MODBUS REGISTER MAPS
INPUT REGISTERS
Data type Description Data Values
1Temperature reading signed int Actual temperature level -300—700 500 = 50,0°C
2Output value 1 unsigned int Output value 1 0—1.000 0 = 0 %
1.000 = 100 %
3Temperature alert ag unsigned int
Flag indicates that measured Temperature is
outside set alert values. Set to '1' when the
measured value is outside the Temperature alert
values dened by holding registers 13 and 14
0—1 0 = Temperature measurement OK
1 = Temperature measurement too low/high
4Temperature range limit
ag unsigned int
Flag indicates that measured temperature is
outside set range limit values. Set to '1' when
the measured temperature is outside limit range
values dened by holding registers 11 and 12
0—1 0 = Temperature range OK
1 = Temperature range too low/high
5Humidity, temperature
sensor fault unsigned int Flag that shows if the communication with
temperature & humidity sensor is lost 0—1 0 = No
1 = Yes
6—9 Reserved, return 0.
10 Relative humidity level unsigned int Actual relative humidity level 0—1.000 1.000 = 100,0 % rH
11 Reserved, returns 0.
12 Relative humidity alert ag unsigned int
Flag indicates that measured Relative humidity
is outside set alert values. Set to '1' when the
measured value is outside the Relative humidity
alert values dened by holding registers 21 and 22
0 1
0 = Relative humidity measurement OK
1 = Relative humidity measurement too low/
high
13 Relative humidity range
limit ag unsigned int
Flag indicates that measured Relative humidity
is outside set range limit values. Set to '1' when
the measured Relative humidity is outside limit
range values dened by holding registers 19 and
20
0—1 0 = Relative humidity range OK
1 = Relative humidity range too low/high
14 Humidity, temperature
sensor fault unsigned int Flag that shows if the communication with
temperature & humidity sensor is lost 0—1 0 = No
1 = Yes
15 Dew point level signed int Calculated dew point -700—700 200 = 20,0°C
16—20 Reserved, return 0.
21 CO2 level unsigned int Actual CO2 level 0—2.000 2.000 = 2.000 ppm
22 Reserved, returns 0
23 CO2 alert ag unsigned int
Flag indicates that measured CO2 level is outside
set alert values. Set to '1' when the measured
value is outside the CO2 values dened by
holding registers 25 and 26
0—1 0 = CO2 measurement OK
1 = CO2 measurement too low/high
24 CO2 range limit ag unsigned int
Flag indicates that measured CO2 is outside set
range limit values. Set to '1' when the measured
CO2 is outside limit range values set dened by
holding registers 23 and 24
0—1 0 = CO2 range OK
1 = CO2 range too low/high
25 CO2 Sensor fault unsigned int Flag that shows if the communication with the
CO2 sensor is lost 0—1 0 = No
1 = Yes
26—40 Reserved, returns 0
41 Ambient light intensity unsigned int Measured ambient light intensity 0—32.000 1.000 = 1.000 lux
42 Active / Standby unsigned int
Active or Standby indication according the
Active / Standby light level dened by holding
registers 35 and 36. If the measured light level
is between the two levels the indication is 0 (Low
light intensity)
0—2
0 = Low light intensity
1 = Active
2 = Standby
43 Ambient light sensor fault unsigned int Flag that shows if the communication with the
ambient light sensor is lost 0—1 0 = No
1 = Yes
RMFPM-2R MULTIFUNCTIONAL ROOM