SFA Smart Control Box User manual

Smart Control Box
LIVBOITSMART
07.2022
Installation and operating manual

EN
CONTENTS
1. SAFETY .......................................................................................................................17
1.1 Identication of warnings ............................................................................................17
1.2 General points...................................................................................................................17
2. TRANSPORT/DISPOSAL .........................................................................................17
2.1 Transport.............................................................................................................................17
2.2 Disposal...............................................................................................................................17
3. DESCRIPTION............................................................................................................17
3.1 Application.........................................................................................................................17
3.2 Technical data of the control box .............................................................................17
3.3 Technical data of the detection device...................................................................17
3.4 Dimensions.........................................................................................................................17
4. INSTALLATION ..........................................................................................................17
4.1 Wall mounting...................................................................................................................17
4.2 Connection of the oat (Sanifos) and pump cables..........................................17
4.2.1 Preparationoftheconductivewires ................................................................................... 17
4.2.2 Connectorswiringforpumps(Sanipump) ...................................................................... 17
4.2.3 Connectorswiringforoats(Sanifos) ............................................................................... 18
4.2.4 Usingtheterminalblocks ......................................................................................................... 18
4.2.5 ConnectiontotheSmartControlBox................................................................................ 19
4.3 Electrical connection......................................................................................................19
4.4 Connecting the wired external alarm box .............................................................19
4.5 Connection to the BMS .................................................................................................19
5. COMMISSIONING.....................................................................................................20
5.1 Start-up conguration................................................................................................. 20
5.2 Checks to be carried out for the commissioning
of a Sanifos lifting station .......................................................................................... 20
6. OPERATION ..............................................................................................................20
6.1 Presentation of the front of the Box...................................................................... 20
6.1.1 Keyidentication .........................................................................................................................20
6.1.2 Operatinglights............................................................................................................................20
6.2 Using the control box .................................................................................................. 20
6.2.1 Onscreendisplay ........................................................................................................................20
6.2.2 Pumpactivation/deactivation ...............................................................................................20
6.2.3 Navigatingthemenu................................................................................................................... 21
6.3 Presentation of the menus...........................................................................................21
6.3.1 LanguageMenu ............................................................................................................................. 21
6.3.2 LogsMenu........................................................................................................................................ 21
6.3.3 SettingsMenu................................................................................................................................ 22
6.4 Remote wired alarm box .............................................................................................23
6.4.1 Technicaldata................................................................................................................................ 23
6.4.2 Dimensions...................................................................................................................................... 23
6.4.3 Installation ....................................................................................................................................... 23
6.4.4 Operation......................................................................................................................................... 23
6.5 SFA connnect (optional) .............................................................................................23
7. SHUTDOWN ..............................................................................................................23
8. MAINTENANCE ........................................................................................................23
8.1 Resetting the pump log ...............................................................................................23
8.2 Maintenance update......................................................................................................24
9. FAULT FINDING........................................................................................................24
10. FOR PROFESSIONALS ...........................................................................................24
10.1 Return to the start-up screen ....................................................................................24
10.2 Explanation of the LEDs on the electronic board .............................................24
10.3 Learning loops .................................................................................................................24
11. GUARANTEE.............................................................................................................24

