System Sensor 1112/24D User manual

D200-63-00 1 I56-931-06
1112/24D Ionization Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read System Sensor Manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing,
placement, zoning, wiring, and special applications.
Copies of this manual are available at no charge from
System Sensor.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
General Description
The 1112/24D is a 4-wire ionization smoke detector that
uses a state-of-the-art sensing chamber. This detector is
designed to provide open area protection.
Installation of this detector is simplified by the use of an
adapter bracket and a plug-in screw terminal block that
can be prewired to the system, allowing the detector to
be easily installed or removed for cleaning. The detector
sensitivity can be tested in place using the MOD400R
Test Module.
An LED on the detector provides local visual indication of
the detector status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every five seconds. The LED also latches on in alarm.
The 1112/24D also features visual indication that mainte-
nance is required; if the sensing chamber drifts out of its
sensitivity limits, the LED ceases to blink.
IMPORTANT: OBSERVE POLARITY
This detector requires that you observe polarity when wiring. If wiring polarity is not observed on the
initiating loop, the unit will send an alarm signal to the control panel to signify incorrect wiring.
A78-2336-05
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716B 12/24V
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
–
+
–
+
+
+
–
–
+
–
N.O. C
+
+
–
N.O. C
: Observe polarity in power and initiating loops when wiring.
NOTE
Figure 1. Wiring diagram for the 1112/24D detector:
D200-63-00 2 I56-931-06
Mounting
Each 1112/24D detector is supplied with a mounting
bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4-inch square electrical box by using a plaster ring.
Wiring Installation Guidelines
CAUTION
Be certain to observe polarity when wiring.
All wiring must be installed in compliance with the Na-
tional Electrical Code, applicable local codes, and any spe-
cial requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
Figure 3. 1112/24D detector mounting bracket:
ALIGNMENT ARROWS
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
Figure 2. Surface mounting 1112/24D detector on 31/2
inch and 4 inch octagonal box:
A78-2563-00 A78-2333-02
pair may be used to provide additional protection against
electrical interference.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance al-
lowed for the control panel being used before wiring the
detector loops.
Wire connections are made by stripping about 1/4inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Tamper-Resist Feature
This detector includes a tamper-resist feature that prevents
its removal from the bracket without the use of a tool. To
make the detector tamper-resistant, remove the smaller tab
by breaking it at the scribed line on the tamper resistant tab
on the detector mounting bracket (see Figure 3), then in-
stall the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screw-
driver to depress the tamper-resistant tab, located in the
Specifications
Diameter: 5.5 inches (140 mm)
Height (including adapter bracket): 1.7 inches (43 mm)
Weight: 5.3 oz. (150 g)
Operating Temperature Range: 32°to 120°F (0°to 50°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Relay Contact Rating–
Resistive Load: 0.1A @ 35VDC
Electrical Ratings
System Voltage nominal: 12 or 24 VDC; 8.5 VDC minimum; 35 VDC maximum
Maximum Ripple Voltage: 30% of nominal voltage (peak to peak)
Reset Voltage: 0.8 VDC minimum
Standby Current: 50 µA maximum
Alarm Current: 17 mA typical, 23 mA maximum @ 12V; 19 mA typical, 25 mA maximum @ 24V
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 60 second reset)
D200-63-00 3 I56-931-06
slot on the mounting bracket (see Figure 4), and rotate the
detector counterclockwise.
Installation
WARNING
Remove power from the control unit or initiating device cir-
cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Rotate the detector clockwise in the mounting bracket
until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
NOTE: This detector has a feature that will signal an
alarm at the control panel if wiring polarity is
incorrect.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
A78-2564-01A
Figure 4. Top and side views showing location of test switch:
PUSH RECESSED
SWITCH WITH A
0.18″MAX. DIAMETER TOOL
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;
A78-2564-00C
I
N
T
A
P
T
O
N
O
D
LED
TEST MODULE
SOCKET RECESSED TEST
SWITCH
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte-
nance and, therefore, will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following pe-
riodic maintenance. Test the 1112/24D as follows:
A. Test Switch
1. A recessed test switch is located on the detector hous-
ing (See Figure 4).
2. Press and hold the recessed test switch with a 0.18
inch maximum diameter tool such as an allen wrench
or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or
analog voltmeter to check the detector sensitivity as de-
scribed in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the de-
tector until the unit alarms.
A detector that fails to activate with any of the above tests
should first be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
Notify the proper authorities the system is back in operation.
D200-63-00 4 I56-931-06
© System Sensor 1998
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
This smoke detector is designed to activate and initiate emergency ac-
tion, but will do so only when it is used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not
reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large de-
lays in detecting a smoldering fire with either an ionization type detector
or a photoelectric type detector. Either one of them may alarm only after
flaming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a fire developing on another level of a building quickly or at
all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
smoldering type. This is to ensure that both can detect a wide range of
types of fires. Ionization detectors offer a broad range of fire sensing capa-
bility but they are somewhat better at detecting fast flaming fires than
slow smoldering fires. Photoelectric detectors sense smoldering fires better
than flaming fires which have little, if any, visible smoke. Because fires de-
velop in different ways and are often unpredictable in their growth, nei-
ther type of detector is always best, and a given detector may not always
provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires re-
sulting from inadequate fire protection practices, violent explosions, es-
caping gases which ignite, improper storage of flammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smok-
ing in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to dilu-
tion of smoke densities created by frequent and rapid air exchanges. Addi-
tionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
To keep your equipment in excellent working order, ongoing maintenance
is required per the manufacturer’s recommendations and UL and NFPA
standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the
National Fire Alarm Code, shall be followed. A preventative maintenance
agreement should be arranged through the local manufacturer’s represen-
tative. Though smoke detectors are designed for long life, they may fail at
any time. Any smoke detector, fire alarm equipment, or any component of
that system which fails shall be repaired or replaced as soon as possible.
WARNING
The Limitations of Property Protection Smoke Detectors
Maintenance
NOTE: Before removing the detector, notify the proper au-
thorities that the smoke detector system is under-
going maintenance and will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
1. Remove the detector housing by gently prying the four
housing tabs on the bottom of the base with a small-
bladed screwdriver and pull the housing from the base.
2. Vacuum the screen carefully without removing it.
3. Remove the screen by pulling it straight away from the
sensing chamber (see Figure 5).
4. Clean the sensing chamber by vacuuming or blowing
out dust and particles.
5. Replace the screen by placing it over the sensing cham-
ber. Rotate the screen until is snaps into place.
6. Replace the housing by aligning the three triangular slots
on the base with their counterparts on the housing. Gen-
tly press the housing until it locks in place.
7. Reinstall the detector.
8. Notify the proper authorities that the system is back in
operation.
REMOVABLE
HOUSING
REMOVABLE
SCREEN
BASE
SENSING
CHAMBER
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
yyyyyyyyyyyyyyyy
Figure 5. Removal of cover and screen for cleaning:
A78-2565-03

