Seiwa LKBB User manual

Thank you very much for purchasing our LED lighting fittings.
Please read this instruction manual to use the product properly.
1) Prior to installing the fitting, check if the product is as per your order.
2) Check for a loose or damaged part due to an accident in transit, etc.
1)
2) Usable in hazardous areas where there may be deflagrative or flammable dust.
- Installation work should be done properly by a qualified electrician in accordance with the related laws and the instruction manual.
- For safety, Installation work should be done by at least two workers.
■
Direct Mount Type, Pipe Pendant Type, Bracket Type (Fig. 1: Example LKBB070541/LKBB070546)
100-242V AC
(50/60Hz)
0.41-0.18A
40.0W
0.33-0.15A
Input Voltage
(Frequency)
Input
Current
Power
Consumption
Lamp house replacemen
Special direct mount
Stanchion
Direct mount
Pipe pendant
The electrical characteristic data is given below (the figure in angle brackets < > in the Installation Type column is asign placed at the end of
each model code to represent the type of installation.)
Lamp house replacemen
Special direct mount
Direct mount
Pipe pendant
Bracket
LKBB07051
LKBB07044
LKBB07052
Model
<0>
LKBB07045
LKBB07041
<6>
<1,1H,2,2H>
<0>
11E0200005A11
To be conserved
Instruction Manual
Prior to use
Dust Ignition proof type LED Lighting Fittings
LKBB07054
IP
rating
Type of
protection
Bracket
<6>
<1>
<2>
33.0W
SDP-13
IP65
Names of the Components and Installation Method
LKBB
After installing the product, be sure to hand this manual over to the user of the product.
Performance
LKBB07055
LKBB07042
<2>
Installation Type
<1>
Stanchion
<1,1H,2,2H>
Fig. 1
Fitting
Holes
Holes
Interval 500
O Ring
Terminal Box
Terminal Box Cap
Locking Screw
Suspension Pipe B
Suspension Pipe A
Suspension Bracket
Rubber Plug
Locking Nuts
Pipe Pendant
Bracket Pipe A
Bracket Pipe B
Bracket Type
Side view
Suspension Pipe A
End with a rubber plug
Suspension Pipe B
Locking Nut
Hinge Shaft
Suspension HooK
O Ring
Red Mark
Locking Screw
Terminal Box Cap Cross
Section
Fastening Ring
Suspension Hook
Power Supply Side
- -

Fix the terminal box and the suspension bracket on the mounting surface securely.
NB: For the bracket type, fix it on a vertical mounting surface securely.
Screw suspension pipes A and B into the fitting.
Lift the fitting, fit suspension pipe B to the suspension bracket.
Completely fix the stand pole with the support (not supplied) and prescribed terminal box mounting screws.
Fit the terminal box cap onto the terminal box and turn the fastening ring 90 degrees until the projection aligns with the red mark.
Tighten the locking screws.
Tighten the fixing nuts on the suspension hardware.
NB1: The pipe, locking screws and cross recessed hexagon blots should be tightened securely. Otherwise, the lamp house might fall.
NB2: Caulk the threaded connections.
NB3:
For the direct mount and Pipe pendant type, The lamp house may be installed within an angle range of 0° (down).
NB4:
■
Stanchion Type (Fig. 2: Example LKBB070551)
Fix the clamp with the clamp fixing screw.
Referring to Fig. 2, pass the electric wires (white and red:
power wires, black: grounding wire) through the stand pole
and insert the pole into the terminal box in the arrow
direction.
Tighten the locking screw on the terminal box. Confirm that
the box does not turn.
The positioning box is not a supplied item. Fit the short nipple
and positioning box referring to the attached Short Nipple
Istallatio Maual.
Fix the stand pole with the support (not supplied) and the
positioning box mounting screws completely. (The pole has
four 8 mm-diameter holes arranged at pitches of 85x85 mm
for the positioning box mounting screws.)
After putting the fastening ring around suspension pipe A, screw the terminal box cap onto the suspension pipe. Confirm that the O ring is in
the groove of the terminal box.
Connect the power and grounding wires inside the terminal box and conduct insulation treatment on them. Then, remove the suspension
hook and place the hook in the terminal box cap. The black and white wires are power wires. You need not care about polarity. The green
wire is a grounding wire.
For the bracket type, the lamp house may be installed within an angle range of 0° (down) to 45° (oblique). For the direct mount and
Pipe pendant type, The lamp house may be installed within an angle range of 0° (down).
In the case of the bracket type, install the fitting with the hinge shaft down according to the drawing. Otherwise, a failure might occur.
拡大図
Clamp Fixing Screw
Clamp
Screw G3/4
Support (not supplied)
Locking Bolts
Clamp Holder
Stand Pole
Joint box (option)
Short Nipple G3/4
Enlarged View
Terminal Box
Fig. 2
- -

