Schletter FixGrid East-West User manual

F i x G r i d E a s t - W e s t
(short side clamping)
F i x G r i d + E a s t - W e s t
(long side clamping)
INSTALLATION MANUAL

MOUNTING INSTRUCTIONS FOR DOUBLE ALIGNMENT (E.G., EAST-WEST):
REQUIRED T O O L
Measuring tape, screwdriver with Bit T X drive T40 (module mounting) and socket wrench insert with SW8
socket wrench (e.g., internal connector)
FURTHE R REQUIRED DOCUMENTS
General mounting instructions - Mounting and project planning
Mounting instructions Module clamps Rapid16
Product Sheet FixGrid Kit
TIGHTENING T ORQU E S
Screw connections M8: 15 Nm
Exception: Self-drilling screws have to be screwed on in a stop-oriented manner
SAFET Y INFORMAT I ON
The system is to be installed only with ballasting in accordance with static loads. You will receive these
with the planning of your solar plant from the Schletter configurator
Risk of breakage! PV modules can be damaged if they are stepped on.
Planning of the solar power system, installation and commissioning may only be performed by qualified
personnel. Improper execution can cause damage to the system and endanger people.
Danger due to electric current! Installation and maintenance of the PV modules may only be performed
by qualified personnel. Observe the safety regulations of the PV module manufacturer!
Risk of falling! There is a risk of falling when working on the roof and when climbing up and down. Is it
imperative that the accident prevention regulations are observed and that suitable fall protection devices are
used. PV mounting systems are not suitable as climbing aids or fall protection.
Risk of injury! People may be injured by falling objects. Before starting the installation work, block off
the danger zone and warn people in the vicinity.
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
2
For roofs with substrate or gravel covering, it must be considered that a low weight
load for the system can only be achieved if sliding of the system sections is reliably
prevented by an adequately slip-free connection for the substrate surface. For gravel
roofs, flush embedding of the base beams in the gravel surface is enough. For overgrown
roofs, slip resistance can be achieved with additional measures. For example,
screws in the continuous beam can be used on the construction site to create a non-slip
connection to the substrate.
NOTE ON USE OF ROOFS WITH SUBSTRATE OR GRAVELLED COVERING

MOUNTING INSTRUCTIONS
Ensure that the flat roof waterproofing is compatible with the mounting system.The roof
drainage system has to be included in the planning of your solar plant.
In the case of very uneven roofs or roof waterproofing, compensatory measures may have to be taken in
order to ensure a uniform introduction of the load.
Necessary distances to roofedges have to be maintained.
The maximum field size depends on the type of roof.
For foil roofs, it is max. 10 m; for concrete roofs, it can also be larger in individual cases.
In the case of roofs with substrate or gravel roofing, it has to be ensured that a sufficiently non-slip
connection occurs.
Please check the existing pitch of the roofandwhether the mounting system has to be secured against
slipping.
Thesurface load is not permitted to exceedthe residual load-bearing capacity of the building!
The partial surface pressure, which acts on the roof membraneand insulation underthe base rails, is not
allowed under any circumstances to exceedthe maximum permissible surface pressure.
Current country-specific rules and regulations have to be observed.
Roof cleaning! In order to ensure that the base rails are supported across their entire surface, impurities
such as moss, leaves,dirt, stones, etc. have to be removed.
If there is a lightning protection system involved, it is important to determine theextent to which
integration by a certified lightning protection company is necessary. Whether or notthe lightning
protection requirements change as a result of the installation also has to be determined.
Due to static reasons, the installation of a single module row is not permitted!
Prior to installation, the roofhas to be checked for damage of any kind, particularly water beading
or damage to the roof membrane. These should be documented with photos in order to be able to
counteract any recourse claims. The system hasbeen developed for modules with a width of 950-1050
m m (standard module dimensions according to the current status). Other module dimensions on request
and separate verification. Information about module clamping pursuant to the manufacturer has to be
observed.
The FixGrid18 mounting system is fixed to the roofpurely with ballast (except special cases). A detailed
ballast calculation can be found in the project-related planning documents. The ballasting is calculated
in such a way that sliding, tilting and lifting of the rack is avoided.
Use only original Schletter components!
No modifications to the modules are required to secure them. It is the client’s/installer’s
responsibility to ensure the clamp location is in accordance with the panel installation
manual.
All other markings, information on the number of modules and
additional information can be found in the project-specific
documents.
Usethecurrent mounting instructions! Accessible on our website:
www.schletter-group.com in the FixGrid18 section.
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
3

