
17
Merlin IV Service and Parts Manual
Section 2. Vender Component Explanation
REFRIGERATION SYSTEM
The vender’s refrigeration system is responsible for the
cooling of the cabinet and the products loaded within
it. The refrigeration system comes as a completely
sealed unit and should never be cut or tapped into, or the
warranty will be voided.
OPERATION REQUIREMENTS: The refrigeration
system requires 115 volts AC from the main wiring
harness for it to operate. The main wiring harness will get
its voltage for the unit from the refrigeration relay.
HEALTH SENSOR OPERATION (if enabled): The
rising temperature in the cooling compartment is reported
to the control board by the temperature sensor. At power
up, the controller will check for the temperature. If the
temperature is above 41°F (5°C), the vender will display
“Out of Order.” Once the “hS” error has been cleared, a
30-minute timer will begin. At the end of this 30 minutes,
the vender will stay in normal operating mode as long
as the temperature remains 41°F (5°C) or below. If the
vender is 41°F (5°C) or below at power up, the vender
will stay in normal operating mode. If the door is open
after power up and the temperature is 41°F (5°C) or below
and stays at 41°F (5°C) or below, a 30-minute timer will
start after the door is closed. If the temperature is above
41°F (5°C) after 30 minutes, the vender will display “Out
of Order.” Any time the vender is in a normal operating
mode and the temperature reaches above 41°F (5°C),
a 15-minute timer will start. If after 15 minutes the
temperature remains above 41°F (5°C), the vender will
display “Out of Order.”
REFRIGERATION COMPONENTS: The refrigeration
system is a sealed system. Described in this section
are explanations of the refrigeration system’s major
components.
Compressor - The compressor is an hermetically-sealed
unit located beneath (outside) the cooling compartment.
The compressor is a pump, driven by the compressor
motor which draws low-pressure vapor (refrigerant) from
the evaporator coil, compresses it, and forces it into the
condenser under high pressure. The motor is started and
controlled by the refrigeration relay.
Condenser - The condenser is located beneath (outside)
the cooling compartment next to the compressor. It
can be seen from the front with the door open. The
condenser removes heat from the high-pressure vapor
discharged from the compressor and condenses it to a
high-pressure liquid. The condenser and evaporator coils
have aluminum fins attached to effectively increase heat
exchange surfaces.
Starting Relay - The starting relay is mounted on the side
of the compressor housing. The compressor motor has
two windings (start winding and run winding). To give
the motor torque when it first starts, the starting relay
switches in the additional start winding. After the motor
gets up to speed, the relay opens the start winding and the
motor continues using only the run winding.
Thermal Overload - The thermal overload is a heat-
sensitive device mounted on the side of the compressor
housing. If the compressor motor gets too hot or draws
an excessive amount of current, the thermal overload
will open, breaking the circuit to the compressor. After
the compressor cools to a safe operating temperature, the
thermal overload will close, allowing the compressor and
condenser fan motors to restart.
Condenser Fan and Motor - The condenser fan and motor,
located beneath the cooling department, are a forced-air
device using outside ambient air to cool the surface of the
condenser coil. The condenser fan and motor run while
the compressor operates.
Evaporator Coil - The evaporator coil is located in the
cooling compartment. As low pressure liquid passes
through the evaporator coil, it absorbs and removes
heat from the compartment as it changes to vapor. The
condenser and evaporator coil have aluminum fins
attached to effectively increase their heat exchange
surfaces.