■
Special Direct Mount Type(Fig. 3: Example LKBB070510)
Fix the fitting on the mounting surface firmly.
Attach the flexible fitting to the terminal box.
NB:
Lamp mounted on a wall surface Lamp mounted on an inclined surface
■
Lamp house replacemen type(Fig. 4: Example LKBB07052)
NB1:
NB2:
■Attachment of Cable Gland (Fig. 5: Example ZCGS-22B)
NB1:
NB2:
NB: Waterproof the threaded connection.
Fasten the cable retaining plate on the cable fixing member.
NB:
Confirm that the cable does not move.
Tighten the locking screw on the body to prevent the cable fixing member from loosening.
Attach the protective tube to the connecting member, then screw the cover into the body securely.
NB1: Confirm that the cover is invisible from the O ring. If visible, the waterproofness is not ensured.
NB2: The cable gland should be a product as specified by SEIWA.
Be sure to remove the locking screw on the cable gland
body before separating the cable gland into parts.
Screw in the lock nut on the body until it touches the body
flange.
Fasten the gland onto the entry of the terminal box (or the
device to which the gland is to be attached) until the body
stops.
Tighten the lock nut toward the terminal box (or the device to
which the gland is to be attached).
Push the washer, rubber sleeve, and washer into the body and
pull out the cable to a sufficient length for cable connection.
Screw the cable fixing member into the body.
Separate the cable gland into parts as shown in Fig. 5 and pass
the cable through the cable gland in the following order:
cover, connecting member, cable fixing member, washer,
rubber sleeve, washer, body, and lock nut.
The cable should be a round cable applicable to the rubber
sleeve. For information on cables applicable to the cable
gland, see the catalog.
If the lighting fitting is used in a place where water may splash on it,
waterproof the joint between the fitting and the existing suspension
pipe.
Before installing the lighting fitting, check the existing piping
(including the pipe and junction box) for rust.
Referring to Fig. 3,pass the electric wires (white
and black: power wires, green: grounding wire)
through the flexible fitting and attach the flexible
fitting to the retainer (lamp house).
Conduct insulation treatment on the electric wires
(white and black: power wires, green: grounding
wire) inside the terminal box.
When the special direct mount type lamp is
mounted on a wall or inclined surface, confirm
that the hinge shaft is down. Otherwise, a failure
might occur.
Referring to Fig. 4,pass the cable from the lighting fitting through the
existing suspension pipe and terminal box and attach the pipe and
box to the fitting.
Connect the wires (white and red: power wires, black: grounding
wire) inside the existing junction box.
Terminal Box
Holes
Holes
Interval 500
Flexible Fitting
Wall Surface
Hinge Shaft
Hinge Shaft
Inclined Surface
Fig. 3
Fig. 4
Fitting
Existing suspension hardware
Existing junction box
Existing suspension pipe
Cable
ձ
ձղ
ձ
Fitting
Fig.5
Lock nut
2-Washers
O ring
Terminal box
Locking screw
Body
Rubber sleeve
Cable fixing member
2-Cable fixing screws
Cable retaining plate
O ring
Connecting member
Cable gland (ZCGS)
Cover
Cable (round)
- -

