ” key to advance to verification of the password.
password confirmed and Pressing “ ” enter key advances to the “Setup Menu”
entry stage. ( See Section 3.2).
When this Screen appears and first digit is blinking means the unit has not accepted the
Password entered. it gives one more chance to enter the password and after this meter will
quit setup menu.
Password Incorrect.
9

3.2 Setup Menu selection
3.2.1 Communication Parameter Selection
3.2.1.2 RS 485 Baud Rate
This screen allows the user to set Baud Rate of RS 485 - MODBUS port. The values
displayed on screen are in bits per second.
Pressing “ ” scroll key accepts the present value and advance to the “RS 485 Parity and
Stop Bit Selection” screen (see Section 3.2.2.3).
Pressing the “ ” enter key advances to the “Baud Rate Edit” mode and pressing the
scroll key scrolls the value through 4800, 9600, 19200 and 38400 baud.
Pressing the enter key sets the value and shows the “RS 485 Baud Rate” screen (see
Section 3.2.1.2).
NOTE: Default value is set as ‘9600’.
3.2.1.1 Address Setting
This screen applies to the RS 485 output. This screen allows the user to set RS 485
address for the meter. The allowable range of addresses is 1 to 247.
Press “ ” enter key to set the RS 485 address of meter.
pressing the “ ” scroll key to advance to the “Buad Rate” setup screen.
Press enter key to enter into edit mode, prompt for first digit.
Press the scroll keys to scroll the value of the first digit. Press the enter key to advance to
next digit.
Similarly, enter second and third digits of address. After entering third digit, pressing enter
key confirms the selection and shows “Done” screen.
The default setting is ‘001’.
3.2.1.3 RS 485 Parity and Stop Bit
This screen allows the user to set Parity & number of stop bits of RS 485 port.
Pressing “ ” scroll key accepts the present value and advances to “pulse output
Parameters” screen (see section 3.2.2)
10

Pressing the “ ” enter key advances to the “Parity & Stop bit Edit” mode & pressing the
“ ’’scroll keys scrolls the value through: nonE1: no parity with one stop bit, nonE2: no
parity with two stop bit, EVEn: even parity with one stop bit, odd: odd parity with one stop
bit
Pressing enter key sets the value and advances to “output parameter Selection” screen
(see Section 3.2.2.).
Default value is set as ‘nonE1’.
3.2.2.1. Pulse Output
This screen is used to set the pulse1 ie SO1 output parameter.
Pressing “ ”scroll key accept the current values and advances to “pulse output 2
Parameter Selection” menu.
Pressing the “ ” enter key advances to the “ pulse output 1 Parameter edit ” mode &
pressing the scroll keys scrolls the value through: IMP KWH, EXP KWH, IMP
KVArh, EXP KVArh, IND KVArh, CAP KVArh. (see Table 3)
Pressing enter key sets the value and advances to “pulse output 2 parameter Selection”
screen.
Default value is IMP KWH - import kwh
3.2.2 Output Parameter Selection
This screen is used to set the pulse2 ie SO2 output parameter.
Pressing “ ”scroll key accept the current values and advances to “Pulse Rate selection”
menu (see Section 3.2.2.2).
Pressing the “ ” enter key advances to the “ pulse output 2 Parameter edit ” mode &
pressing the scroll keys scrolls the value through: IMP KWH, EXP KWH, IMP
KVArh, EXP KVArh, IND KVArh, CAP KVArh. (see Table 3)
Pressing enter key sets the value and advances to “Pulse Rate” screen (see Section
3.2.2.2)
3.2.2.2. Pulse Rate
This screen applies to the Pulse Output option only. The screen allows user to set the
following pulse rates: 1 pulse per 1 (1kWh) / 10 (1kWh) / 100 (1kWh) / 1000 (1kWh).
Pressing “ ” scroll key accepts the present selection and takes to the “Pulse Duration
Selection” menu (See section 3.2.2.3).
Pressing the “ ” enter key advances to “Pulse Rate Edit” mode & pressing Scroll key will
scrolls the value through the values 1, 10, 100 and 1000.
Pressing the enter key set the value and advances to “Pulse Duration” screen (see Section
3.2.2.3).
The default setting is ‘1000’.
11

3.2.2.3 Pulse Duration
This screen applies only to the Pulse Output. This screen allows the user to set pulse
Output energization time in milliseconds.
Pressing “ ” scroll key accepts the present value and advance to “Demand integration
time” screen ( see section 3.2.2.4).
Pressing the “ ” enter key advances to “Pulse Duration Edit” mode and pressing the “
”scroll keys scroll the value through 60, 100 and 200 miliseconds.
Pressing the enter key selects the value and advances to “Demand integration time” menu
(see Section 3.2.2.4).
Default value is set to ‘200’ ms.
Note - For 100 A current setting use 60 ms as value of pulse duration
This screen is used to set the period over which current and power readings are to be
integrated. The Unit of displayed value is minutes.
Pressing “ ” scroll key accepts the present value and advance to “Reset Parameter”
screen.
Pressing the“ ” enter key advances to “Demand integration time Edit” mode and pressing
the scroll keys scroll the value through 5,10,15,30 minutes.
Pressing the enter key selects the value and advances to “Reset Parameter” menu (see
Section 3.2.2.5).
Default value is set to ‘15’minute.
This screen is used to reset different parameters.
Pressing “ ” scroll key accepts the present value and advance to “Auto Scroll” screen.
Pressing the “ ” enter key advances to “Reset Parameter Edit” mode and pressing the
scroll keys scroll through none, partial energy, demand, power down counter and all .
Pressing the enter key selects the value and advances to “Auto scroll” menu (see Section
3.2.2.6).
3.2.2.5 Reset Parameter Selection
3.2.2.6 Auto Scrolling
This screen allows user to enable auto screen scrolling.
Pressing “ ” scroll key accepts the present status and advance to the “Change Password
”screen (see Section 3.2.2.7).
Pressing the “ ” enter key advances to “Auto scroll Edit” mode and pressing the scroll
keys scroll through no,10, 20, 30 sec.
No - Auto scroll is disabled
10,20,30 - Autoscroll activated and number here displays Time in seconds between two
screens in autoscroll
Pressing the enter key selects the value and advances to “Set Password” menu
(see Section 3.2.2.7).
3.2.2.4 Demand Integration Time
12

3.2.2.7 New / Change Password
This screen allows user to set password screen scrolling.
Pressing “ ” scroll key accepts the present status and advance to the “quit screen” screen
(see Section 3.2.2.8).
Pressing the “ ”enter key advances to “Set password Edit” mode and
pressing the “ ”scroll keys scroll the value of first digit from 0 through to 9.
Pressing the “ ” enter key selects the value and advances to set second digit.
pressing the “ ”scroll keys scroll the value of second digit from 0 through to 9.
Pressing the “ ” enter key selects the value and advances to set third digit.
pressing the “ ”scroll keys scroll the value of third digit from 0 through to 9.
Pressing the “ ” enter key selects the value and advances to set forth digit.
pressing the “ ”scroll keys scroll the value of fourth digit from 0 through to 9.
Pressing the “ ” enter key selects the value and advances to Password conformation.
3.2.2.8 Quit Setup Menu
This screen allows user to Exit from Setup Menu.
Pressing the “ ” enter key advances to “quit setup” edit mode
pressing the “ ” scroll key scroll the options yes or no.
Pressing the “ ” enter key will conforms the selection.
if YES selected then meter will quit from setup, selecting the NO option it will advanced to
address setup screen (see Section 3.2.1.1).
13

