S&P PCD110M User manual

VENTILATION FAN
WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
Model: PCD110M
CAUTION
CLEANING & MAINTENANCE
OPERATION
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting
brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the
motor with the exact service motor. The impeller should also be replaced.
-
+-
+1 2 3
1 2 3
Toggle
switch
Power box
Low airflow
knob
Timer delay
knob
2 function wall control switch for fan and LED night light control respectivtly
80 90 110 120 90 110 120 140
1 2 31 2 31 2 31 2 31 2 31 2 31 2 31 2 3
6"
Switch
position
Duct
diameter
(inches)
Airflow
(CFM)
6"
6"
6"4"4"4"4"
80 90 110 120 90 110 120 140
1 2 31 2 31 2 31 2 31 2 31 2 31 2 31 2 3
6"
Switch
position
Duct
diameter
(inches)
Air deliver
(CFM)
6"
6"
6"4"4"4"4"
is the position of switch
Other airflow reference performance based on HVI
Procedures 915, 916, and 920.
Factory setting: 110CFM ( )
HVI Certified performance based on HVI Procedures 915,
916, and 920.
The control box, located inside the fan housing, has three separate
adjustments:
(1) The low airflow knob adjusts the lower airflow from 30CFM up to
the air flow rate of the high fan speed determined by the toggle switch
setting.
(2) The time delay knob is adjustable from 3 to 30 minutes and will
switch the fan to the low speed setting after motion is no longer
detected in the room for the set period of time.
(3) The toggle switch will adjust the upper fan speed setting from 80
to 120 CFM using a 4" duct, or 90 to 140 CFM using a 6" duct.
Both 4" & 6" duct adaptors are included.
with 6" duct
WARNING -TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer
b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switching
on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated
construction codes and standards.
d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting.
Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f). Ducted fans must always be vented to the outdoors.
g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit (ceiling installation only).
h). This unit must be grounded.
i). Not for Use in Kitchens.
j). Install Fan At Least 2.5 m (8.2 feet) Above The Floor
k). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics,
crawl spaces, or garages
l). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control Device.
m). The fan must not be installed in a ceiling thermally insulated to a value greater R40
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up. DO NOT MOUNT THIS
PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
*The manual in electronic format can be download in our company web, or obtained from our dealer.
Max 30CFM Max 3min
S T
-
+-
+
Max. 30CFM 30min 3min
S T

Hold the housing so that it is in contact with the bottom of the joist. Attach
the housing with four (4) screws to the joist through the holes in each
mounting flange.
1. MOUNT HOUSING TO JOIST OR I-JOIST.
HANGER
BAR
2. MOUNT WITH HANGER BARS
2a. Sliding hanger bars have been provided, which allow the housing to
be positioned accurately anywhere between the framing. The bars span
up to 24 in. and can be used on all types of framing: I-joist, standard joist,
and truss construction. Slide hanger bars onto housing and adjust as
needed to fit between framing.
PLAN THE INSTALLATION
TYPES OF TYPICAL INSTALLATIONS
1. Do not use in a cooking area.
2. Two ways to connect ductwork to a factory-shipped unit.
ASSEMBLY INSTRUCTIONS
1. Housing mounted to I-joists (Start at “ASSEMBLY INSTRUCTIONS 1”)
2. Housing mounted to joists (Start at “ASSEMBLY INSTRUCTIONS 1” )
3. Housing mounted to truss (Start at step “ASSEMBLY INSTRUCTIONS 2”)
2
OPERATION
7 to 9 feet
7 to 9 feet.
The fan and LED light can be operated separately.
Turn on the switch to activate sensor and continuous ventilation
system. The fan will run continuously at the pre-set low speed.
When motion is detected, the fan speed increases to high speed.
When the person exits the area, the fan remains working at high
speed until the delay time has passed (adjustable 3-30 minutes).
After the time delay, the fan speed is reduced to the continuous
ventilation rate.
ROOF CAP*
(with built-in
damper)
ROUND
DUCT* WALL CAP*
(with built-in
damper)
*Purchase
separately
POWER
CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct
joints with
tape.
Keep duct
runs short