1. DEFINING THE BASE RAIL LENGTHSAND DISTANCES BETWEEN MODULE SUPPORTS.
This applies to modules width between 950mm and 1050mm( other modules needs a special release)
The length of the base rails depends on the selected module width, maintenance aisle width and the
number of module rows.The distance between "System Rail at the bottom" and"System Railat the top"
only dependsuponthe module inclination. The first support should be placed at least 40 mm from the
frontedge of the base rail. The module frames are always flush at the top with the Rapid 16 module clamps.
The base rail length can be selected from the six standard lengths (2150, 2650, 3150, 4200, 6000, 6300 mm)
and combined with each other. The base rails can be connected with theinternal connector, Item No.
129078-000. The maximum permissible field size has to be observed!
FixGrid East-West
(short side clamping)
Mounting distances
VERSION 13:
maintenance walk
way width:
150mm
TECHNICA L DATA
•Conf orms to UL 2703
•Certi f ie d to LT R AE-001
•Fire c l ass r esi stanc e rati n g: C lass A w he n
us ed wi t h t ype I ph o to vol ta i c mo d ul e s
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
4
VERSION 10:
The mounting times can be optimized by pre-assembling a series of base rails next to each other
on mounting frames with the module supports.
VERSION 5:

1. DEFINING THE BASE RAIL LENGTHSAND DISTANCES BETWEEN MODULE SUPPORTS.
This applies to modules width between 950mm and 1050mm( other modules needs a special release)
The length of the base rails depends on the selected module width, maintenance aisle width and the
number of module rows.The distance between "System Rail at the bottom" and"System Railat the top"
only dependsuponthe module inclination. The first support should be placed at least 40 mm from the
frontedge of the base rail. The module frames are always flush at the top with the Rapid 16 module clamps.
The base rail length can be selected from the six standard lengths (2150, 2650, 3150, 4200, 6000, 6300 mm)
and combined with each other. The base rails can be connected with theinternal connector, Item No.
129078-000. The maximum permissible field size has to be observed!
FixGrid + East-West
(long side clamping)
Mounting distances
maintenance walk
way width:
150mm
TECHNICAL DATA
•Co nfor ms to UL 2703
•Certi f ie d to LT R AE-001
•Fire c l ass r esi stanc e rati n g: C lass A w he n
us ed wi t h t ype I ph o to vol ta i c mo d ul e s
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
5
The mounting times can be optimized by pre-assembling a series of base rails next to each other
on mounting frames with the module supports.
VERSION 10:
VERSION 5:

3. MOUNTING O F THE SURFACE PROTECTIO N MAT
•After removing the protective film, gluethe cut parts of the surface protection matonto the base
rails.
•Take into account a projection of the surface protection mat of at least 30 m m at the railends.
•Marking for the mounting of the module support:
Frontedge of the module support = Distance - 28 mm
•Place the frontedge of the support on the mark; pay attention to the direction of rotation!
•Turn clockwise by 90°.
Observe suitable module and row distances for railand module mounting.
In the case of transversely flowing rainwater, the distance has to be
dimensioned on the basis of the amount of precipitation on site.
The installation distances of the surface protection mats below the base rail result from the chosen
installation variant.
Variant A
•Mount 20-mm-thick and300-mm-long strips centrally under each support
•Load introduction on a small area (for low loads and/or solid subsoil)
•An additional surface protection mat should be positioned under joints of the base rails!
•If the roof water drains off transversely, an almost unhindered drainage is possible.
always centered below bearing
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
6
2. MOUNTING O F THE MODULE SUPPORT WITH PRE-ASSEMBLED SC RE W -IN C O N N E C TO R O N
TH E BASE RAIL

4. ALIGNMENT O F THE BASE RAILS
•Align base rails parallel to each other; align the FixGrid system rails flush and at right angles to the
base rails on the subsoil.
•Distance g = Module length + 23 mm
The permissible surface pressure of the roofhas to be checked!
Sufficient drainage of rainwater has to be ensured!
Variant B
•Apply20-mm-thick and300-mm-long strips at a distance of 100 mm
•Load introduction on large area (for high loads and/or soft subsoil with low permissible surface
pressure)
•Also suitable for transversely draining roof water
The permissible surface pressure of the roofhas to be checked!
Sufficient drainage of rainwater has to be ensured!
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
7
5. EXTENSION OF THE BASE RAILS
•Insert splice section 150mm into
the base rail as shown below.
•Secure splice in place using self
drilling screws provided, 1 per base
rail per splice.

