S&P INITIA 225 User manual

INITIA 225
EN
Installation manual and switching on

Contents
1. General information
2. Technical information
3. Installation
4. Characteristics and electrical connections
5. Verification of the INITIA
6
Switching on the INITIA
6
.
Switching
on
the
INITIA
f ff
Be
f
ore undertaking any work, turn o
ff
and disconnect the machine.
During normal operation, never stop the ventilation system.

1- General information
Balanced mechanical Supply and Extract ventilation with high-efficiency heat
exchanger
1
1
Introduction
1
.
1
Introduction
This manual is intended for the use of INITIA 225 and its peripherals (ductwork, vents, controllers).
It is designed to provide clear and safe guidance for the design, installation and use of the product.
The products are constantly evolving and so, Soler & Palau reserves the right to modify this manual
without prior notice.
1.2 Warranty and Liability
Warranty
The INITIA 225 heat recovery system has a three year warranty from the date of purchase. This warranty
includes free delivery of necessary spare parts.
The warranty does not cover:
Installation and removal costs
Defects that, in the opinion of Soler & Palau, are due to improper installation, handling, neglect or
accidental
damage
accidental
damage
.
Those defects that arise as a result from operations or repair performed by a third party without
permission from Soler & Palau.
To return a defective part, the user should contact their installer.
Liability
INITIA 225 is designed for ventilation systems in individual dwellings.
Sole
r
& Palau is not responsible fo
r
damage caused by:
• Improper use,
• Normal wear of components,
• Failure to follow the instructions in this manual concerning safety, use and installation
• The use of parts not supplied by Soler & Palau.
1
3
Safety
1
.
3
Safety
General health and safety standards
Following installation, there should be no risk to safety, health and the environment according to EC
directives. This also applies to other products used in the installation.
The following general guidelines are important:
Follow the safety instructions to prevent injuries and damage to the motor fans.
The technical characteristics described in this manual may not be changed.
The motorised fans must not be modified.
The motorised fans must be supplied with a single phase AC supply of 230 V / 50 Hz.
So that the installation complies with EC directives, the INITIA 225 must be connected to the electricity
grid according to current standards.
The device must be installed so that under normal operating conditions, there is no risk of contact with
moving parts and power.
The
INITIA
225
meets
legal
requirements
for
electrical
equipment
The
INITIA
225
meets
legal
requirements
for
electrical
equipment
.
Before working on the machine, always turn the power off.
Use appropriate tools.
Use the machine only for the purpose for which it is intended

2 Technical information
2.1 General information
The INITIA 225 ensures optimum ventilation of a house with a maximum energy recovery. It draws air
from the rooms (bathroom(s), toilet, kitchen and wash room(s)) and supplies fresh air through the main
rooms (living room, bedroom (s), office, etc ).
The
fresh
and
extract
air
flows
are
separated
and
filtered
Only
heat
energy
is
transferred
to
the
fresh
air
The
fresh
and
extract
air
flows
are
separated
and
filtered
.
Only
heat
energy
is
transferred
to
the
fresh
air
introduced. Thanks to the high-efficiency heat exchanger used in the INITIA 225 performance can reach
95%.
Condensation forms during the heat exchange process and is recovered in the condensate tray, which
must be connected to a waste water drain.
The INITIA has a 100% heat exchanger bypass system and this allows the introduction of fresh air at
night without it being heated by contact with warm air accumulated in the house during the day. The
system operates automatically or can be used manually (see section 5-2).
2.2 Description of the INITIA
Fresh air Fresh air input Stale extract air Exhaust air
Control unit
D 160/150mm
Filter access hatches

Fresh air intake
This spigot is to connect the supply duct of fresh air from outside.
To prevent condensation it is recommended to use insulated ducts.
Install the fresh air intake (wall or roof) a sufficient distance from any area of high
pollution (trees, exhaust fumes, road, etc).
This duct must be sealed and insulated to prevent condensation on the outside
and inside.
Blowing fresh air into the house:
This spigot is for connecting the duct for blowing warmed fresh air into the house.
T
id
ht
l
th
dt
h ld
b
i ltd
d
th h
th
h td
T
o avo
id
h
ea
t
l
oss,
th
e
d
uc
t
ss
h
ou
ld
b
e
i
nsu
l
a
t
e
d
an
d
pass
th
roug
h
th
e
h
ea
t
e
d
area.
Stale air extract from the house:
This spigot is for the connection of the exhaust air duct from the house.
To
avoid
heat
loss
and
to
optimise
the
best
performance
of
your
system
ducts
To
avoid
heat
loss
and
to
optimise
the
best
performance
of
your
system
,
ducts
should be insulated and pass through the heated area.
Exhaust:
This spigot is to connect the exhaust duct for the exhaust air from inside the
house towards the outside.
This duct must be sealed and insulated to prevent condensation on the outside
and inside.
By-pass:
By leaving out the heat exchanger, the INITIA 100% bypass system allows the
i t d ti
f
fh
i
t
i ht
ith t
it
bi
h td
b
tt
ith
ht
i
i
n
t
ro
d
uc
ti
on o
f
f
res
h
a
ir
a
t
n
i
g
ht
w
ith
ou
t
it
b
e
i
ng
h
ea
t
e
d
b
y con
t
ac
t
w
ith
h
o
t
a
ir
accumulated in the house during the day. This system also works manually (see
section 5-2).
Operation without
the bypass Operation with
the bypass

