3
CSS 34
Operating instructions
Safety sensor
EN
2.5 Technical data
Standards: IEC 60947-5-3; ISO 13849-1;
IEC 61508, IEC 62061
Enclosure: glass-fibre reinforced thermoplastic
Operating principle: inductive
Coding levels according to ISO 14119: low
Actuator and switch distances
(according to IEC 60947-5-3): see table "Actuator / Switch distances“
Hysteresis: max: 1.5 mm
Repeat accuracy R: < 0.5 mm
Switching frequency f: 3 Hz
Series-wiring: max. 31 devices
Cable length: max. 200 m
Connector: M12, 8-pin in casing
Pre-wired cable: Y-UL 2517 / 8 × AWG 22 / 8 × 0.35 mm², 2 m
Temperature resistance of the cable:
- at rest:
- in motion:
Ambient conditions:
Ambient temperature Tu:
Storage and transport temperature:
Resistance to vibration:
Resistance to shock: 30 g / 11 ms
Protection class: IP65, IP67 to IEC 60529
Electrical data:
Rated operating voltage Ue:
(stabilised PELV to IEC 60204-1)
Rated operating current Ie:0.6 A
Required rated short-circuit current: 100 A
Fuse (line protection): note the wire
diameter of continuing wire:
- for wire variants:
- for plug version: 2.0 A
Rated insulation voltage Ui:32 VDC
Rated impulse withstand voltage Uimp:800 V
No-load current Io:0.1 A
Response time: < 30 ms
Duration of risk: < 60 ms
Protection class: II
Overvoltage category: III
Degree of pollution: 3
EMC rating: according to IEC 60947-5-3
Electromagnetic interference: according to IEC 60947-5-3
Safety outputs Y1/Y2: normally open function, 2 channel,
p-type, short-circuit proof
Rated operating voltage Ue1:max. 1 V below Ue
Leakage current Ir:< 0.5 mA
Rated operating current Ie1:max. 0.25 A, dependent
on ambient temperature
Minimum operating current Im:0.5 mA
Utilisation category: DC-12, DC-13
Rated operating voltage/current Ue1/Ie1:24 VDC / 0.25 A
Diagnostic output: short-circuit proof, p-type
Voltage drop: < 5 V
Rated operating voltage Ue2:min. (Ue– 5 V)
Operating current Ie2:max. 0,05 A
Utilisation category: DC-12, DC-13
Rated operating voltage/current Ue2/Ie2:24 VDC / 0.05 A
Wiring capacitance for serial diagnostics: max. 50 nF
2.6 Safety classification
Standards: ISO 13849-1, IEC 61508, IEC 62061
PL: e
Control Category: 4
PFH value: 3.6 x 10-9 / h
SIL: suitable for SIL 3 applications
Service life: 20 years
3. Mounting
3.1 General mounting instructions
During fitting, the requirements of ISO 14119 must be ob-
served.
The component can be mounted in any position. The active surface
of the safety sensor and the actuator has to be opposite. The sensor
enclosure must not be used as an end stop. The active surface of the
safety sensor is either the lateral surface marked with the type plate or
the front, rounded surface. The safety sensor must only be used within
aoar.
The safety sensor and the CST 34-.-1 or CST 34-S-2 actuators are
supplied with integrated mounting plate. With the slotted holes of the
mounting plates, possible tolerances can be horizontally and vertically
compensated. The components are fitted with M4 screws.
The safety sensors and the actuators can be clipped onto the mounting
plate with different actuating directions. Both components are fixed by
means of a locking cap.
Safety sensor and actuator must be permanently fitted to the
safety guards and protected against displacement by suitable
measures (tamperproof screws, gluing, drilling of the screw
heads).
The mounting plates must be pinned after their fixation. The
mounting brackets also must be secured by means of the
supplied locking pin to protect them against tampering. The
CST-S-3 and CST 180 actuators must be protected by tam-
per-proof screws or a tamper-proof fitting.
must be fitted so that it is protected against unintentional
contact with persons.
To avoid any interference inherent to this kind of system and any reduc-
tion of the switching distances, please observe the following guidelines:
Minimum distance between two sensors: 100 mm