7. INSTALLTHE FIRST MODULE
•Applythe Rapid 16 end clamps (atthe top and at the bottom) to the module and tighten,Screws
M8 (T40).
8. INSTALL FIRST MODULE
•Applythe next module.
•Tighten the middle clamps (atthe bottom and at the top) between the modules with Screws M8
(T40)
•Pre-assemble the other middle clamp on the free module side.
•Connect the module cable according to the plan.
•Repeat steps up to the last module in the row.
•Place the module center clamp on the module; do not tighten.
•Connect the module cable according to the plan.
6. AP P LY THE FIRST MODULE
•Click Rapid 16 end clamps into place at the edge of the module field and position them. Also click
the Rapid 16 middle clamp into place at a generous distance so that the module can be inserted
between the clamps.
•Place the module on the FixZ System Rail 18 and align it with the upperedge using the pre-
attached Rapid 16 clamps. Pay attention to the alignment of the module row.
Torque Value for Rapid16 clamps = 15 N.M/11 FT-LBS
(available in 50 or 100mm lengths)
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
8

9. MOUNT THE L AST M ODULE O F THE ROW
•Install the last module.
•Tighten the middle clamps (atthe bottom and at the top) between the modules with Screws M8
(T40)
•Mount and tighten the end clamps on the free side of the module.
•Connect the module cable according to the plan.
Insert the end clamps at least 30 m m from the railend
Note the module spacing for middle clamps
10. O BSTRU C T THE BALL AST
There are basically 3 ballasting options:
•Ballasting with 100-mm-wide concrete blocks on the base rails (see Detail A)
•Ballasting with additional trough (see Detail B)
•Ballasting with additional ballast shafts (see Detail C)
•Ballasting from the combination of the 3 possibilities
Theinformation about ballasting can be obtained
with the planning of your solar plant from the Schletter
configurator.
Use fixing flaps to attach the parts of the surface protection mat to the additional trough.
(Ballast is not included in the scope of delivery).
1-2 mm 1-2 mm
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
9
min. 30 mm

LAY THE BAL L A S T WITH ADDITI ON AL BA LL AST TR AY S
If the ballast trays are filled with gravel,the gravel can be prevented from leaking at the row ends by
folding up the tray ends. To do so, the ends of the ballast trays have to be folded at the perforation.
The first ballast tray is laid from the right with the recesses
andthe upstand on the base rails.
All other trays are turned 180degrees (recesses on the left) from right to left. The tray always lies with
the side of the slots at the bottom and in the base rail with a positive fit.
At the last ballast tray, the endhas to be unfolded again.
Further Information about our systemscan be found on our website:
www.schletter-group.com in the solar section under Downloads.
Detail A Detail B Detail C
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
10

BALLAST EXAMPLES FIXGRID 5
(PER ONE OF THE TWO MODULES OF THE EAST-WEST CONFIGURATION)
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
11
BALLAST EXAMPLES FIXGRID 10
(PER ONE OF THE TWO MODULES OF THE EAST-WEST CONFIGURATION)

BALLAST EXAMPLES FIXGRID 10 +
(PER ONE OF THE TWO MODULES OF THE EAST-WEST CONFIGURATION)
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
12
BALLAST EXAMPLES FIXGRID 5 +
(PER ONE OF THE TWO MODULES OF THE EAST-WEST CONFIGURATION)

BALLAST EXAMPLES FIXGRID 10 +
(PER TWO MODULES OF THE EAST-WEST CONFIGURATION)
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
13
BALLAST EXAMPLES FIXGRID 5 +
(PER TWO MODULES OF THE EAST-WEST CONFIGURATION)

INFORMATION A B O U T INTERNAL AND EXT E RN AL GROUNDING
Theinternal bonding path starts at the module and continues via the earthing pin into the clamping part
and continues via thescrew, the assembly claw, the module suport andthe turn-in connector to the basic
profile.
Theexternal bonding path must be specified by the Installer.
COMPONENTS RECOMMENDED BY SCHLET TERFOR EQUIPOTE NTIAL BONDING
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
14

Installer is responsible for and shall provide an appropriate method of direct to-earth
grounding according to the latest edition of the National Electrical Code, including
NEC 250: Grounding and Bonding, and NEC 690: Solar Photovoltaic Systems." and
"Installation shall be in accordance with CSA C22.1, Safety Standard for Electrical
Installations, Canadian Electrical Code, Part 1.
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
15

ILSCO GROUNDING PAT H INSTALLATIO N INSTRUCTION
GBL-4SS, Ground L ug Installation Instructions for Photo Voltaic Applications
glass
module frame
stainless steel
hex nut
stainless steel
star washer
deox
ground lug
GBL-4SS
stainless steel
flat washer
stainless steel
split washer
stainless steel
hex bolt
side view frontview
1.Install GBL-4SS ground lugper diagram, use #10-32 mounting hardware.
2.Apply a liberal amount of conductor on frontand back side of module frame at mounting hole.
Although not required, Schletter strongly recommend theuse of conductor compound between the
mounting surfaces in order to better protectthe connection in all environmental conditions and promote
connection longevity.
3. For GBL-4SS, apply 35 in-lbs mounting torque to #10 mounting bolt.
4. Apply a liberal amount of conductor compound in wireway of ground lug
5.Install ground conductor in lugand torquewire screw to the following:
6 AWG: 35 in-lbs.
8 AWG: 25 in-lbs.
10 - 14 AWG: 20 in-lbs.
*Flat washer and split washer are not required
Additional Information:
a.GBL-4SS. is suitable for use with flat-surfaced anodized aluminum or galvanized steel
designated G90 minimum. The acceptable mounting hole diameter is 0.196 inches
±0.004 inches (4.98mm±.1mm).
b.The acceptable framing material thickness is a minimum of 0.062 inches (1.57mm)
to 0.250 inches (6.35mm), with a flat surface are of no less than 34 by 12mm (bottom
of the lug).
c.FixGrid mounting system is to be only in combination with listed PV-modules
that include the specific rack system in their installation manual. Refer to the
approved module list for the listing PV-modules which can be used in com-
bination with the FixGrid.
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
16

d.For sizing of an Equipment Grounding Conductor (EGC), the rating of the O vercurrent Protection
Device (OCPD) in circuit ahead of the Equipment shall notexceedthe values in NEC table 250.122 where
theEGC is only required to be larger than thecircuit conductors supplying the equipment.
e.For use with a Grounding Electrode Conductor (GEC), the size of the conductor shall comply with NEC
articles 250.66 for AC systemsand250.166 for D C sy stems.
f. Rated maximum system overcurrent protection (Cu conductor):
12 AWG:
10 AWG:
20A
30A
g. This racking system may be used to ground and/or mount a PV module complying with UL 1703 only
when the specific module has been evaluated for grounding and/or mounting in compliance with the included
instructions.
O vercurrent Protection Device (grounding)
•Accommodated stranded or solid copper wire (2 gauge to 14 gauge).
•Must usebare copper wire to connect to the grounding wire, remove at least two inches of insulation
to expose copper wire.
•Connects to the bottom 10 rail channel of module rail.
Loosen or remove top portion of groundinglog and insert
grounding wire into appropriate groove.
Grounding log (Part # 135003-003) Grounding wire must extend
through grounding lug by at least
1/4 inch
Gauge of Grounding Wire conductor
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
17

GENERA L NOTES O N MAINTE NANC E
Yearly inspection of the system should be conducted to maintain optimal performance by qualified
personnel.
Visual inspection for
•signs of damage
•signs of wear of components
•signs of components
•position of the ballast
•position of roof protection mats
Replace any affected components immediatly: torque at module clamps must be verified with a
Torque wrenchand should be set at 50% of intended tightening torque.
Do not touch thelive part of thewire, cable and connector directly but with safery equipment
(insulating tools) when necessary.
WARNING! Contact your installer immediatly if you suspect your system is not working
properly.
WARNING! ThePV System must be shut down first if it needs any electrical
maintenance. Improper maintenance may cause lethal electric shocks/ or burns.
Fire Test
FixGrid racking system meet with Standard UL 2703, Clauses 11.1
that required a rack mounting system intended for stand-off, rack,
or direct mounting in combination with a specified roof, or
intended for integral mounting in combination with the specified
PV module(s) comply with the fire resistance requirements for a
“Class A” PV System Rating in accordance with the Standard for
Flat-Plate Photovoltaic Modules and Panels, UL 1703.
•Fire Test Class A Type 1
•Fire class resistance rating: Class A when used with Type I
photovoltaic modules only
Fire Test configuration
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
18