2.3 Dimensional characteristics:
2.3-a Main unit:
Weight: 41 Kg:
2.3-b Timer:
75x75

Wall mount
3 Installation
3.1 Vertical wall:
>300
Uninsulated
duct
InsulatedductInsulatedduct
Ducts must be insulated and
perfectly inserted
3.2 On the ground:
It is advisable to install the INITIA in the
heated area of the house. If not, it is
essential to isolate the condensation
drain.

3.3 On level ground: Specific optional kit (foot and condensation drain)
Calle
DO NOT INSTALL THE INITIA IN A CEILING
Conduit non
isolé
Conduit isolé Conduit isolé
• It is advisable to install the INITIA in the heated area of the house. If not, it is essential to
isolate the condensation drain.
•Ducts must be insulated and perfectly inserted
DO
NOT
INSTALL
THE
INITIA
IN
A
CEILING
Adjustable cover caps (optional):
4x
4x

SAMPLE “DISTRIBUTION” ASSEMBLY
Kitchen
CPR or CT
150
Bathroom
installations
BDO or BOAP
125
BDO or TPM
80
Bathroom
installations
7 spigot distribution
Gable air vent D150
L /li i
Or
PAF 150
L
ounge
/li
v
i
ngroom
& Bedrooms
Or
Or
Roof air vent D150 4 or 8 spigots
distribution
When using
insulated flexible
insulated
flexible
duct, it is
imperative to
correctly tense it.

SAMPLE“DISTRIBUTION”ASSEMBLY
CT 150
CT
150
Lounge/Living room
BDOP 125
Kitchen
BDOP 125
BDOP D80
+
+
RD80
Bedrooms
Bathrooms
BAR
+
Bathrooms
Gable air vent D150
BDOP D80
+
RD80
+
Or
PAF 150
Or
Or
When using
insulated flexible
duct, it is
imperative to
correctly tense it.
Roof air vent D150

4 Characteristics and electrical connections
Connect the supplied cable to the mains using a sealed connection box.
Cable type H05VV-F-5G1 Power distribution box
Lenght 1.2 m
Connection box
Câblageavecfonctionrafraîchissementnocturne
Power: Single phase 230V-50Hz
Electrical protection:3A
Max. Power:230 W
Maximum ambient temperature:50ºC
Maximum flow temperature:45ºC
Do not turn on the unit the ventilation system is complete (air intake, discharge grille
or roof outlet, air and extraction vents, network and filters installed)
After switching on the INITIA unit, make necessary adjustments to the installation
(see Chapter 6)
(see
Chapter
6)
.

5 Verification of the INITIA
5.1 etting the operating speeds.
The INITIA has 3 operation speeds controlled by three adjustable potentiometers on the control unit (1).
1
Flow rates depend on the configuration of the house, depending on the number of main rooms (living
room, dining room, bedroom, office, etc) and the number and type of service rooms (bathroom, toilet,
laundry, etc), and the surface area.
Open
the
unit
and
set
according
to
the
configuration
of
the
house
each
potentiometer
as
shown
in
the
Open
the
unit
and
set
,
according
to
the
configuration
of
the
house
,
each
potentiometer
as
shown
in
the
table below.
Potentiometer 1 = Low speed setting
Potentiometer 2 = High speed setting
Potentiometer
3
=
Night
cooling
setting
Potentiometer
3
Night
cooling
setting
France
Cuisine SdB1 SdB2WC1 WC2 Séjour Ch1 Ch2 Ch3 Ch4
M ini M axi Raf rai.
Poten.
1
Poten.
2
Poten.
3
TypeT2 x x ‐xx xx‐‐‐ 75 135 150 001
INSUFFLATION Adjustment
Typede
logement
EXTRACTION Flowrate
xx‐x‐x xx ‐‐ 90 150 180 113
xx‐x x x xx ‐‐105 165 180 223
x xxx‐x xx ‐‐120 180 180 333
x x x x x x xx ‐‐135 195 180 443
xx‐x‐x xxx ‐105 180 210 235
x xxx‐x xxx ‐135 210 210 455
x x x x x x xxx ‐135 210 210 455
TypeT3
TypeT4
xx‐x x x x x x x 105 195 225 246
x xxx‐x x x x x 120 210 225 356
x x x x x x x x x x 135 225 225 466
TypeT5et
+

