MI00596-0-EN INSTALLATION MANUAL 1/4
INSTALLATION MANUAL
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287
WARNING: The full content of this manual must be read before any operation. The module must only be used by
qualied electricians. Specic documentation is available via QR-CODE shown on page 1.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be surrendered to a collection centre
authorized to recycle electrical and electronic waste.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to
electrostatic discharges. Take appropriate measures during any operation.
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the
instrument or the connected equipment. The warranty shall become null and void in the event of improper use or
tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if
the instructions contained in this manual are not followed.
CONTACT INFORMATION
Technical support [email protected] Product information [email protected]
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies.
Stated data may be modied or supplemented for technical and/or sales purposes.
R-32DIDO
R-32DIDO-P
DOCUMENTATION
R-32DIDO
DOCUMENTATION
R-32DIDO-P
MI00596-0-EN INSTALLATION MANUAL 2/4
MODULE LAYOUT
Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
LED STATUS LED meaning
PWR On Device powered
Off Device not powered
IO1/IO32 On Digital input/output active
Off Digital input/output not active
OUT
SUP
On Digital inputs/outputs powered
Off Digital inputs/outputs not powered
STS
(Status)
On IP address set
Flashing Waiting for the IP address from the DHCP
COM
(R-32DIDO-P version only)
Off No Pronet communication
Flashing Pronet communication present
FAIL On Digital output in FAIL
Off Digital output OK
RX
(R-32DIDO version only)
On RS485 port wiring error
Flashing Reception of data packet completed on RS485
TX
(R-32DIDO version only) Flashing Transmission of data packet completed on RS485
ETH TRF (Yellow) Flashing Packet transit on Ethernet port
ETH LNK (Green) Flashing The Ethernet port is connected (LINK)
SIGNALS VIA LED ON FRONT PANEL
CERTIFICATIONS
https://www.seneca.it/products/r-32dido/doc/CE_declaration
TECHNICAL SPECIFICATIONS
32.2 mm
mm
0.09
106.6 mm
MI00596-0-EN INSTALLATION MANUAL 3/4
INSULATION
POWER SUPPLY Voltage: 10÷40Vdc; 19÷28Vac; 50÷65Hz; Absorption: 3W max; Dissipation: 6.5W max
ENVIRONMENTAL
CONDITIONS
Operating temperature: from -25°C to +65°C
Humidity: 10% ÷ 90% non condensing.
Storage temperature: from -30°C to +85°C
Protection rating: IP20
CONFIGURATION With integrated WEB Server
CONNECTIONS/
COMMUNICATION
PORTS
3.5 mm pitch terminal block, 1.5 mm2 max cable section
1 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-1 model)
2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-2 model)
1 RS485 port on terminals 23-24-25 (only R-32DIDO-1/ R-32DIDO-2 versions)
DIGITAL INPUTS
Number of channels: 32; Voltage: Threshold ON: >9V; Threshold OFF: < 4 V; Vmax: 24 V;
Impedance 9kΩ
Individually congurable
DIGITAL OUTPUTS Number of channels: 32, MOSFET, PNP; Max voltage/current: 0.2 A / 24 V
Individually congurable
COUNTERS: Number of counters: 32 at 32 bit, maximum speed: 50 Hz
40
41
42
....
63
64+
65-
+
LOAD
LOAD
LOAD
LOAD
LOAD
12/24V
18+
19-
ELECTRICAL CONNECTIONS
21
22
20
–/
+ /
23 B(-)
24 A(+)
25 GND
POWER SUPPLY RS485 SERIAL PORT
The power supply must be sized according to the expected load at the outputs. Terminals 18-64 and 19-65 can be connected
together on the same power supply.
*For correct instrument operation, power the I/Os via the I/O Ext Supply 1 and 2 terminals at the same time.
DIGITAL INPUTS (PNP)
Inputs from 9 to 32
DIGITAL INPUTS (PNP)
Inputs from 1 to 8
DIGITAL OUTPUTS (PNP)
Outputs from 9 to 32
DIGITAL OUTPUTS (PNP)
Outputs from 1 to 8
The upper power supply limits must not be exceeded, as this could cause serious damage to the module.
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).
CAUTION
CAUTION
CAUTION
Connection to the RS485 port.
Polarity is not standardised; in some devices of other brands it
may be inverted.
PWR
1500 Vac
DIGITAL
INPUT/OUTPUT
USB
RS485
ETH1
PORT1
ETH2
PORT2
PWR AUX
*** *
10
11
12
....
17
18+
19-
+
12/24V
64+
65-
40
41
42
....
63
64+
65-
+
12/24V
18+
19-
10
11
12
....
17
18+
19-
+
LOAD
LOAD
LOAD
LOAD
LOAD
12/24V
64+
65-
MI00596-0-EN INSTALLATION MANUAL 4/4
DAISY-CHAIN (R-32DIDO-2 / R-32DIDO-2-P ONLY)
IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES
Using the daisy-chain connection it is not necessary to use switches to connect the devices.
The following examples show the correct connections.
There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be
connected eliminating any loops. The following examples show the incorrect connections.
The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a
power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be acces-
sible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires
that the sum of the lengths of the two cables connected to the switched off module is less than 100m.
MODULE 1 MODULE 2 MODULE 3
MODULE 1 MODULE 2 MODULE 3
ETHERNET CONNECTION RULES
For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.
CAT6 for industrial environments.
FACTORY IP ADDRESS
The default module IP address is static: 192. 168. 90. 101
WEB SERVER
To access the maintenance Web Server with the 192.168.90.101 factory IP address
(Default user: admin; Default password: admin) http://192.168.90.101
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
MODULE 1 MODULE 2
LOOP
MODULE 3
MODULE 1
LOOP
DIP- SWITCH SW1: through DIP-SWITCH-SW1 it is possible to set the IP conguration of the device:
DESCRIPTION DIP 1 DIP 2
To obtain the conguration from the Flash memory, both SW1 DIP
switch selectors must be set to OFF
To reset the device to factory settings both SW1 DIP switches must
be set to ON
To force the device's IP address to the standard value of SENECA
Ethernet products: 192.168.90.101
Reserved
DIP - SWITCH SETTINGS
The DIP-switch settings are read only at boot time. At each change, perform a restart.
DIP-SWITCHES are located on the back of the device.
To access the DIP-SWITCH it is necessary to remove the bottom of the instrument.
CAUTION
CAUTION
WARNING
WARNING

