RMS 4M300 Service manual

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 1/6
Features
◼Colour coded ‘finger safe’ test
sockets suit standard or
shrouded type 4mm banana
plugs
◼14 independent circuits suitable
for CT or VT connections
◼Test plug available with
automatic CT shorting option
◼Test plug fitted with insertion
handles & locking screws
◼Side label instructions on
changing from normal service
condition to the test condition
◼Optional automatic DC auxiliary
isolation function
◼High current / voltage rating
◼Compact & economic design
◼Made in Australia
Application
Test links are an important accessory for
protection, metering & control panels.
They enable test technicians to quickly &
safely isolate protection relays so that test
signals may be injected & system
performance verified.
There are a number of advantages in
performing injection tests at the protection
relay panel:
◼Reduction in down time of the
equipment under test.
◼Testing does not cause
disturbance to wiring, terminals
or equipment settings.
◼Existing auxiliary supply to the
equipment under test may be
isolated.
The 4M300 Test Link Panel has been
designed as a general-purpose isolation &
test signal injection point. Standard 4mm
diameter sockets are employed so that
common banana plugs may be used to
short CT inputs & connect test equipment.
Equipment under test need only be
removed for servicing if problems are
detected.
Technical Bulletin 4M300
Test Block System
Figure 1:
4M320-A Test Plug
Description Made in Australia
The Test Block type 4M300 comprises fourteen (14) test circuits, each of which is connected
to a separate pair of terminals at the rear of the case. During the normal operation of the
associated protection equipment, each pair of terminals are connected together by a circuit-
shorting link. Changing the 4M300 Test Block from the normal service condition to the test
condition is described below & depicted in figure 3:
Test Circuit Access
Access to the circuits, for testing purposes, is gained by first removing the front cover. For the
4M300-B model the Isolation Plug is withdrawn & the circuit between terminals 13 & 14
interrupted. By routing the main DC supply to the protection scheme or relay through this
circuit, removal of the Isolation Plug will thereby prevent inadvertent tripping of the protection
during the ensuing tests.
Test Plug Insertion
Insertion of the Test Plug type 4M320, isolates the live side circuits from the equipment side.
The Test Plug carries 28 4mm ‘finger safe’ test sockets. These sockets are suitable for
shrouded or standard 4mm banana plugs. Each test socket is identified by a number, which
corresponds to the numbered terminal on the rear of the case when the Test Plug is inserted.
The test socks are colour coded - BLACK to indentify the equipment side sockets & YELLOW
to identify the live side sockets.

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 2/6
RECOMMENDED WIRING LAYOUT
It is recommended that the Test Block is always wired with
connections to the protective relay or scheme made to the EVEN
numbered equipment side terminals. Connections to other
equipment, e.g. CT’s , VT’s & DC supplies, should be made to the
ODD numbered live side terminals on the Test Block. This ensures
that when the Test Plug is used, the BLACK sockets of the Test
Plug are the isolated relay circuits & the YELLOW sockets on the
Test Plug are connected to the potentially live supplies as shown in
figure 8.
Test equipment can be connected to the relay or scheme using the
BLACK sockets in the Test Plug, & operation of contacts can be
monitored. When using the 4M300-B Test Block, the DC supply
may be used during testing by linking across sockets 13/14 &
15/16 of the Test Plug.
Operation
CT SHORTING –MANUAL (External)
It is essential that the sockets of the 4M320 Multi-Finger Test Plug
which correspond to the current transformer (CT), secondary
windings are linked prior to the test plug being inserted into the test
block. This ensures that the current transformer secondary
windings are not open circuited when they are isolated from the
protection relay scheme.
This may be achieved using external shorting links to ensure that
the CT secondary windings are short circuited before they are
disconnected from the protection relay or scheme, thereby
avoiding dangerously high voltages.
The continuity of the shorting plug / wire links & their state of
insulation should be checked prior to into the 4M300 test block.
CT SHORTING –AUTOMATIC (Internal)
The 4M320 may be ordered with internal CT shorting links fitted to
pre-designated positions as follows:
4M320-B Internal links between terminals 21-23-25-27
Refer figure 8
Where these 4M320 test plug versions are employed it is essential
that the CT circuits are wired to the 4M300 test block in the
matching positions.
To Reiterate: The 4M320 requires the USER to ensure that the
necessary shorting links - manual or automatic –are
fitted prior to plugging into the 4M300 test block.
TEST LEAD INSERTION
Before use the insulation of the flying leads should be visibly
checked for damage.
Flexible banana test leads with shrouded plugs are recommended
for operator safety. 2.5mm2multi-strand wire with PVC insulation is
recommended for adequate current rating and flexibility.
TEST PLUG INSERTION
To avoid high voltage shock hazard external CT circuits must NOT
be open circuited. Shorting links must be in position BEFORE test
plug insertion.
Insertion of the 4M320 connects the live side circuits to the
YELLOW test sockets on the front panel. The equipment side
circuits are connected to the BLACK test sockets on the front
panel. Each test socket is identified by a number, which
corresponds to the numbered terminal on the rear of the case
when the Test Plug is inserted.
FINGER SAFE TEST SOCKETS
BLACK - even numbered - equipment side sockets
YELLOW - odd numbered - live side sockets
Figure 2: Close up view of the ‘finger safe’ test plug sockets that
accept standard 4mm shrouded test plugs
!