The LED lamp is turned on by applying the rated voltage to the power cable of the product.
■Inspection 1)
2) Prior to maintenance, be sure to turn off the power.
3) Carry out maintenance properly in accordance with the related law and regulations.
4) If a repair is needed, consult us.
1) In the period when the product is in use, never disassemble it.
2) For disposal of the product, follow the regulations and rules of your local government.
When reordering, please let us know:
・Drawing or drawing No. for the delivered product
・Manufacturing lot number on the nameplate
1.
2. Prior to maintenance or inspection, be sure to turn off the power.
3. Confirm that the screws and bolts are fastened properly and tightly.
4. In the case of the stanchion type, be sure to provide a support at least 800 mm above the bottom of the pole.
5.
6.
7.
8. The supply voltage variation should be within ±6% of the rating.
9. Close unused entries of the terminal box with plugs.
10.
11.
12.
Prior to maintenance or inspection, be sure to turn off the power.
13. To prevent shortening of the service life, avoid turning on the fitting in direct sunlight.
14. To avoid noise or malfunctioning, don't use a radio, television or wireless infrared remote control near the fitting.
15.
16.
17.
18.
Do’t ope the product. Otherwise, a eplosio, fire, or electric shock ight result.
19. The cable gland must be a product specified by SEIWA.
20. The LED lamp and the power supply unit cannot be replaced.
21. Do’t look straight at the LED lap. It ca daage our ees.
The product must be used in a location where it can be used safely according to its explosion protection type (indicated on the body).
Disassembly and Disposal
Reordering
If the above information is unavailable, give us any material showing the appearance of the product or details of the product specification
(dimensions, mounting interval, lamp type, etc.).
The product should be oriented within an angle range of 0 ° (down) to 90 ° (horizontal). Don ’t install the product vertically with its
longitudinal side in a vertical position. If it is installed vertically, an insulation failure or electric shock might result.
For outdoor use, waterproof the screwed portion of the conduit, the cable entry fittings and the joint with the stand pole to prevent
rainwater infiltration.
When installing the fitting, be sure to connect external wires inside a specified part of the fitting. Don't open any other part of the fitting
unless necessary.
In cleaning the fitting, gently wipe with water or mild detergent. Don’tuse thinner, benzene or alkaline detergent. Such
chemicals might cause discoloration or deterioration in quality and strength, resulting in a damage.
How to Use
Maintenance
The ambient temperature should be within the range of -20°Cto +40°C. The use of the product out of this range may shorten the service
life.
In grounding work, be sure to follow the technical standards for electrical equipment and explosion-protected equipment of your country.
Inadequate grounding might cause an explosion, fire or electric shock.
For white LED lamps, the luminescent color and brightness may vary with individual LEDs because of their nature. Also note that the rate
of attenuation with time varies with individual LED lamps.
The product must be mounted on a sturdy wall surface or structure which is vibration-free and less susceptible to damage. Otherwise, it
might fall or be damaged.
For use in an unfavorable location (a very hot, cold or humid place or a place in which there is strong wind or vibration, a salt damage
environment or a dusty or corrosive gas atmosphere), a special countermeasure should be taken.
Fig.6
Nameplate
CAUTIONS
- -

- Prior to use, please read the safety precautions and instruction manual thoroughly to use the product properly.
-
- Please keep the manual in a handy place for later reference.
●The various marks have the following meanings:
11E0000712D11
Safety Precautions
To be conserved
L照6
Be sure to turn
off the power.
In grounding work, be sure to follow the technical standards for electrical equipment and explosion-protected equipment of
your country. Inadequate grounding might cause an explosion, fire or electric shock.
The parts once removed for cleaning should be replaced properly according to the instruction manual.
An improperly placed part might cause the product to explode or fall, resultng in an injury or property damage.
Do’t ope LED lap protetie oers suh as the frot glass ad glass gloe.
Do’t touh a LED lap, otherise a alfutio or lightig failure ight our.
Do’t ed, tist or pull the poer ale y fore.
Inadequate handling of the cable might damage it and result in a fire or electric shock.
Do’t oert the produt.
Conversion might cause the product to fall or result in a fire or electric shock.
When leading the power cable into the product through a conduit or the like, waterproof the connection and joint
adequately to prevent water infiltration. Inadequate waterproofing might cause a fire or electric shock.
WARNING
If you use a product in a hazardous location where there is a gaseous, steamy or dusty atmosphere, it should be of the
flameproof type suitable for the location. Use of an unsuitable type apparatus might cause an explosion or fire.
The ambient temperature should be within the operating temperature range specified in the instruction manual. If the
product should be used at a temperature higher than specified, an early lighting failure or malfunction might occur or an
explosion or fire might result.
If a product must be oriented in a specific manner for use, install it properly according to the marking on its body or the
instruction manual. Otherwise, an explosion, fire or electric shock might result.
Don’t touch.
Be sure to
ground.
Prohibited.
Be careful of
ignition.
After installing the product, be sure to hand the safety precautions and instruction manual over to the user of the product.
Caution
WARNING:
CAUTION:
Improper handling may lead to a human death or serious bodily injury.
Improper handling may lead to a bodily injury or property damage.
Disassembly &
conversion
prohibited.
Don’t use near
a water source.
Be sure to
follow the
instructions.
When leading the power cable into the product, be sure to follow the technical standards for electrical equipment and
explosion-protected equipment of your country. Inadequate cable connection or waterproofing might cause an explosion,
fire or electric shock.
For electrical connections, use crimp-type terminals, etc. to secure the connections and conduct insulation treatment. An
inadequate connection or inadequate insulation might cause an imperfect contact, leading to an explosion, fire or electric
shock.
Do’t oer the produt ith a iflaale aterial suh as loth or paper or put aythig i the produt.
Such a material or thing might cause an explosion or fire.
- 1/2 -

