www.sentera.eu
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 9 - 10
back to the table of contents
Fig. 5 P1 header
12345
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
12345
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
MODBUS REGISTER MAPS
MODBUS REGISTERMAP
INPUT REGISTERS
Input Registers Data type Description Data Values
1Temperature reading signed int Actual temperature level -300—700 500 = 50,0°C
2Output value 1 (T) unsigned int Output value 1 (T) 0—1.000 0 = 0 %
1.000 = 100 %
3Temperature alert ag unsigned int
Flag indicates that measured Temperature is outside set alert values. Set to
'1' when the measured value is outside the Temperature alert values dened
by holding registers 13 and 14
0—1
0 = Temperature measurement OK
1 = Temperature measurement too low/
high
4Temperature range limit ag unsigned int
Flag indicates that measured temperature is outside set range limit
values. Set to '1' when the measured temperature is outside limit range
values dened by holding registers 11 and 12
0—1 0 = Temperature range OK
1 = Temperature range too low/high
5Humidity, temperature sensor fault unsigned int Flag that shows if the communication with temperature & humidity sensor
is lost 0—1 0 = No
1 = Yes
6—9 Reserved, return 0
10 Relative humidity level unsigned int Actual relative humidity level 0—1.000 1.000 = 100,0 % rH
11 Output value 2 (rH) unsigned int Output value 2 (rH) 0—1.000 0 = 0 %
1.000 = 100 %
12 Relative humidity alert ag unsigned int
Flag indicates that measured Relative humidity is outside set alert
values. Set to '1' when the measured value is outside the Relative
humidity alert values dened by holding registers 21 and 22
0—1
0 = Relative humidity measurement OK
1 = Relative humidity measurement too
low/high
13 Relative humidity range limit ag unsigned int
Flag indicates that measured Relative humidity is outside set range limit
values. Set to '1' when the measured Relative humidity is outside limit
range values dened by holding registers 19 and 20
0—1 0 = Relative humidity range OK
1 = Relative humidity range too low/high
14 Humidity, temperature sensor fault unsigned int Flag that shows if the communication with temperature & humidity
sensor is lost 0—1 0 = No
1 = Yes
15 Dew point level signed int Calculated dew point -700—700 200 = 20,0°C
16—50 Reserved, return 0
HOLDING REGISTERS
Holding Registers Data type Description Data Values
1 Device slave address unsigned int Modbus device address 1—247
default: 1
2Modbus baud rate unsigned int Modbus communication baud rate 0—6
default: 2
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400
4 = 57.600
5 = 115.200
6 = 230.400
3Modbus parity unsigned int Parity check mode 0— 2
default: 1
0 = 8N1
1 = 8E1
2 = 8O1
4Device type unsigned int Device type. Read only DSTHG-2 = 1.632
DSTHF-2 = 1.633
5 HW version unsigned int Hardware version of the device. Read only XXXX 0x0100 = HW version 1.0
6 FW version unsigned int Firmware version of the device. Read only XXXX 0x0200 = FW version 2.2
7 Reserved, returns 0
8 Modbus safety timeout unsigned int After time with no Modbus communication,
outputs are set to 0.
0—60
default: 0 60 = 60 minutes
9Modbus network resistor
termination (NBT) unsigned int Set device as end device of the line / or not by
connecting NBT
0—1
default: 0
0 = NBT disconnected
1 = NBT connected
10 Modbus registers reset unsigned int
Resets Modbus Holding registers to default
values. When finished this register is
automatically reset to '0'
0—1
default: 0
0 = Idle
1 = Reset Modbus Registers
11 Minimum temperature range unsigned int
Minimum value of temperature range, cannot
be set higher than maximum temperature
range minus 5°C
-300 - (Max-50)
default: 0 100 = 10,0°C
12 Maximum temperature range unsigned int
Maximum value of temperature range, cannot
be set less than minimum temperature range
plus 5°C
(Min+50)—700
default: 500 500 = 50,0°C
13 Minimum temperature alert unsigned int Minimum temperature alarm value
Min. temperature range —Max.
temperature alarm
default: 0
500 = 50,0°C
14 Maximum temperature alert unsigned int Maximum temperature alarm value
Min. temperature alarm —Max.
temperature range
default: 500
500 = 50,0°C
15—18 Reserved, return 0
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER