manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. RKC INSTRUMENT
  6. •
  7. Controllers
  8. •
  9. RKC INSTRUMENT HA400 Series User manual

RKC INSTRUMENT HA400 Series User manual

For detailed handling procedures and key operations, refer to separate
HA400/HA900/HA401/HA901 Operation Manual (IMR01N02-E).
The manual can be downloaded from the official RKC website:
http://www.rkcinst.com/english/manual_load.htm.
Digital Controller
IMR01N01-E8
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place the manual in a convenient location for easy reference.
This product is intended for use with industrial machines, test and measuring equipment. (It is not
designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source
of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
If input/output or signal lines within the building are longer than 30 meters.
If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage
connections such as power supply terminals must be enclosed in the instrumentation panel to
avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action. The power must be turned off before repairing work for input break
and output failure including replacement of sensor, contactor or SSR, and all wiring must be
completed before power is turned on again.
To prevent instrument damage as a result of failure, protect the power line and the input/output
lines from high currents with a suitableovercurrent protection device with adequate breakingcapacity
such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric
shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front panel
with a hard object.
Do not connect modular connectors to telephone line.
When high alarm with hold action/re-hold action is used for Event function, alarm does not turn
on while hold action is in operation. Take measures to prevent overheating which may occur if
the control device fails. NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of
electricity, process control, computer technology andcommunications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this
instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made
by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
componentshave a limited service life, orcharacteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes
no warranty expressed or implied, with respect to the accuracy of the information. The
information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
1. MOUNTING
Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions.
(IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 10 to 50 C (14 to 122 F)
Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX. W. C 29 g/m3dry air at 101.3 kPa)
Installation environment conditions: Indoor use, Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location:
Rapid changes in ambient temperature
which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam
splashes.
(4) Mount this instrument in the panel considering the following conditions:
Provide adequate ventilation space so that heat does not build up.
Do not mount this instrument directly above equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
If the ambient temperature rises above 50C (122 F), cool this instrument with a forced air fan,
cooler, etc. Cooled air should not blowdirectly on this instrument.
In order to improve safety and the immunity to withstand noise, mount this instrument as far
away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm.
Rotating machinery: Separate as far as possible.
For correct functioning mount this instrument in a horizontal position.
(5) In case this instrument is connected to a supply by means of a permanent connection, a switch or
circuit-breaker shall be included in the installation. This shall be in close proximity to the equipment
and within easy reach of the operator. It shall be marked as the disconnecting device for the
equipment.
Dimensions
Mounting Procedures
1. Prepare the panel cutout as specified in Dimensions.
2. Insert the instrument through the panel cutout.
3. Insert the mounting bracket into the mounting groove of theinstrument.
Do not push the mounting bracket forward. (Fig. 1)
4. Secure the bracket to the instrument by tightening the screw.
Take care to refrain from moving the bracket forward.
5.
Only turn about one full revolution after the screw touches the panel.
(Fig. 2)
If the screw has been rotated too tight, the screw may turn
idle. In such a case, loosen the screw once and tighten it
again until the instrument is firmly fixed.
6. The other mounting bracket should be installed in the same way
described in 3.to 5.
When the instrument is mounted, always secure with two mounting brackets so that upper
and lower mounting brackets are positioned diagonally.
The waterproof/dustproof (optional) on the front of the instrument conforms to IP65 when
mounted on the panel. For effective waterproof/dustproof, the gasket must be securely
placed between instrument and panel without any gap. If gasket is damaged, please contact
RKC sales office or the agent.
Removal Procedures
1.Turn the power OFF.
2. Remove the wiring.
3. Loosen the screw of the mounting bracket.
4. Hold the mounting bracket by the edge () and tilt it () to remove from
the case.(Fig. 3)
5. The other mounting bracket should be removed in the same way as
described in 3.and 4.
6. Pull out the instrument from the mounting cutout while holding the front
panel frame of this instrument. (Fig. 4)
2. WIRING
Wiring Cautions
For thermocouple input, use the appropriate compensation wire.
For RTD input, use low resistance lead wire with no difference in resistance between the three
or four lead wires.
To avoid noise induction, keep input signal wire away from instrument power line, load lines
and power lines of other electric equipment.
Signal connected to Voltage input and Current input shall be low voltage defined as “SELV”
circuit per IEC 60950-1.
If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise
filter.
- Shorten the distance between the twisted power supply wire pitches to achieve
the most effective noise reduction.
- Always install the noise filter on a grounded panel. Minimize the wiring distance
between the noise filter output and the instrument power supply terminals to achieve
the most effective noise reduction.
- Do not connect fuses or switches to the noise filter output wiring as this will reduce
the effectiveness of the noise filter.
Allow approximately 5 seconds for contact output when the instrument is turned on.
Use a delay relay when the output line is used for an external interlock circuit.
Terminal Configuration (All the terminal configuration of HA400, HA401, HA900 and HA901 is the same.)
Specifications
Power supply voltage:
90 to 264 V AC [Power supply voltage range], 50/60 Hz (Rating: 100 to 240 V AC)
21.6 to 26.4 V AC [Power supply voltage range], 50/60 Hz (Rating: 24 V AC)
21.6 to 26.4 V DC [Power supply voltage range] (Rating: 24 V DC)
Power consumption:
HA400/HA401: 16.5 VA max. (at 100 V AC) 22.5 VA max. (at 240 V AC)
15.0 VA max. (at 24 V AC) 430 mA max. (at 24 V DC)
HA900/HA901: 17.5 VA max. (at 100 V AC) 24.0 VA max. (at 240 V AC)
16.0 VA max. (at 24 V AC) 470 mA max. (at 24 V DC)
Measured input: TCinput, RTD input, Voltage input, Current input
Optional input: Remote input (Not isolation type), Feedback resistance input,
CT input, Event input, Power feed forward input
Output 1 to Output 3:
Relay contact output: 250 V AC, 3 A (Resistive load), 1a contact
Electrical life: 300,000 times or more (Rated load)
Voltage pulse output: 0/12 V DC (Allowable load resistance 600 or more)
Current output: 0 to 20 mA DC, 4 to 20 mA DC
(Allowable load resistance 600 or less)
High-speed AT type HA400/HA900 Instruction
Standard AT type HA401/HA901 Manual
Voltage output: 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
(Allowable load resistance 1 kor more)
Triac output: Allowable load current: 0.4 A Minimum load current: 30 mA
Load voltage: 75 to 250 V AC
Sensor power supply output (Optional) [Only OUT3 is selectable]:
Rated voltage: 24 V DC 5 % Rated current: 24 mA max.
Output 4 and Output 5:
Relay contact output: 250 V AC, 1 A (Resistive load), 1a contact
Electrical life: 300,000 times or more (Rated load)
Control method: Brilliant PID control (Direct action, Reverse action,
Position proportioning or Cascade is available)
A
llowable ambient temperature:
10 to 50 C (14 to 122 F)
A
llowable ambient humidity: 5 to 95 %RH
Absolute humidity: 29 g/m3dry air at 101.3 kPa
Operating environment: There should be neither corrosive gases nor much dust.
Weight: HA400/HA401: Approx. 360 g
HA900/HA901: Approx. 460 g
To prevent injury to persons, damage to instrument and equipment, a
suitable external protection device shall be required.
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals,
etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
!
WARNING
CAUTION
Mounting brackets: 2 (Waterproof/Dustproof type: 4)
Instruction Manual: 1 (IMR01N01-E8)
Product Check
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity,
magnetic fields or noise.
Direct air flow from anair conditioner.
Exposure to direct sunlight.
Excessive heat accumulation.
Power supply wiring must be twisted and have a low voltage drop.
This instrument with 24 V power supply is not provided with an overcurrent protection device.
For safety install an overcurrent protection device (such as fuse) with adequate breaking capacity
close to the instrument.
- Fuse type: Time-lag fuse (Approved fuse according CSA C22.2 No.248.14 or UL248-14)
- Fuse rating: Rated current: 1.0 A
For an instrument with 24 V power supply input, supply power from “SELV” circuit defined as IEC
60950-1.
A suitable power supply should be considered in end-use equipment. The power supply must be
in compliance with a limited-energy circuits (maximum available current of 8 A).
Use the solderless terminal appropriate to the screw size.
- Screw size: M3×6 (With 5.8×8 square washer)
- Recommended tightening torque: 0.4 N・m (4 kgf・cm)
- Specified solderless terminals: With isolation
- Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm2
Make sure that duringfield wiring parts of conductors can not
come into contact with adjacent conductive parts.
To prevent electric shock or instrument failure, always turn off the power
before mounting or removing the instrument.
!
WARNING
To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power
to the instrument.
!
WARNING
(4) Output 3
4
(Optional)
TC
TC 

24
23
RTD
RTD
B
B
A
24
23
22
A
21
Voltage/Current
24
23
IN 

(13) Measured input (1-input)
(6) Output 1 1
Relay contact
NO
OUT1
12
11
Voltage pulse/
Voltage/Current
OUT1

12
11
Triac
OUT1
12
11
(5) Output 2
1
OUT2
NO 10
9
Relay contact
Voltage pulse/
Voltage/Current
OUT2


10
9
Triac
OUT2
10
9
(4) Output 3
NO
OUT3
8
7
Relay contact
Voltage pulse/
Voltage/Current
OUT3


8
7
Triac
OUT3
8
7
(2) Output 5
3
Relay contact
3
4
OUT5
NO
(14) Measured input (2-input)
RTD
RTD2
B
B
A
21
20
19
A
B
B
22
24
23
RTD1
TC
TC1


21
20
24
23
TC2


Voltage/Current
IN2


21
20
24
23
IN1


In 2-input controller, input 1 and input 2 can be different
input types. Also, input 2 can be used as remote input
(Isolation type)
(3) Output 4
3
Relay contact
5
6
OUT4
NO
24V DC
Sensor
power supply
OUT3


8
7
3
When output 3 is used for a sensor
power supply (optional), outputs 4 and 5
are not available.
4Output 3 can be used as a power supply
(optional) for the transmitter (pressure
sensor, temperature sensor, etc).
(1) Power supply


24 V
DC
2
1
L
N
100-240 V
A
C
2
1
L
N
24 V
A
C
2
1
(9)Input 5
36
35
DI5
Contact
(10) Communication 1/Input (Optional)
RS-232C
RD
SD
SG
15
14
13
RS-485
T/R (B)
T/R (A)
SG
15
14
13
(11) Input 2
18
17
16
CT2
CT1
CT FBR
17
16
O
W
C
18
CT/PFF
18
17
16
PFF
CT1
(12) Input 2
Remote
20
19


(Optional
)
Contact
30
DI2
DI1
DI3
33
32
34
31
DI4
13
14
15
16
17
18
19
20
21
22
23
2
4
25
26
27
28
29
30
31
32
33
34
35
3
6
1
2
3
4
5
6
7
8
9
10
11
12
(1)
(2)
(3)
(4)
(5)
(6)
(8)(7) (9)
(10)
(11)
(12)
(13)
1-input controller
13
14
15
16
17
18
19
20
21
22
23
2
4
25
26
27
28
29
30
31
32
33
34
35
3
6
1
2
3
4
5
6
7
8
9
10
11
12
(1)
(2)
(3)
(4)
(5)
(6)
(8)(7) (9)
(10)
(11)
(14)
2-input controller
(7)Communication 2 (Optional)
RS-422A
R (A)
28
T (A)
26
SG
25
R (B)
29
T (B)
27
PROFIBUS
VP
DGND
28
RxD/TxD-P
26
25
27
RxD/TxD-N
RS-232C
RD
27
SD
26
SG
25
RS-485
T/R (B)
27
T/R (A)
26
SG
25
DeviceNet
CAN-L
28
V
25
V
29
26
CAN-H
27
Drain
CC-Link
SLD
28
DA
25
FG
29
26
DB
27
DG
1
OUT1 and OUT2 are not isolated from each otherexcept for relay or triac output.
2Remote input, CT input, PFF input and FBR input are not isolated between measured input.
CT: Current transformer input
PFF: Power feed forward input
FBR: Feedback resistance input
5 When the CC-Link communication
(optional) is specified, these
terminals are not available.
(Optional
)
(8)Input 5
RS
Contact
13
DI6
14
15
DI7
Fi
g
.1
Fi
g
.2
Fi
g
. 3


Front panel
frame
Pull out
Panel Fi
g
. 4

3.2 MIN

5.5 MA
X
4 mm
*1 Rubber (Optional) *2 Up to 4 mounting brackets may be used.
*3 If the HA400/HA401s or HA900/HA901s have waterproof/dustproof (optional), protection will be compromised and
not meet IP65 by close mounting.
*4 When controllers are closely mounted, ambient temperature must not exceed 50 °C (122 F).
For mounting of the HA400/HA401 or HA900/HA901, panel thickness must be between 1 to 10 mm.
When mounting multiple HA400/HA401s or HA900/HA901s close together, the panel strength should be checked to
ensure proper support.
25 45

0.6

0
30 0.8
0
92
Individual mounting
L = 48×n-3
n: Number of units (2 to 6)
0.8
0
92
L 0.6
0
Close mounting
*
3,
*
4
30 0.8
0
92
920.8
0
25
L = 96×n-4
n: Number of units (2 to 6)
0.8
0
92
L

0.8

0
Individual mounting Close mounting
*
3,
*
4
HA400/HA401
(Unit: mm)
11.1
10.1 100
(
1
)
*1
91.8
110.8 44.8
48
96
91.8
*2
96
96
HA900/HA901
11.1
10.1 100
(
1
)
*1
91.8
110.8
(Unit: mm)
The first edition: JUN. 2002 [IMQ00]
The eighth edition: FEB. 2012 [IMQ00]
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799)
E-mail: [email protected]
FAX: 03-3751-8585 (+81 3 3751 8585) MAY 2013
® RKC INSTRUMENT INC.
Modbus is a registered trademark of Schneider Electric.
DeviceNet is a registered trademark of Open DeviceNet Vender Association, Inc.
CC-Link is a registered trademark of Mitsubishi Electric Co. Ltd.
3. PARTS DESCRIPTION
(1) Area display
Area (AREA) lamp [Green] Lights when memory area number is displayed.
Memory area display Displays memory area number (1 to 16).
(2) Upper display
Measured value 1 (PV1) lamp [Green] Lights when measured value 1 is displayed on the PV1/PV2
display unit.
Measured value 2 (PV2) lamp * [Green] Lights when measured value 2 is displayed on the PV1/PV2
display unit.
Manual (MAN) mode lamp [Green] Lights when operated in manual mode.
Remote (REM) mode lamp [Green] Lights when remote setting function is activated.
Autotuning (AT) lamp [Green] Flashes when autotuning is activated.
(After autotuning is completed: AT lamp will go out)
Measured value (PV1/PV2) display Displays PV1, PV2 or various parameters’ symbols.
* This lamp is activated only with 2-input controller.
(3) Lower display
Measured value 2 (PV2) lamp * [Green] Lights when measured value 2 is displayed on the SV display unit.
Set value (SV) lamp [Green] Lights when set value (SV) is displayed on the SV display unit.
Manual (MAN) mode lamp * [Green] Lights when operated in manual mode.
Autotuning (AT) lamp * [Green] Flashes when autotuning is activated.
(After autotuning is completed: AT lamp will go out)
Set value (SV) display Displays SV, PV2 or various parameters’ set values.
* This lamp is activated only with 2-input controller.
(4) Output/Alarm lamp
Output (OUT1 to OUT5) lamp [Green] Lights when the output corresponding to each lamp is ON.
Alarm (ALM) lamp [Red] Lights when alarm (Event or HBA function) is turned on. The type
of alarm which is on can be checked on the event monitor display.
(5) Bar graph display *
One of the displays shown in the table below can be selected for the bar-graph.
Manipulated output value (MV)
display Displays the manipulated output value (MV). When manipulated output
value (MV) is at 0 % or less, the left-end dot of the bar-graph flashes.
When MV exceeds 100 %, the right-end dot at the right end flashes.
Feedback resistance input value
(POS) display Displays the feedback resistance input value (POS).
(Available with position proportioning PID control)
Deviation display Displays the deviation between the measured value (PV) and the set
value (SV). When the Deviation display is selected, the dots at both
ends of bar-graph light.
Measured value display Displays the measured value (PV). Scaling is available within the input
range.
Set value display Displays the set value (SV). Scaling is available within the input range.
*The number of dots: 10 dots (HA400/401), 20 dots (HA900/901)
(6) Direct key
Auto/Manual transfer key Switching the Auto/Manual control mode between Auto (PID control)
mode and Manual mode.
Remote/Local transfer key Switching the Remote/Local control mode between Remote control and
Local control.
RUN/STOP transfer key Switching the RUN/STOP mode between RUN and STOP.
(7) Operation key
Set (SET) key Used for parameter calling up and set value registration.
Shift key Shift digits when settings are changed. Used to selection operation
between modes.
Down key Decrease numerals.
Up key Increase numerals.
(8) Infrared port
Used when sending and receiving data between this controller and the PDA installed with the RKCIr software.
To avoid damage to the instrument, never use a sharp object to press keys.
4. OPERATION FLOW OF EACH MODE
In order to make this instrument operable after being mounted on equipment and then wired, it needs to be set with operating conditions such as the set value (SV), input/output function, control function, etc. specific to each customer. In addition, the following
operational flowchart illustrates key operation in each mode or each setting item. When actually setting these operating conditions specific to the customer, refer to the HA400/HA900/HA401/HA901 Operation Manual (IMR01N02-E).
(2)
(3)
(1)
(4)
(5)
(6)
(8)
HA400/HA401
OUT1 OUT2 OUT3 OUT4 OUT5 ALM
A
RE
A
PV2 MANREM
AT
S
V
PV1 PV2 MANREM
AT
MOD
E
SE
T
A
/M R/L R/S
(7)
(2)
(1)
(8)
(3)
(4)
(5)
(7)
HA900/HA901
AREA PV2 MAN REM ATSV
PV1 PV2 MAN
REM
A
T
SE
T
MODE
OUT1 OUT2 OUT3 OUT4 OUT5 ALM
A
/M R/L R/S (6)
A
/M
SE
T
MODE
R/L
R/S
[Example] 0 5
0
10
0
0 5
0
10
0
[Example]
0 
[Example]
Power ON Input type/Input range Display
Press the
shift key while
pressing the
SET key.
Press and hold the SET key for 2 seconds.
Press and hold the SET key for 2 seconds. Press the shift key while pressing the SET key.
Press and hold the shift key for
1 second.
Press the shift key while
pressing the SET key.
Press the shift key whil
e
pressing the SET key fo
r
2 seconds.
Operation of various functions
For the operation of various functions, refer to the HA400/HA900/HA401/HA901 Operation Manual
(IMR01N02-E).
For the communication function, refer to the following manuals.
HA400/HA900/HA401/HA901 Communication Instruction Manual [RKC communication/Modbus]
(IMR01N03-E)
HA400/HA900/HA401/HA901 PROFIBUS Communication Instruction Manual (IMR01N04-E)
HA400/HA900/HA401/HA901 DeviceNet Communication Instruction Manual (IMR01N05-E)
HA400/HA900/HA401/HA901 CC-Link Communication Instruction Manual (IMR01N20-E)
For an instrument with Z-1145 specification, refer to the following instructionmanuals.
HA400/HA900/HA401/HA901 Z-1145 Specification (IMR01N25-E)
For an instrument with Z-1151 specification, refer to the following instructionmanuals.
HA400/HA900 Z-1151 Specification (IMR01N27-E)
The above manuals can be downloaded from the official RKC website:
http://www.rkcinst.com/english/manual_load.htm.
Operation Mode
Input 1_PID/AT transfer
Input 2_PID/AT transfer
Input 1_Auto/Manual
transfer
Remote/Local transfer
RUN/STOP transfer
Return to Input 1_PID/AT transfer
In this mode, it is possible to selects the operation modes of the instrument.
SET key or Shift key
SET key or Shift key
SET key or Shift key
SET key or Shift key
SET key or Shift key
SET key or Shift key
Input 2_Auto/Manual
transfer
Parameter Setting Mode
In this mode, it is possible to set parameters relating to control such as PID constants, event set values, etc. Up to
16 individual sets of SVs and parameters in Parameter setting mode can be stored and used in Multi-memory area
function.
: Parameters related to
Multi-memory area function
Event 1 set value
LBA1 time
LBA1 deadband
Input 1_proportional
band for PI/PID
control
Input 1_integral time
for PI/PID control
Input 1_derivative
time for PID control
Input 1_control
response parameter
Return to first parameter setting
item of parameter setting mode
Event 2 set value
Event 3 set value
LBA2 time
LBA2 deadband
Event 4 set value
Input 2_control
response parameter
Input 1_setting change
rate limiter (up)
Input 1_setting change
rate limiter (down)
Input 2_setting change
rate limiter (up)
Input 2_setting change
rate limiter (down)
A
rea soak time
Link area number
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
Input 2_proportional
band for PI/PID
control
Input 2_integral time
for PI/PID control
Input 2_derivative
time for PID control
This instrument returns to the PV1/SV1 monitor screen if no key operation is performed fo
r
more than 1 minute.
Parameters whichare not related to existing functions onthe controller are not displayed.
(Except Engineering mode)
Turn off the power at once. If error occurs
after the power is turned on again, please
contact RKC sales office or the agent.
A
/D conversion error
EEPROM error
A
djusted data erro
r
Upper display
RAM check error
Watchdog timer error
Hardware configuration error
Software configuration error
Program busy
Lower display
Over-scale
Underscale
Input error Displays when the measured value (PV)
exceeds the input error determination poin
t
(high or low limit) or display range limi
t
(19999 to 99999). Check the sensor o
r
input lead.
*Input error determination point (high limit):
Input scale high (5 of input span)
Input error determination point (low limit):
In
p
ut scale low

(
5

of in
p
ut s
p
an
)
Measured
value (PV)
[Flashing]
[Flashing]
[Flashing]
Description Solution
Display of self-diagnostic error and overscale/underscale
When two or more errors occur simultaneously, the error code numbers are totaled and
displayed as one number.
Setup Setting Mode
SET key
HBA1 set value
Heater break
determination point 1
Heater melting
determination point 1
Input 2_digital filter
Input 2_PV ratio
Communication
speed 1
Data bit
configuration 1
Input 2_proportional
cycle time
Device address 1
(Slave address 1)
Device address 2
(Slave address 2)
Communication
speed 2
Data bit
configuration 2
Set lock level
Interval time 2
Return to first parameter setting item of Setup setting mode
In this mode, it is possible to set setting items not corresponding to the memory area, setting lock levels, etc.
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
Input 2_PV low input
cut-off
Input 1_digital filter
Input 1_PV ratio
Input 1_PV bias
Input 2_PV bias
Input 1_proportional
cycle time
SET key
SET key
SET key
SET key
SET key
Input 1_PV low input
cut-off
HBA2 set value
SET key
SET key
SET key
Heater break
determination point 2
Heater melting
determination point 2
Interval time 1
SET key
Infrared communication
address
nfrared communication
speed
SET key
SV Setting & Monitor Mode
: Parameters related to Multi-memory area function
SET key
PV1/SV1 monitor
PV2/SV2 monitor
PV1/PV2 monitor
Input 1_SV setting
Input 2_SV setting
Remote input value
monitor
Cascade monitor
Input 1_MV monitor
Input 2_MV monitor
Event monitor
CT1 monitor
CT2 monitor
Memory area
selection
Return to PV1/SV1 monitor
Memory area soak
time monitor
In this mode, it is possible to set SV which is the desired value for control and also to monitor PV, SV, MV, etc.
SET key
SET key
SET key
SET key
PV1 value
SV1 value
PV2 value
SV2 value
PV1 value
PV2 value
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
SET key
Feedback resistance
input value monitor
SET key CC-Lin
k
communication status
Engineering Mode
In this mode, it is possible to set operating conditions such as the Input/Output
function, control function, etc. specific to each customer. For details, refer to
HA400/HA900/HA401/HA901 Operation Manual (IMR01N02-E).
Press the shift key while pressing the SET key.
Return to PV1/SV1 monitor of SV setting & Monitor mode

Other manuals for HA400 Series

3

This manual suits for next models

3

Other RKC INSTRUMENT Controllers manuals

RKC INSTRUMENT CB100 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT CB100 Series User manual

RKC INSTRUMENT THV-10 User manual

RKC INSTRUMENT

RKC INSTRUMENT THV-10 User manual

RKC INSTRUMENT HA400 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT HA400 Series User manual

RKC INSTRUMENT CB100 Series Manual

RKC INSTRUMENT

RKC INSTRUMENT CB100 Series Manual

RKC INSTRUMENT THW-3 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT THW-3 Series User manual