Other System Sensor Security Sensor manuals

System Sensor B210LP User manual

System Sensor

System Sensor B210LP User manual

System Sensor 4451HTA User manual

System Sensor

System Sensor 4451HTA User manual

System Sensor B114LPBT User manual

System Sensor

System Sensor B114LPBT User manual

System Sensor B524IEFT-1 User manual

System Sensor

System Sensor B524IEFT-1 User manual

System Sensor B224RB User manual

System Sensor

System Sensor B224RB User manual

System Sensor B401BR User manual

System Sensor

System Sensor B401BR User manual

System Sensor CO1224 User manual

System Sensor

System Sensor CO1224 User manual

System Sensor B200SA User manual

System Sensor

System Sensor B200SA User manual

System Sensor B404B User manual

System Sensor

System Sensor B404B User manual

System Sensor EBR User manual

System Sensor

System Sensor EBR User manual

System Sensor ECO1005ABL User manual

System Sensor

System Sensor ECO1005ABL User manual

System Sensor 9440X FAAST User manual

System Sensor

System Sensor 9440X FAAST User manual

System Sensor OSI-RIE Series User manual

System Sensor

System Sensor OSI-RIE Series User manual

System Sensor B501AUS User manual

System Sensor

System Sensor B501AUS User manual

System Sensor B801RA User manual

System Sensor

System Sensor B801RA User manual

System Sensor DH400ACDC User manual

System Sensor

System Sensor DH400ACDC User manual

System Sensor B404BT User manual

System Sensor

System Sensor B404BT User manual

System Sensor B224RB User manual

System Sensor

System Sensor B224RB User manual

System Sensor WFDT User manual

System Sensor

System Sensor WFDT User manual

System Sensor CO1224T Instruction Manual

System Sensor

System Sensor CO1224T Instruction Manual

System Sensor 8100A FAAST User manual

System Sensor

System Sensor 8100A FAAST User manual

System Sensor B501AP User manual

System Sensor

System Sensor B501AP User manual

System Sensor B110RLP User manual

System Sensor

System Sensor B110RLP User manual

System Sensor B110LP User manual

System Sensor

System Sensor B110LP User manual

Popular Security Sensor manuals by other brands

Buckingham 60007 instructions

Buckingham

Buckingham 60007 instructions

PCB Piezotronics 1203-15A Installation and operating manual

PCB Piezotronics

PCB Piezotronics 1203-15A Installation and operating manual

Vega VEGAPULS C 21 operating instructions

Vega

Vega VEGAPULS C 21 operating instructions

Zircon StudSensor L70 OneStep user manual

Zircon

Zircon StudSensor L70 OneStep user manual

BRITBE G3 PRO instruction manual

BRITBE

BRITBE G3 PRO instruction manual

Transmitter Solutions iGAZER50LR instruction manual

Transmitter Solutions

Transmitter Solutions iGAZER50LR instruction manual

Dynalog C-SCAN 2000 Series Operator's manual

Dynalog

Dynalog C-SCAN 2000 Series Operator's manual

Dräger X-plore 5500 Instructions for use

Dräger

Dräger X-plore 5500 Instructions for use

Bosch DS1103i installation instructions

Bosch

Bosch DS1103i installation instructions

GE Motion Sensor user manual

GE

GE Motion Sensor user manual

X4-Life 701445 user manual

X4-Life

X4-Life 701445 user manual

Aqara TH-S02D user manual

Aqara

Aqara TH-S02D user manual

Weco CDZ Series user manual

Weco

Weco CDZ Series user manual

Olympus EPOCH 6LT user manual

Olympus

Olympus EPOCH 6LT user manual

Heiman HM-807DWP manual

Heiman

Heiman HM-807DWP manual

suprema BioEntry Series installation guide

suprema

suprema BioEntry Series installation guide

iProTech Protect 1207i user manual

iProTech

iProTech Protect 1207i user manual

EVE 20EBG8701 Get started

EVE

EVE 20EBG8701 Get started

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.