4. Digital Input :
4.1 Digital Input and Tariff Selection:
TABLE 2 : Relationship between Digital Input and Tariff
Digital Input 1 Tariff number
LOW Tariff 1
HIGH Tariff 2
The meter is optionally provided with 1 Digital Inputs for selection of active tariff respectively for energy
metering.
5. SO Output :
5.1 Pulse Output :
Pulse Output is opto-coupler based S0 which can be used to drive an external mechanical counter for energy
measurement. The Pulse Output can be configured to the parameters mentioned in TABLE 3 through setup
parameter screen.
The Meter is provided with two opto-isolated pulse outputs that can be configured for any one of the Active,
Reactive and Apparent Energy parameters. Refer TABLE 3 for parameters for pulse output. The pulse width
and rate of pulse out is onsite programmable .
TABLE 3 : Parameters for Pulse Output
1
2
3
4
5
6
Parameter
Number Parameter 1P 2W
Import Active Energy
Export Active Energy
Import Reactive Energy
Export Reactive Energy
Inductive Reactive Energy
Capacitive Reactive Energy
14

6. RS 485 ( ModBus ) Output :
The Energy Meter supports MODBUS (RS485) RTU protocol (2-wire ) .
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained
together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents,
an Earth connection should be made at one point on the network. Loop (ring) topology does not require any
termination load. Line topology may or may not require terminating loads depending on the type and length of
cable used. The impedance of the termination load should match the impedance of the cable and be at both
ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments can
be connected in RS485 network. The permissible address range for The Meter is between 1 and 247
for 32 instruments. Broadcast Mode (address 0) is not allowed.
After sending any query through software (of the Master), it must allow 300ms of time to elapse before assuming
that the Meter is not going to respond. If slave does not respond within 300 ms, Master can ignore the previous
query and can issue fresh query to the slave.
16 Presets Multiple Registers Set the content of read / write locations ( 4X )
04 Read input Registers Read content of read only location ( 3X )
Read Holding Registers Read content of read /write location ( 4X )
03
Communication Baud Rate is user selectable from the front panel between 2400,4800,9600,19200,38400 bps.
Function code :
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of the message
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754)
Most significant byte first (Alternative least significant byte first)
Format of Data Bytes
2 byte Cyclical Redundancy Check (CRC)
Error Checking Bytes
1 start bit,
8 data bits, least significant bit sent first
1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity
Byte format
Each byte in RTU mode has following format:
Exception Cases : An exception code will be generated when Meter receives ModBus query with valid parity
& error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value)
The response generated will be “Function Code” ORed with HEX (80H ). The exception codes are listed below
15

01 Illegal function The function code is not supported by Meter
02 Illegal Data Address Attempt to access an invalid address or an
attempt to read or write part of a floating point value
03 Illegal DataValue Attempt to set a floating point variable to an invalid value
6.1 Accessing 3X and 4X register for reading measured values:
Two consecutive 16 bit registers represent one parameter. Refer TABLE 1 for the addresses of 3X and 4X
registers used for parameters measured by the instrument. Each parameter is held in the 3X as well as 4X
registers. Modbus Code 04 and 03 are used to access all parameters in 3X and 4X registers respectively.
Example :
To read parameter,
Voltage2 from 3X: Start address = 00 00 Number of registers = 02
Watt1 from 4X: Start address = 00 0C Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each query for reading the data must be restricted to 40 parameters or less. Exceeding the 40 parameter
limit will cause a ModBus exception code to be returned.
Device
Address
Function
Code
Start Address
High
Start Address
Low
Number of
Registers Hi
Number of
Registers Lo
CRC
Low
CRC
High
01 (Hex) 04 (Hex) 00 (Hex) 02(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)
Query for 3X read:
3X Response: Voltage 1 (219.254V)
Device
Address
Function
Code
Byte
Count
Data Register1
High Byte
CRC
High
01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 5B (Hex) 41 (Hex) 21 (Hex) 6F (Hex)
Data Register1
Low Byte
Data Register2
High Byte
Data Register2
Low Byte
9B (Hex)
CRC
Low
Byte Count : Total number of data bytes received.
Query for 4X read:
Device
Address
Function
Code
Start Address
High
Start Address
Low
Number of
Registers Hi
Number of
Registers Lo
CRC
Low
CRC
High
01 (Hex) 03 (Hex) 00 (Hex) 0E(Hex) 00 (Hex) 02(Hex) E0 (Hex) C9 (Hex)
16
16