FS
Middle Clamp 0,67
End Clamp 0,68
FI XZ- PROFILES INC L. TU RN-IN C O N N E C TOR
Maximum permissible pressure values 5400 kPa
Maximum permissible tensile values 2400 kPa
RAPID 16 shear strength [kN/ clamp]
INF ORM ATI ON O N TENSILE O R SHE AR ST RENG TH
Rapid 16 module clamps (according Z-14.4 - 631)
(available in 50 or 100mm lengths)
SHEAR
Loaddirection:
TENSILE
Profile FT[kN]
Middl
e Clamps FixZ 3,88
En
d Clamps FixZ 1,63
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
19

APPROVED MODULE LIST
MANUFACTURER MODEL NUMBERS
FIXGRID EAST-WEST I V1 I INSTALLATION MANUAL I
12-2020 SCHLETTER NA Inc. I SUBJECT TO CHANGE
WITHOUT NOTICE
20
Boviet Solar
Canadian Solar
BVM6612
ET Solar
Hanwha Q Cells
CS6X‐P‐FG
CS6X‐P
CS6V‐M
CS6U‐P
CS6U‐M
CS6U
CS6P‐P‐SD
CS6P‐P
CS6P‐M
CS6K‐P‐FG
CS6K‐P
CS6K‐MS
CS6K‐M AB
CS6K‐M
CS6K
CS5A‐M
CS3W‐PB‐AG
CS3W‐P
CS3W‐MS
CS3W‐MB‐AG
CS3W
CS3U‐PB‐AG
CS3U‐P
CS3U‐MS
CS3U‐MB‐AG
CS3U
CS3L‐P
CS3L‐MS
CS3L
CS3K‐PB‐AG
CS3K‐P
CS3K‐MS
CS3K‐MB‐AG
CS3K
CS1Y‐MS
CS1U‐MS
CS1K‐MS
CS1H‐MS
ET‐M660 290|285|280|275|270 WW|WB
ET‐M672 340|335|330|325|320 BB
ET‐M672 345|340|335|330|325 WW|WB
ET‐P660 265|260|255|250 BB
ET‐P660 270|265|260|255 WW|WB
ET‐P672 315|310|305|300 BB
ET‐P672 320|315|310|305 WW|WB
L‐G2
L‐G3
L‐G4
Q.PEAK DUO BLK‐G5
Q.Peak DUO BLK‐G6
Q.Peak DUO G6
Q.Peak DUO LG6
Q.PEAK DUO‐G5.X
Q.PEAK DUO‐G5
B.LINE PRO L G4.1
B.LINE PLUS L G4.2
B.LINE PRO L G4.2
B.LINE PLUS BFR G4.1
B.LINE PRO BFR G4.1
This manual suits for next models
1
Other Schletter Inverter manuals
Popular Inverter manuals by other brands

Spectrum Technologies
Spectrum Technologies 3999 quick start guide

Shihlin electric
Shihlin electric SL3 Series user manual

Tabuchi Electric
Tabuchi Electric THD-S55P3B-US user manual

Generac Power Systems
Generac Power Systems Guardian 04389-1 Installation and owner's manual

Grundfos
Grundfos RSI Booklet

GRIDFREE
GRIDFREE Weekend Warrior installation manual

Dometic
Dometic MSI912 Installation and operating manual

Sungrow
Sungrow SG3.0RT user manual

Cerus Industrial
Cerus Industrial C Series Installation & operation manual

ionGen
ionGen GTX12V315A-E2107-CS200 Installer's guide

Cobra
Cobra CPI2590 operating instructions

Mitsubishi Electric
Mitsubishi Electric F800-E Series instruction manual