RKC INSTRUMENT CB Series Instruction manual

RKC INSTRUMENT

RKC INSTRUMENT CB Series Instruction manual

RKC INSTRUMENT MA900 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT MA900 Series User manual

RKC INSTRUMENT THV-1 User manual

RKC INSTRUMENT

RKC INSTRUMENT THV-1 User manual

RKC INSTRUMENT HA430 User manual

RKC INSTRUMENT

RKC INSTRUMENT HA430 User manual

RKC INSTRUMENT CB100 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT CB100 Series User manual

RKC INSTRUMENT SA100L User manual

RKC INSTRUMENT

RKC INSTRUMENT SA100L User manual

RKC INSTRUMENT CD101 User manual

RKC INSTRUMENT

RKC INSTRUMENT CD101 User manual

RKC INSTRUMENT CB100 Series Manual

RKC INSTRUMENT

RKC INSTRUMENT CB100 Series Manual

RKC INSTRUMENT HA400 Series Use and care manual

RKC INSTRUMENT

RKC INSTRUMENT HA400 Series Use and care manual

RKC INSTRUMENT CB103 User manual

RKC INSTRUMENT

RKC INSTRUMENT CB103 User manual

RKC INSTRUMENT REX - C100 Manual

RKC INSTRUMENT

RKC INSTRUMENT REX - C100 Manual

RKC INSTRUMENT CB100L Manual

RKC INSTRUMENT

RKC INSTRUMENT CB100L Manual

RKC INSTRUMENT SRZ User manual

RKC INSTRUMENT

RKC INSTRUMENT SRZ User manual

RKC INSTRUMENT FB900 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT FB900 Series User manual

RKC INSTRUMENT SA200 Series User manual

RKC INSTRUMENT

RKC INSTRUMENT SA200 Series User manual

RKC INSTRUMENT REX-C100 User manual

RKC INSTRUMENT

RKC INSTRUMENT REX-C100 User manual

RKC INSTRUMENT FB400 Series Use and care manual

RKC INSTRUMENT

RKC INSTRUMENT FB400 Series Use and care manual

RKC INSTRUMENT THV-10 User manual

RKC INSTRUMENT

RKC INSTRUMENT THV-10 User manual

RKC INSTRUMENT CB103 Manual

RKC INSTRUMENT

RKC INSTRUMENT CB103 Manual

Popular Controllers manuals by other brands

Leica CS10 user manual

Leica

Leica CS10 user manual

Bogen UTI312 Specifications

Bogen

Bogen UTI312 Specifications

National Instruments NI SMD-7613 user manual

National Instruments

National Instruments NI SMD-7613 user manual

Kobold ACM-1 operating instructions

Kobold

Kobold ACM-1 operating instructions

Pilz PNOZ mm0.2p operating manual

Pilz

Pilz PNOZ mm0.2p operating manual

DeVilbiss DVFR-4 Operation manual

DeVilbiss

DeVilbiss DVFR-4 Operation manual

Seg System A2 H15 General information

Seg

Seg System A2 H15 General information

Vivo DESK-V103E instruction manual

Vivo

Vivo DESK-V103E instruction manual

AWELCO THOR 750 manual

AWELCO

AWELCO THOR 750 manual

DROPSA ADVANCED LUBRICATION CONTROLLER INSTRUCTION AND PRODUCT DATA SHEET

DROPSA

DROPSA ADVANCED LUBRICATION CONTROLLER INSTRUCTION AND PRODUCT DATA SHEET

Mach M20.06 user manual

Mach

Mach M20.06 user manual

Carel ir33+ quick start guide

Carel

Carel ir33+ quick start guide

Tusa PLATINA R-100 Technical manual

Tusa

Tusa PLATINA R-100 Technical manual

Extron electronics MLC 206 Backlight Replacement Guide

Extron electronics

Extron electronics MLC 206 Backlight Replacement Guide

Satel ACU-280 manual

Satel

Satel ACU-280 manual

Dynamite DYNM3865 instruction manual

Dynamite

Dynamite DYNM3865 instruction manual

ATC A-52 Series user manual

ATC

ATC A-52 Series user manual

Brama S-A1 user guide

Brama

Brama S-A1 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.