Other manuals for R-32DIDO

1

This manual suits for next models

3

Other Seneca Control Unit manuals

Seneca Z-8AI User manual

Seneca

Seneca Z-8AI User manual

Seneca Z Series User manual

Seneca

Seneca Z Series User manual

Seneca Z-TWS11 User manual

Seneca

Seneca Z-TWS11 User manual

Seneca MyBoat-WR User manual

Seneca

Seneca MyBoat-WR User manual

Seneca MyAlarm3 Cloud User manual

Seneca

Seneca MyAlarm3 Cloud User manual

Seneca Z-PC Z-TWS5 User manual

Seneca

Seneca Z-PC Z-TWS5 User manual

Seneca 85389091 User manual

Seneca

Seneca 85389091 User manual

Seneca Z-PC SERIES User manual

Seneca

Seneca Z-PC SERIES User manual

Seneca Z Series User manual

Seneca

Seneca Z Series User manual

Seneca Z-8TC-LAB User manual

Seneca

Seneca Z-8TC-LAB User manual

Seneca Z-PASS1 User manual

Seneca

Seneca Z-PASS1 User manual

Seneca Z-LINK1-LO User manual

Seneca

Seneca Z-LINK1-LO User manual

Seneca Z-4DI-2AI-2DO User manual

Seneca

Seneca Z-4DI-2AI-2DO User manual

Seneca R-8AI-8DIDO-P User manual

Seneca

Seneca R-8AI-8DIDO-P User manual

Seneca Z-PC SERIES User manual

Seneca

Seneca Z-PC SERIES User manual

Seneca VPN BOX 2 User manual

Seneca

Seneca VPN BOX 2 User manual

Seneca Z113S User manual

Seneca

Seneca Z113S User manual

Seneca Z-8AI User manual

Seneca

Seneca Z-8AI User manual

Seneca Z109REG2 User manual

Seneca

Seneca Z109REG2 User manual

Seneca Z-4TC User manual

Seneca

Seneca Z-4TC User manual

Popular Control Unit manuals by other brands

PIETRO FIORENTINI SCN Technical manual

PIETRO FIORENTINI

PIETRO FIORENTINI SCN Technical manual

Texas Instruments AN-2166 LMZ10500 manual

Texas Instruments

Texas Instruments AN-2166 LMZ10500 manual

NI REM-11190 Getting started guide

NI

NI REM-11190 Getting started guide

CALEFFI SATK Series Installation, operation and maintenance manual

CALEFFI

CALEFFI SATK Series Installation, operation and maintenance manual

Gi MP48 DF installation manual

Gi

Gi MP48 DF installation manual

golmar M-IP-GB2 user manual

golmar

golmar M-IP-GB2 user manual

Siemens SIMATIC ET 200SP manual

Siemens

Siemens SIMATIC ET 200SP manual

Omron CJ1W-NC214 - datasheet

Omron

Omron CJ1W-NC214 - datasheet

Econ 7343 Installation & operation manual

Econ

Econ 7343 Installation & operation manual

Norgren VR10 Installation & Maintenance Instruction

Norgren

Norgren VR10 Installation & Maintenance Instruction

PIKO 35260 installation instructions

PIKO

PIKO 35260 installation instructions

DELTA DORE PACK DELTA 8000 BUS CO 1.1 Instructions for use

DELTA DORE

DELTA DORE PACK DELTA 8000 BUS CO 1.1 Instructions for use

Sit 650 DELTA Use and Installation Instructions

Sit

Sit 650 DELTA Use and Installation Instructions

Gemu 650 manual

Gemu

Gemu 650 manual

DeZurik PTW manual

DeZurik

DeZurik PTW manual

Iluminarc Ilumicode V 2.21 user manual

Iluminarc

Iluminarc Ilumicode V 2.21 user manual

ProSoft inRAx MVI56-DEM user manual

ProSoft

ProSoft inRAx MVI56-DEM user manual

ITOH DENKI POWER MOLLER PLUS SOG user manual

ITOH DENKI

ITOH DENKI POWER MOLLER PLUS SOG user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.