2
Operating instructions
Pull-wire emergency stop switches ZQ 900
EN
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly
forbidden, the manufacturer shall accept no liability for damages
resulting from such invasive work, arbitrary repairs, conversions and/or
modifications to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
ZQ 900-
➀➁
-
➂
No. Option Description
➀
11 1 NO contact / 1 NC contact
13 1 NO contact / 3 NC contacts
22 2 NO contacts / 2 NC contacts
02 2 NC contacts
04 4 NC contacts
➁
without emergency-stop button
N with emergency-stop button
➂
Cable entry 3x M20
STC2 Connector plug, M12, A-coded, 4-pole
FB Connector plug, M12, A-coded, 8-pole
Only if the information described in this operating instructions
manual are realised correctly, the safety function and
therefore the compliance with the Machinery Directive is
maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Purpose
Pull-wire emergency stop switches are used on machinery and plants,
where triggering the emergency stop command must be enabled at
arbitrary points on the wire run. If the tensioned pull-wire is pulled or
in case of wire breakage or if the optional emergency stop switch is
pushed, the switching function of the pull-wire emergency stop switch is
activated (refer to image 1).
F
1
Image 1: Position indication and actuation
Design/operating principle
The pull-wire emergency stop switches of the ZQ 900 series are brought
into the operational condition by the proper pre-tensioning of the wire.
Up to two switching elements located on the inside of the switch have
either 2 or 4 contacts, whereby the NC contacts are closed and the
NO contacts are opened in tensioned condition.
After actuation of the emergency stop function, a latching mechanism
maintains the stop command until the switch is released by pushing the
blue reset button. Prior to the reset of the emergency stop signal, the
reason why the switch has been actuated must be determined. The
switch can only be reset if the switch is correctly pre-tensioned (position
indication in central position, refer to image 1).
The ZQ 900-FB is for use in combination with the safety field box SFB
made by Schmersal.
The user must evaluate and design the safety chain in
accordance with the relevant standards and the required
safety level.
The entire concept of the control system, in which the safety
component is integrated, must be validated to the relevant
standards.
2.4 Technical data
Standards: EN 60947-5-1, EN 60947-5-5, EN 620, EN ISO 13850
Enclosure: zinc die-cast, paint
Cover: thermoplastic
Degree of protection: IP65, IP67 to EN 60529
- ZQ 900-...-N: IP65
Protection class: I
Degree of pollution: 3
Contact material: Silver
Switching system: Change-over contact with double break,
1 to 4 NC contacts,
snap action with positive break NC contacts
Termination: screw terminals or connector plug M12,
A-coded, 4-pole or 8-pole
Cable section: max. 2.5 mm²
(incl. conductor ferrules)
Cable entry: 3x M20
Utilisation category AC-15, DC-13 Ie/Ue:
- Screw terminal connection 4 A / 240 V/AC, 1 A / 24 V/DC
- Plug connector M12, 4-pole 4 A / 240 V/AC, 1 A / 24 V/DC
- Plug connector M12, 8-pole 2 A / 24 V/AC, 1 A / 24 V/DC
Rated impulse withstand voltage Uimp:
- Screw terminal connection 6 kV
- Connector plug M12, 4-pole 2.5 kV
- Connector plug M12, 8-pole 0.8 kV
Rated insulation voltage Ui:
- Screw terminal connection 500 V
- Connector plug M12, 4-pole 250 V
- Connector plug M12, 8-pole 32 V
Thermal test current Ithe:
- Screw terminal connection 10 A
- Connector plug M12, 4-pole 4 A
- Connector plug M12, 8-pole 2 A
Short circuit resistance:
- Screw terminal connection 6 A gG D-fuse
- Connector plug M12, 4-pole 4 A gG D-fuse
- Connector plug M12, 8-pole 2 A gG D-fuse
Required rated short-circuit current: 1,000 A
Ambient temperature: –25 °C … +70 °C
Wire length: max. 75 m depending in relation to the
range of ambient temperature (see image 4)
Mechanical life: > 1.000.000 operations
Input terminal wire size AWG: 14-22
Max. Torque: 7 Lb In
Use solid or stranded copper conductors only.
2.5 Safety classification
Standards: EN ISO 13849-1
B10D NC contact: 100,000
Mission time: 20 years
TF
D
10Dopop
op
n
(Determined values can vary depending on the application-specific
parameters hop, dop and tcycle as well as the load.)
If multiple safety components are wired in series, the Performance
Level to EN ISO 13849-1 will be reduced due to the restricted error
detection under certain circumstances.