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 3/6
Figure 3 Operation
Changing the 4M300 Test Block system from the normal service
condition to the secondary injection test condition is achieved in
three steps shown in figure 3 below:
TOP VIEW
REAR VIEW
Shown with isolation plug fitted to short terminals 13 & 14 (4M300-B model only)
NORMAL SERVICE CONDITION
SECONDARY INJECTION TEST CONDITION
Circuit isolating bar not yet engaged
4M320 terminals touch
Automatic CT shorting engaged
Circuit isolating bar engaged
Equipment side circuits isolated from live side circuits
WITHDRAW DC AUXILIARY ISOLATION PLUG (4M300-B model only)
DC auxiliary supply link between terminals 13 & 14 is removed
Step 1 - DC AUXILIARY SUPPLY ISOLATION
Step 2 - AUTOMATIC CT SHORTING
Step 3 - CIRCUIT ISOLATION
Auxiliary supply isolated - 4M300-B
CT shorting links engaged
INSERT 4M320[B] TEST PLUG
Automatic shorting of CT's wired to terminals 22, 24, 26 & 28
4M320[B] Test Plug fully inserted
4M300-B Test Block Terminal Status
Other
ODD
terminals
LIVE
SIDE
13
13
13
13
21
21
21
21
23
23
23
23
25
25
25
25
27
27
27
27
Other
EVEN
terminals
EQUIPMENT
SIDE
14
14
14
14
22
22
22
22
24
24
24
24
26
26
26
26
28
28
28
28
All circuits isolated
4M320-A Manual
4M320-B Automatic
Equipment side & live side
contacts shorted

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 4/6
Single plug Plug +
spare socket
Figure 4: Two ended test lead - short
P/N 310-230-075-1 75mm wire length version depicted
Single plug Plug +
spare socket
Figure 5: Two ended test lead - long
P/N 310-230-180-1 180mm wire length version depicted
Test Leads
SHROUDED TEST LEADS
Two types of shrouded ‘finger safe’ test leads are available:
Part Number
Description
Quantity
supplied per
4M320
310-230-075-1
Two ended test lead - 75mm
3
310-230-180-1
Two ended test lead - 180mm
3
Wire type: 2.5mm2multi-strand wire with yellow PVC insulation
TEST LEAD PLUGS
Two types of shrouded plug are employed on each test lead as
depicted in figure 4 & 5.
Single Plug
The single plug is the most compact & may be plugged into any
test socket.
Dual Plug
The dual or ‘piggy back’ plug is larger & should be plugged into the
test sockets on the outside edge of the 4M320. The lead emerging
from the dual plug should face out from center of the 4M430 to
ensure adequate clearance for other plugs.
CONNECTING MULTIPLE TEST LEADS
Test leads may be linked in a daisy chain arrangement to perform
manual CT shorting as described on page 2. Three (3) leads are
required to short a group of four (4) CT circuits as follows:
1. Connect the first lead between sockets 21-23
2. Connect the second lead between sockets 25-27
3. Connect the third lead to link the dual plugs in sockets 21-25
An additional lead may be fitted into the third lead dual plug for a
ground connection where required.

