6Revision – MOVIMOT® MM..D with AS-Interface and DRS/DRE/DRP AC Motor
2Motor with operating point 230 V / 60 Hz
Technical Data
2.3 Motor with operating point 230 V / 60 Hz
MOVIMOT®type MM 03D- 233-
00
MM 05D- 233-
00
MM 07D- 233-
00
MM 11D- 233-
00
MM 15D- 233-
00
MM 22D- 233-
00
Part number 18215084 18215092 18215106 18215114 18215122 18215130
Size 1 2
Apparent output power at
Vline = AC 200 – 240 V
SN1.0 kVA 1.3 kVA 1.7 kVA 2.0 kVA 2.9 kVA 3.4 kVA
Supply voltages
Permitted range
Vline AC 3 x 200 V / 230 V / 240 V
Vsupply = AC 200 V –10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz ±10%
Nominal line current
(at Vline = AC 230 V)
Iline AC 1.9 A AC 2.4 A AC 3.5 A AC 5.0 A AC 6.7 A AC 7.3 A
Output voltage VO0 – Vline
Output frequency
Resolution
Operating point
fo2 – 120 Hz
0.01 Hz
230 V at 60 Hz
Nominal output current INAC 2.5 A AC 3.2 A AC 4.0 A AC 5.5 A AC 7.3 A AC 8.7 A
Continuous output current
with option
MLK30A AC 2.5 A AC 3.2 A AC 4.0 A AC 5.5 A AC 7.3 A AC 8.7 A
MLK31A AC 2.5 A AC 3.2 A AC 4.0 A AC 4.6 A AC 6.2 A AC 8.0 A
Motor power S1 PMot
0.37 kW
0.5 HP
0.55 kW
0.75 HP
0.75 kW
1.0 HP
1.1 kW
1.5 HP
1.5 kW
2.0 HP
2.2 kW
3.0 HP
PWM frequency 4 (factory setting) / 8 / 161)kHz
1) 16 kHz PWM frequency (low-noise): When DIP SWITCH S1/7 is set to ON, the units operate at a PWM frequency of 16 kHz (low noise)
and switch back in steps to lower switching frequencies depending on the heat sink temperature and the load.
Current limitation Imax Motive: 160% with
Regenerative: 160% with
Max. motor cable length 15 m when the MOVIMOT®inverter is installed close to the motor (with SEW hybrid cable)
External braking resistor Rmin 150 Ω68 Ω
Interference immunity Meets EN 61800–3
Interference emission with
MLK..
Complies with category C3 according to EN 61800-3 (limit class A to EN 55011 and EN 55014)
Ambient temperature with
option
MLK30A –25 – +40 °C depending on the motor, PNreduction: 3% INper K to max. 60 °C
MLK31A –25 – +40 °C depending on the motor,
PNreduction: 3% INper K to max. 60 °C
–25 – +40 °C
Climate class EN 60721-3-3, class 3K3
Storage temperature2)
2) If the unit is stored for a long time, connect it to the supply system voltage for at least 5 minutes every 2 years. Otherwise, the unit's
service life may be reduced.
–30 to +85 °C (EN 60721-3-3, class 3K3)
Maximum permitted vibra-
tion and shock load
according to EN 50178
Degree of protection
(depending on the motor)
IP54, IP55, IP65 (optional, specify when ordering)
IP67 (only possible for inverter with connection box)
Duty type S1 (EN 60149-1-1 and 1-3), S3 max. cycle duration 10 minutes
Cooling type (DIN 41751) Self-cooling
Installation altitude h≤1000 m: No reduction
h > 1000 m: INreduction by 1% per 100 m
h > 2000 m: Vsupply reduction by AC 3 V per 100 m, overvoltage class 2 according to DIN 0110-
1
hmax = 4000 m, see chapter "Installation altitudes above 1000 m asl"
Required preventive mea-
sures
Grounding the unit