Other countries:
Poten.
1
Débit
V1
Poten.
2
Flow
rate
V2
Poten.
3
Flow
rate
V3
075 0135 0135
1
90
1
150
1
150
Réglagepotentiomètres/Débits
For
example
:
1
90
1
150
1
150
2105 2165 2165
3120 3180 3180
4135 4195 4195
5150 5210 5210
6165 6225 6225
For
example
:
Mini calculated flow rate = 105m3/h
→Potentiometer 1 / Position 2
Max flow calculated = 180 m3/h
→Potentiometer 2 / Position 3
Cool air flow (by way of example; there is no specific
regulatory rate) = 225 m3/h
3
5.2 Control unit operation:
→Potentiometer 3 / Position 6
2
6
1
5
• Turning on the bypass:
Manually activate the bypass by pressing the icon (1). The bypass is activated for 8 hours.
The operation is indicated by the green LED (2).
This can be turned off at any time by pressing the icon
4

• Clogged filters alarm (3):
When the filters are clogged, a red LED (4) appears to warn you to change the filters.
Remove the filter covers (F1= Filter F5 on intake network or F2= Filter G4 on extraction
network).
• Display of automatic defrost (7).
The INITIA has an automatic high-performance, efficient defrosting system.
The s
y
stem automaticall
y
o
p
erates before the tem
p
erature on the extraction ductwork and
Once the filters have been changed, press the icon to reset (LED goes off).
y yp p
downstream of the exchanger goes negative. Air intake is reduced. In case of
extremely low temperatures air intake may stop. When the temperature returns to positive,
intake flow returns to 100%.
In regions where temperatures are consistently negative and can drop below -10 º C, it
is advisable to install a preheating coil.
6 Switchin
g
on the INITIA
is
advisable
to
install
a
preheating
coil.
g
Tostartyourinstallation,usethefollowingprocess:
1. Verifythatallsystemcomponentsarecorrectlyinstalledandconnected:
•Freshairintakeductinsulatedandconnectedcorrectly(Donotuseafreshairintakeequippedwith
insectscreen)
•Freshairandexhaustductsinsulatedandconnectedcorrectly
•
Fresh air and exhaust vents connected
•
Fresh
air
and
exhaust
vents
connected
•Flowregulatorsmountedintherightdirection(ifinstalled)
•Airoutletusinginsulatedductandconnectedtotheoutside(Usingaroofcowloroutletwithoutan
insectscreen)
•Insulatedflexibleductstautandlargeradiusbends(ifinstalled)
•Checkthattheunusedspigotsonplenumsaresealed(ifinstalled)
•Condensationdrainwellconnected(siphon)
•
Check that all connections are sealed (on the
Initia
on plenums and vents)
Check
that
all
connections
are
sealed
(on
the
Initia
,
on
plenums
and
vents)
•Checkthesettingofthepowercircuitbreaker(3A)
2. TurnontheINITIA
3. Adjusttheminimumflowrate(Potentiometer1),themaximumflow(Potentiometer2)andrefreshrate
(Potentiometer3).


Ref. 902 32 030 30
S&P Sistemas de Ventilación S.L.U.
C/ Llevant, 4
08150 Parets del Vallès (Barcelona)
Tel. +34 93 571 93 00
Fax +34 93 571 93 01
www.solerpalau.com
Table of contents
Other S&P Fan manuals

S&P
S&P TD SILENT Series User manual

S&P
S&P Compact Sp Series Operation manual

S&P
S&P ECOWATT PLUS CRHB 400 N User manual

S&P
S&P TDM-100 Installation instructions

S&P
S&P SILENT-100 DESIGN Manual

S&P
S&P HR100V Assembly instructions

S&P
S&P decor-100 DC User manual

S&P
S&P TD SILENT User manual

S&P
S&P SILENTUB Series User manual

S&P
S&P DECOR-200 S User manual