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 5/6
Figure 6
4M300-B Test Link Plug
Depicted in the normal service condition
with the isolation plug installed
Technical Data
4M300-A TEST BLOCK (Isolating Plug not fitted)
14 Equipment side terminals (Even terminal numbers).
14 Live side terminals (Odd terminal numbers).
14 Live side to equipment side shorting links.
This arrangement provides for up to 14 independent circuits to be connected.
An isolating circuit is not provided on this model.
4M300-B TEST BLOCK (Includes Isolating Plug)
14 Equipment side terminals (Even terminal numbers).
14 Live side terminals (Odd terminal numbers).
13 Live side to equipment side shorting links.
1 Isolating circuit between terminals 13 & 14
This arrangement provides for up to 12 independent circuits to be connected.
An additional DC auxiliary circuit is provided with an isolating link across terminals 13
&14. This circuit is automatically opened when the Isolation Plug is removed.
4M320 TEST PLUG
28 test sockets suitable for 4mm banana plugs.
Securing screws to retain the Test Plug during testing operations.
CURRENT RATINGS
All CT circuits & terminals: 20A continuous
(Terminal 1 to 28) 400A 1s
VOLTAGE RATINGS
All circuits & terminals: 600V AC continuous
320V DC continuous
System auxiliary voltage: 40V DC minimum
CASE TYPE
2M28 Size 2 28 terminals
COMPLIANCE STANDARDS
IEC 60068-2-1, 60068-2-2, 60068-2-78
IEC 60255-1, 60255-21-1, 60255-21-2, 60255-21-3, 60255-27
IEC 60529
IEC 60947-1, 60947-7-1
INSULATION WITHSTAND
All Models
2KV AC RMS for 1 min: . between all terminals & all terminals & case.
1.2/50μs 5KV impulse between any contact pair and either adjacent contact pair. All
terminals and case.
4M300-B Test Block & 4M320 Test Plug only
1KV AC RMS for 1 min. between terminals 13 & 14 when the isolation plug is removed.
TEMPERATURE
Operating range: -10 to +55 oC
Storage range: -25 to +70 oC
HUMIDITY
Operating range: 40°C and 93% relative humidity non-condensing
IP RATING
Installed: IP5x (from front with cover fitted)
Front view
2 holes of 3.7
Side view
4M300
Test Block & draw out
Isolating Plug
Terminal layout Panel cut out
Size 2M case suits
flush panel mounting &
4U high 19 inch rack frame
217
2M28-S Short case version (Order code A)
235
2M28 Long case version (Order code B)
Figure 7: Case details

Visit www.rmspl.com.au for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 4M300/Issue K 10/08/21 - 6/6
Generate the required ordering code as follows: e.g. 4M300-BA
1
2
4M300
TEST BLOCK (SOCKET)
1
AUXILIARY SUPPLY ISOLATING LINK
A Not required (Isolation Plug not supplied)
B Required (Test Block supplied with Isolation Plug)
2
CASE LENGTH (Match to 4M320 case length)
A Short Default
B Long
Ordering Information
Generate the required ordering code as follows: e.g. 4M320-BA
1
2
4M320
TEST PLUG
1
CT SHORTING LINKS
A Manual (External links to be fitted by operator)
B Automatic (Internal links fitted between terminals
21, 23, 25 & 27)
2
CASE LENGTH (Match to 4M300 case length)
A Short Default
B Long
TYICAL APPLICATION OF 4M300 TEST BLOCK & 4M320 TEST PLUG
4M300 Test Block
(REAR VIEW)
Live side
sockets
YELLOWBLACK
Equipment
side sockets
*
*
Apply secondary injection test signals
Trip & alarm
contacts or
VT connections
as required
Relay scheme
DC auxiliary
Protection scheme
1
3
5
7
9
11
13
15
17
19
21
23
25
27
2
4
6
8
10
12
14
16
18
20
22
24
26
28
S2
S2
S2
P1 P2
S1
S1
S1
A
B
C
Figure 8: Typical use of 4M300 Test Block & 4M320 Test Plug
4M300-A Terminals 13/14 connected as per other positions
4M300-B Terminals 13/14 open circuit when Isolation Plug removed
Phase A
Phase B
Phase C
E/F
DC
auxiliary
4M320-A Manual
4M320-B Automatic
CT shorting links:
Heavy
duty
current
injection
sockets
4M320 Test Plug
(FRONT VIEW)
Fit external
links 13-14
& 15-16 if
station DC
auxiliary
is required
during
testing
1
5
9
17
21
25
3
7
11
19
27
23
2
6
10
14
18
4
8
12
16
20
24
26
28