ITALIANO 2/8
3 current or voltage analog outputs with 12 bit resolution.
Start/end scale voltage programmable between: -10 – +10 V, 0 – +10 V or +2 – +10 V.
Start/end scale current programmable between 0 – 20 mAo4–20mA
1500V insulation between: analog outputs and remaining low voltage circuits.
Outputs protection via 400W/ms TVS transient current suppressors;
PTC load protection.
Negative common connection.
.Removable terminals with section of 2.5 mm2
Fast response time (step 10-90%): < 50 ms.
Power supply and serial connection wiring facilitated by means of a bus that can be
housed in the DIN guide.
RS485 serial communication with Modbus-Rtu protocol, maximum 64 nodes.
RS232 on frontal pane for serialserial connection l with Modbus protocol
communications and also for programming.
Insertion and extraction from bus without interruption of communication or of system
power supply.
Communication times below 10 ms (@ 38400 Baud).
Connection distance up to 1200 m.
DIP-Switch settings for Module address and Baud rate.
T H AL SPECIFICATIONSEC NIC
-10 – 10 V, 0 – 10 V, 2 – 10 V. Output impedance > 600 W
0 – 20 mA, 4 – 20 mA. Output impedance < 600 W
Number of output channels
Voltage output resolution
Current output resolution
Calibration Max: 0.2% of E.E.S., typical: 0.1% of E.E.S.
Linearity: 0.05% of Electical End Scale (E.E.S.)
Thermal stability: 0.01%/°C of E.E.S.
Calibration Max: 0.2% of E.E.S., typical: 0.1% of E.E.S.
Linearity: 0.05% of Electical End Scale (E.E.S.)
Thermal stability: 0.01%/°C of E.E.S.
Before executing any operation it’s mandatory to read all the content of this user Manual.
Only electrical-skilled technicians can use the module described in this user Manual.
No warranty is guaranteed in connection with faults resulting from improper use, from
modifications or repairs carried out by Manufacturer-unauthorised personnel on the module, or if
the content of this user Manual is not followed.
Only the Manufacturer is authorized to repair the module or to replace damaged components.