Ni-Cd
Ni-MH
L照6
Please note that the above addresses and phone numbers may be changed.
Installation of the product should be carried out by a qualified person.
Installation by an unqualified person is legally prohibited.
Don’t use the product in a strong corrosive gas atmosphere which contains hydrochloric acid or chlorine gases or the like.
Use in a corrosive gas atmosphere might cause the product to corrode and fall, resulting in an injury.
Do’t use the produt at a oltage other tha the rated oltage idiated o the aeplate.
Otherwise, breakage, fire or electric shock might result.
Before cleaning, be sure to turn off the power.
Otherwise, a fire or electric shock might result.
CAUTION
Any product not marked as a product for outdoor use should not be used outdoors or in a humid place or near a water
source. Its use in such a place might cause a fire or electric shock.
The product should be mounted on a surface robust enough to support its weight, properly according to the instruction
manual. Improper installation might cause the product to fall or result in an electric shock or injury.
CONTACT DETAILS
Never touch LED light sources and their surroundings.
The light sources and their surroundings are very hot, so an accidental touch might cause a burn.
A lighting fitting has a service life. A product which has been used for eight to ten years may have degraded internal parts
even if it looks normal. For safety and energy saving, we recommend you check and replace it. The LED module design life is
6,0000 hours (different from the lighting fitting life) when used at an ambient temperature of 30°C, 10 hours per day, 3,000
hours per year. If used at a higher temperature or more hours per year, the life would be shortened. Have a specialist
inspect the product every three years. If used for an extended period without inspection, a smoke, fire, or electric shock
might result.
Fax
2-19-6 Yanagibashi, Taito-ku, Tokyo 111-0052 Japan
+81 3 5833 8971
+81 774 58 2034
+81 3 5833 8946
Tokyo Branch
Fax
SEIWA ELECTRIC MFG.CO., LTD.
Phone
Phone
36 Shinike, Terada, Joyo, Kyoto Pref. 610-0192 Japan
Head Office
+81 774 55 8181
For further information on the product, contact any of our offices listed below (if you like to make an inquiry, let us know the model name
indicated on the product nameplate).
To ensure brightness and safety, carry out periodical cleaning and inspection.
If you find a problem, discontinue the use of the product and have it repaired by a specialist.
For a product marked with a frequency, don’t use the product at a frequency other than 50 or 60 Hz (local power supply
frequency). Use at a wrong frequency might cause a fire.
JBRC Japan Portable Rechargeable Battery Recycling Center
Phone +81 3 6403 5763
Resycling
Please bring used Secondary batteries to the recycling station for effective use of precious
resources and global environment conservation.
If you continue to use the product in an abnormal condition (smoke, odor, etc.), an explosion, a fire or electric shock might
result. If you detect an abnormality, immediately turn off the power switch. Confirm that the abnormal condition has been
eliminated and make a repair call.
WARNING
- 2/2 -
This manual suits for next models
8
Table of contents
Other Seiwa Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Feit Electric
Feit Electric STRP/2X2/4WY/LED Important Safety Instructions and Installation Guide

KSR
KSR KSR9846 Installation sheet

Fox-Lux
Fox-Lux FXEXB Installation, Maintenance and Servicing Notes

XanLite
XanLite LSAK3SOLAR manual

Lightolier
Lightolier Lighting Systems EC2-8 Specification sheet

Chauvet
Chauvet DMX-355 user manual