4X Response: Watt1 (2000 W)
Device
Address
Function
Code
Byte
Count
Data Register1
High Byte
CRC
High
01 (Hex) 03 (Hex) 04 (Hex) 44 (Hex) FA (Hex) 00 (Hex) 00 (Hex) CE (Hex)
Data Register1
Low Byte
Data Register2
High Byte
Data Register2
Low Byte
F2 (Hex)
CRC
Low
17
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Byte count : No. of Bytes Demanded by user in query.
TABLE 4 : 3 X and 4 X register addresses for measured parametersTABLE 4 : 3 X and 4 X register addresses for measured parameters
30001
30003
30005
30007
30009
30011
30013
30015
30017
30019
30021
30023
30025
30027
40001
40003
40005
40007
40009
40011
40013
40015
40017
40019
40021
40023
40025
40027
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Voltage
-
-
Current
-
-
Active Power
-
-
Apparent Power
-
-
Reactive Power
-
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
02
04
06
08
0A
0C
0E
10
12
14
16
18
1A
Address
(3X)
Address
(4X)
Parameter
Number
Parameter
Hex Address
High Byte
Low Byte
17

30029
30031
30033
30035
30037
30071
30073
30075
30077
30079
30081
30083
30085
30087
30089
30091
30093
30095
30097
30099
30101
30103
30105
30107
30109
30111
30113
30115
30117
30119
30121
30123
30125
30127
30129
40029
40031
40033
40035
40037
40071
40073
40075
40077
40079
40081
40083
40085
40087
40089
40091
40093
40095
40097
40099
40101
40103
40105
40107
40109
40111
40113
40115
40117
40119
40121
40123
40125
40127
40129
14
15
16
17
18
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
-
Power Factor
-
-
Angle
Freqency
kW Import Demand
kW Import Max Demand
kWr Export Demand
kW Exp. Max Demand
kvar Imp. Demand
kvar Imp. Max Demand
kvar Exp. Max Demand
kvar Exp. Max Demand
kva Imp. Demand
kva Imp. Max Demand
kva Exp. Demand
kva Exp. Max Demand
Current Imp. Demand
Current Imp Max. Demand
Current Exp. Demand
Current Exp. Max Demand
Watt R Fundamental
Active Import Energy Overflow Count
Active Import Energy
Active Export Energy Overflow Count
Active Export Energy
Reactive Import Energy Overflow Count
Reactive Import Energy
Reactive Export Energy Overflow Count
Reactive Export Energy
Apparent Import Energy Overflow Count
Apparent Import Energy
Apparent Export Energy Overflow Count
Apparent Export Energy
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1C
1E
20
22
24
46
48
4A
4C
4E
50
52
54
56
58
5A
5C
5E
60
62
64
66
68
6A
6C
6E
70
72
74
76
78
7A
7C
7E
80
Address
(3X)
Address
(4X)
Parameter
Number
Parameter
Hex Address
High Byte
Low Byte
TABLE 4 : Continued
18