NAIL
2b. Extend the hanger bars to the width of the framing. Position the
ventilator with the hanger bar tabs wrapped around the bottom edge of
the framing, holding the ventilator in place.
Secure hanger bars to framing using one screw on each end of hanger bar.
Select a proper hole and secure the hanger bars together using flange
screws.
3. ATTACH DAMPER/DUCT CONNECTOR
Snap the damper/duct connector onto the fan housing. The connector
must be flush with the top of the housing, and the damper flap should
fall closed.
4. INSTALL ROUND DUCTWORK
Connect the round ductwork (not included) to the damper/duct connector,
and run the ductwork to a roof or wall cap (not included). Using tape (not
included), secure all the ductwork connections so that they are air tight.
Run 120 V AC house wiring to the location of the fan. Use only UL-approved connectors (not included) to attach the house wiring to the
wiring plate. Refer to the wiring diagram, and connect the wires as shown.
Install ceiling material to complete the ceiling construction. Then, cut around
the fan housing.
First insert the sensor plug into the plug base on the power box, and then
install the grille.
To attach the grille assembly to the fan housing, pinch the grille springs on
the sides of the grille assembly, and position the grille into the housing with
the grille springs in the appropriate slots. Push the grille assembly towards
the ceiling to secure.
ASSEMBLY INSTRUCTIONS
ASSEMBLY INSTRUCTIONS
CONNECT ELECTRICAL WIRING
INSTALL GRILLE
SCREW
3
DUCT
FAN
FAN
LIGHT
SWITCH BOX
BLK
WHT
D
Low CFM
switch
S
elay time
Preset switch
Fan
N
LED
Sensor
and LED
Light
GRD
UNIT
SWITCH
SWITCH
BLK
WHT
LINE
IN
LED NIGHT
CONTROL
CIRCUIT
BRN UNIT
BLACK(BLK)
LED NIGHT
LIGHT
SWITCH BOX
FAN
120V AC LINE IN
GROUND (GRD)
BROWN(BRN)
WHITE (WHT)
WIRE PANEL
RECEPTACLE
Insulated flexible duct is recommended for the quietest possible installation.
If rigid duct is used, a short (1-3 feet) section of insulated flexible duct will
ensure quiet operation

WARRANTY
SERVICE PARTS
4
5
6
d
e
a
1
12
2
3
4
b
c
7
9
8
10
10
11
PART PART NAME Qty.
1
2
3
4
5
6
7
8
9
10
11
a
b
c
d
e
Housing
Damper / Duct Connector
Wiring plate
Screw
Blower Wheel
Wire Panel / Harness Assembly
Motor
1
1
2
1
1
1
1
1
1
1
4
1
12 Sensor (includes sensor system and LED light) 1
4
4
1
4
1
Isolator
Motor Plate
Washer
Nut, Hex Lock
Grille Assembly (includes part 2 & 12)
Grille Spring
Hanger Bar Kit
Screw
Power Box
* Blower Assembly includes part 6, 5, d, 4, c, b, a.
Replacement installation:
Remove the screw (part c), then take out the motor plate (part 4) from
the housing (part 9) by pushing down the rib in the plate while pulling
out on the side of the housing. Replace the broken parts.
WARNING: Before replacing, be sure to turn off power at power source.
S&P USA Ventilation Systems, LLC. & S&P Canada Ventilation Products, Inc. warrants to the original end user of its
products that our exhaust fans will be free from defects in materials and workmanship for a period of Five (5) years from
the date of original purchase. 6 years warranty for motor and 5 years warranty for the remaining fan parts. THERE ARE
NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED
WARRANTIES OF SUITABILITY FOR A PARTICULAR PURPOSE.
During this five year period, S&P will, at its option, repair returned products or parts, or provide replacement products or
parts, without charge, for any product or part which is found to be defective under normal use.
This warranty does not cover normal maintenance and service or any parts that have been subject to misuse, negligence,
accident, improper maintenance or repair, faulty installation or installation contrary to recommended installation instructions.
S&P’s obligation to repair or replace, at S&P’s option, shall be the purchaser’s sole and exclusive remedy under this
warranty. No labor or materials are covered by this warranty. S&P shall not be liable for incidental damages arising out of
or in connection with product use or performance.
This warranty gives you specific legal rights. You may also have other rights which vary from state to state.
To qualify for warranty service, you must notify S&P at the address or telephone number stated below, provide the model
number and part identification, and describe the nature of any defect in product or part. You may be required to ship a
defective part to S&P. There will be no charge for shipping repaired or replacement parts from S&P to you if your address
is in the United States or Canada. At the time of requesting warranty service, you must present evidence of the original
purchase date.
S&P USA Ventilation Systems,LLC.
6393 Powers Avenue Jacksonville, FL 32217
P. 904-731-4711
F. 904-731-8322
www.spvg-northamerica.com
S&P Canada Ventilation Products, Inc.
5600 Ambler Drive Mississauga, ON L4W 2K9
P. 866-733-0233
F. 866-358-5346
www.solerpalaucanada.com
Table of contents
Other S&P Fan manuals

S&P
S&P SILENT-100 DESIGN Manual

S&P
S&P TTT Series User manual

S&P
S&P PCD80XH User manual

S&P
S&P HVE-230 A User manual

S&P
S&P METEOR-ES N User manual

S&P
S&P EDM-80N Manual

S&P
S&P ARTIC-405 CN GR User manual

S&P
S&P TD-125XS Assembly instructions

S&P
S&P DECOR-100 VISUAL User manual

S&P
S&P DOMEO 210 RD User manual

S&P
S&P HTB-140 Technical Document

S&P
S&P HTB-2500 Quick guide

S&P
S&P KIT EDM-100 12V+CT-12/14 User manual

S&P
S&P BSP User manual

S&P
S&P EBB-175 User manual

S&P
S&P FIRE FAN P User manual

S&P
S&P PULSE Series User manual

S&P
S&P CTBH ECOWATT User manual

S&P
S&P TDM-100 Installation instructions

S&P
S&P TPSB ECOWATT Series User manual