Page 14
Page 14
COMPONENT DESCRIPTION
A. EVAPORATOR TEMPERATURE
SENSOR - BLUE 2 POLES CONNECTOR
- MANUAL RESET
The evaporator sensor probe is inserted into its
tube well, which is welded on the evaporator
outlet line. It detects the temperature of the
refrigerant on the way out from the evaporator
and signals it by suppying a low voltage current
flow to the P.C. Board Micro-Processor.
According to the current received, the micro-
processor let the ice maker to continue its
operations or not. In case the evaporating tem-
perature,after 10 minutes from theunit start-up,
does not go below -1°C (30°F) the evaporator
sensor signal reaching the microprocessor is
suchto stopimmediatelythe unitoperation,with
the 3rd Warning YELLOW LED that blinks.
B. WATER LEVEL SENSOR - RED TWO
POLES CONNECTOR - AUTOMATIC
RESET
Thissensorsystemconsistoftwosmallstainless
steelrodsvertically fitted on the innerfaceofthe
reservoircoverand electrically connected to the
low voltage circuit of the P.C. Board. When the
coverofthereservoirispositionedinitsplacethe
tips of both the rods dip into the reservoir water
and detects and signals its presence by supply
power back to the P.C. Board.
NOTE. In the event of shortage of water in
thereservoiror,incasethewaterusedistoo
soft (de-mineralized) to cause greater
resistence to the current flow (conductivity
lowerthan30
µ
S)thissensorsystemcauses
the shutoff of the machine, to protect it
fromrunningwithaninterruptedorinadequate
water supply.
In this situation the 5th YELLOW LED will
glow to warn of the machine shutoff and the
reason why.
C. CONDENSER TEMPERATURE SENSOR
- BLACK TWO POLES CONNECTOR -
MANUAL RESET
The condenser temperature sensor probe,
located within the condenser fins detects the
condenser temperature variations and signals
them by supplying current, at low voltage, to the
P.C. BOARD.
In relation to the different current received, the
micro processor of the P.C. BOARD supplies,
through a TRIAC, the power at high voltage to
the fan motor so that it can cool the condenser
and reduce its temperature.
In the event the condenser temperature rises
and reaches 70°C the current arriving to the
micro processor is such to cause an immediate
and total stop of the machine operation with the
glowing of the 2nd RED WARNING LED.
NOTE. To restart the unit after the shutoff
caused by the hi condenser temperature, it
is necessary to push the RE-SET button
(after having remedied to the causes of unit
stoppage) or to switch OFF and ON the
power line main disconnect Switch.
D. GEAR MOTOR ROTATION AND SPEED
SENSOR - RED FOUR POLES
CONNECTOR - MANUAL RESET
This safety device is housed on top of the Drive
Motoranddetects-basedonHallEffectprinciple
- the rotating speed and rotating direction of the
drive Motor.
Should the rotating speed drop below
1300 r.p.m. the magnitude measured by this
device is such to signal to the microprocessor to
stop the unit and light-up the 3rd YELLOW LED.
Thesamereactionoccureswhenthedrivemotor
will tend to rotate in the wrong direction
(counterclockwise) or it doesn't rotate at all.
NOTE. To restart the unit after the shutoff
caused by this safety device, it is necessary
firsttoeliminatethecausethathasgenerated
theinterventionofthedeviceandthenpress
the RE-SET push button or switch OFF and
ON the power line main disconnect switch.
E. ICEBINLEVELLIGHTCONTROL-BLACK
FOUR POLES CONNECTOR -
AUTOMATIC RESET
The electronic ice bin level control, located into
theicespout,hasthefunctiontostoptheoperation
oftheicemachine when the light beam between
the light source and the sensor gets interrupted
by the flake ice which accumulates in the spout.
When the light beam is interrupted the 1st RED
LEDlocatedinthefrontoftheP.C.BOARDgoes
off; in case the light beam gets interrupted for as
longas6seconds,theicemachinestopswiththe
glowing-up of the 6th YELLOW LED to monitor
the full ice bin situation.
The 6 seconds of delay prevents that any
minimuminterruptionofthelightbeamduetothe
regular ice chuting through the ice spout may
stop the operation of the unit.
As soon as the ice is scooped out (with the
resumption of the light beam between the two
infraredsensoroficelevel control)theREDLED
lights up and after 6 seconds the ice machine
resume its operation with the simultaneous
extinguishing the 6th YELLOW LED.
F. ICE/WATER OPTICAL DISPENSING
DEVICE - BLUE FOUR POLES CONNECTOR
Located on the front of the dispensing area it
consists of the combination of an infrared
Transmitter and Receiver.
When a glass or a carafe is placed in front of the
Infrared sources, the optical device transmits a
signal to the PC Board that is equivalent to
activate the dispensing drive motor which, in