30131
30133
30135
30137
30139
30141
30143
30145
30147
30149
30151
30153
30155
30157
30159
30161
30163
30165
30167
30169
30171
30173
30175
30177
30179
30181
30183
30185
30187
30189
30191
30193
30195
30197
30199
40131
40133
40135
40137
40139
40141
40143
40145
40147
40149
40151
40153
40155
40157
40159
40161
40163
40165
40167
40169
40171
40173
40175
40177
40179
40181
40183
40185
40187
40189
40191
40193
40195
40197
40199
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
Active Energy Overflow Count
Active Energy
Reactive Energy Overflow Count
Reactive Energy
Apparent Energy Overflow Count
Apparent Energy
T1 Active Import Energy Overflow Count
T1 Active Import Energy
T1 Active Export Energy Overflow Count
T1 Active Export Energy
T1 Reactive Import Energy Overflow Count
T1 Reactive Import Energy
T1 Reactive Export Energy Overflow Count
T1 Reactive Export Energy
T1 Apparent Import Energy Overflow Count
T1 Apparent Import Energy
T1 Apparent Export Energy Overflow Count
T1 Apparent Export Energy
T1 Active Energy Overflow Count
T1 Active Energy
T1 Reactive Energy Overflow Count
T1 Reactive Energy
T1 Apparent Energy Overflow Count
T1 Apparent Energy
T2 Active Import Energy Overflow Count
T2 Active Import Energy
T2 Active Export Energy Overflow Count
T2 Active Export Energy
T2 Reactive Import Energy Overflow Count
T2 Reactive Import Energy
T2 Reactive Export Energy Overflow Count
T2 Reactive Export Energy
T2 Apparent Import Energy Overflow Count
T2 Apparent Import Energy
T2 Apparent Export Energy Overflow Count
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
82
84
86
88
8A
8C
8E
90
92
94
96
98
9A
9C
9E
A0
A2
A4
A6
A8
AA
AC
AE
B0
B2
B4
B6
B8
BA
BC
BE
C0
C2
C4
C6
Address
(3X)
Address
(4X)
Parameter
Number
Parameter
Hex Address
High Byte
Low Byte
TABLE 4 : Continued
19

30201
30203
30205
30207
30209
30211
30213
30215
30217
30219
30221
30223
30225
30227
30229
30231
30233
30235
30237
30239
30241
30243
30245
30247
30249
30251
30253
30255
30257
30259
30261
30263
40201
40203
40205
40207
40209
40211
40213
40215
40217
40219
40221
40223
40225
40227
40229
40231
40233
40235
40237
40239
40241
40243
40245
40247
40249
40251
40253
40255
40257
40259
40261
40263
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
T2 Apparent Export Energy
T2 Active Energy Overflow Count
T2 Active Energy
T2 Reactive Energy Overflow Count
T2 Reactive Energy
T2 Apparent Energy Overflow Count
T2 Apparent Energy
PartialActive Import Energy Overflow Count
Partial Active Import Energy
Partial Active Export Energy Overflow Count
Partial Active Export Energy
Partial Reactive Import Energy Overflow Count
Partial Reactive Import Energy
partial Reactive Export Energy Overflow Count
Partial Reactive Export Energy
Partial Apparent Import Energy Overflow Count
Partial Apparent Import Energy
Partial Apparent Export Energy Overflow Count
Partial Apparent Export Energy
Partial Active Energy Overflow Count
Partial Active Energy
Partial Reactive Energy Overflow Count
Partial Reactive Energy
Partial Apparent Energy Overflow Count
Partial Apparent Energy
Run Hour
On Hour
No of Interrupts
Impulse Rate
Power Fail Status
Tarrif Status
Current Direction
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
01
01
01
01
C8
CA
CC
CE
D0
D2
D4
D6
D8
DA
DC
DE
E0
E2
E4
E6
E8
EA
EC
EE
F0
F2
F4
F6
F8
FA
FC
FE
00
02
04
06
Address
(3X)
Address
(4X)
Parameter
Number
Parameter
Hex Address
High Byte
Low Byte
TABLE 4 : Continued
Note: 1. The values are updated depending on update rate which can be set by the user.
For example, if user set update rate 10 min, then the values on these registers (marked with *) will
get updated on every 10 min.
2. External Counter gets updated when Digital Input is configured in Pulse Mode.
20
Table of contents
Other Rish Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

LinkU
LinkU LP-3PX user guide

Pro's Kit
Pro's Kit TE-8202A-W Series Operation manual

Elite
Elite MicroVario user manual

Accu-Flo Meter Service Ltd.
Accu-Flo Meter Service Ltd. 01N Series Operation guide

HANYOUNG NUX
HANYOUNG NUX PF3 instruction manual

Challenger Optics
Challenger Optics CO-OPM-96 Interactive operating manual