EN
17
1. SAFETY
1.1 IDENTIFICATION OF WARNINGS
Meaning
DANGER
This term denes a high risk of danger, which can
lead to death or serious injury, if not avoided.
WARNING
This term denes a medium risk of danger, which can
lead to serious or minor injury, if not avoided.
NOTICE
This term characterises dangers to the machine and
its proper operation.
Warning of a general danger.
The danger is specied by indications given in the
table.
This symbol characterises dangers associated with
the voltage and provides information on voltage
protection.
1.2 GENERAL POINTS
This operating and installation manual contains important instructions
to follow for the tting, operation and maintenance of the XXX control
box. Following these instructions guarantees safe operation and pre-
vents injury and property damage. It always has to be available on site
of operation of the machine/plant.
Not only the general safety instructions mentioned in this main point
on safety have to be observed, but also the special safety instructions
mentioned in the other sections.
Failure to comply with this operating and installation manual will result
in the loss of warranty rights and rights to damages.
2. TRANSPORT/DISPOSAL
2.1 TRANSPORT
For all transportation, the control panel must be switched o (see
7.
Shutdown)
ENVIRONMENTAL TRANSPORT CONDITIONS:
Parameters Value
Relative humidity 85% maxi. (no condensation)
Ambient temperature -10°C to+70°C
2.2 DISPOSAL
The device must not be disposed of as household waste
and must be disposed of at a recycling point for electrical
equipment. The device’s materials and components are re-
usable. The disposal of electrical and electronic waste, re-
cycling and recovery of any form of used appliances con-
tribute to the preservarion of our environment.
3. DESCRIPTION
3.1 APPLICATION
The Smart control box is a monitoring and control box for SFA lifting
stations. It allows the operation and parameterization of the connected
station, as well as the real time consultation of the activity and opera-
tion history.
3.2 TECHNICAL DATA OF THE CONTROL BOX
Parameter Value
Nominal supply voltage 1 ~ 220-240 V AC
Network frequency 50-60 Hz
Protection class IP 54
Power cable Type 1~ version: H07RN-F-3G 1.5 mm2
3~ version: H07RN-F-5G 2.5 mm2
Length 2.5 m
3.3 TECHNICAL DATA OF THE DETECTION DEVICE
• Analog level sensor
• Signal 0-5 V
• Input voltage 0-12 V
3.4 DIMENSIONS
Sanicubic
Sanifos
4. INSTALLATION
DANGER
Submersion of the control device.
Risk of electric shock!
Only use the control device in rooms safe from floods.
4.1 WALL MOUNTING
The Smart controm box must be installed indoors, in a place protected
from humidity and frost.
The Smart control box is supplied with a wall bracket.
• Mount the wall bracket horizontally, using the appropriate xings for
your wall.
• Snap the Smart control box onto the bracket.
4.2 CONNECTION OF THE FLOAT (SANIFOS) AND PUMP
CABLES
Cables are connected via waterproof terminal blocks.
4.2.1 Preparation of the conductive wires
Connector
Conductor PE 1~: N, L
3~: L1, L2, L3
Disassembly length y (mm) 33 25
Stripping length x (mm) 8 8
4.2.2 Connectors wiring for pumps (Sanipump)
NOTICE
It is imperative to respect the colours of the wires
when making the connections so as not to cause a mal-
function.

EN
18
Sanifos with Sanipump GR/VX Single-phase version:
: Green/Yellow wire
Position 1: Brown wire
Position 2: Blue wire
Position 3: White wire
Sanifos with Sanipump GR/VX Three-phase version:
: Green/Yellow wire
Position 1: Brown wire
Position 2: Black wire
Position 3: Grey wire
Sanifos with Sanipump SLD (single- or three-phase version):
: Green/Yellow wire
Position 1: Black wire
Position 2: Grey wire
Position 3: Brown wire
Note: The terminal blocks are already mounted on the Sanicubic pump
cables.
4.2.3 Connectors wiring for floats (Sanifos)
Follow this wiring diagram:
Connect the 2 wires to slots 1 and 2, re-
gardless of colour. It is only important to
respect these two locations.
The wiring is identical for the 3 oats.
4.2.4 Using the terminal blocks
Tightening torque: 0,5 Nm
(DIN 5264 A)
4.2.4.1 Assembling the connector
4.2.4.2 Closing the connector
Tightening torque: 1,5 – 2 Nm
4.2.4.3 Opening the connector

EN
19
4.2.5 Connection to the Smart Control Box
4.2.5.1 Connecting and locking the connector
1
4.2.5.2 Unlocking and disconnecting the connector
4.2.5.3 Location of Connector Connections
Sanifos
Pump 1: Pump 1
Pump 2: Pump 2
OFF: Low level oat
ON: High level oat
ALARM: Alarm oat
Sanicubic
Pump 1: Pump 1
Pump 2: Pump 2
PRESSOSTAT: ON/Alarm level
NOTICE
Pulling force on the cables.
Risk of tearing.
Cut the cables to the correct length.
Strip cables and wires.
Never pull or move the cables when they are connected.
Do not exert any constraints, e.g. by bending the
cable too tightly.
4.3 ELECTRICAL CONNECTION
DANGER
Electrical connection work performed by an unqua-
lied personnel.
Risk of electric shock!
The electrical connection must be carried out by a
qualied electrician.
The electrical connection must comply with the stan-
dards in force in the country of installation.
The device’s power supply must be connected to ground (class I) and
protected by a high sensitivity dierential circuit breaker (30 mA) rat-
ed at:
- 25 A for single-phase Sanicubic 2 VX, Sanifos with 2 single-phase
Sanipump SLD,
- 16 A for all other cases.
The connection must be used exclusively to provide the power to the
Smart Control Box.
4.4 CONNECTING THE WIRED EXTERNAL ALARM BOX
The cable from the external alarm box is already connected to the elec-
tronic board.
• Connect the jack to the bottom of the external alarm box.
Note: The power supply of the external alarm box is done through the
Smart box. If the jack plug is incorrectly inserted, the external alarm
box will signal a power failure (see
6.4.4 Operation).
4.5 CONNECTION TO THE BMS
Option of a remote alarm facility : dry contact (no voltage).
3 BMS are available: a BMS with NO (Normally Opened) contact, a BMS
with NC (Normally Closed) contact and a congurable NO BMS (see
6.3.3SettingsMenu
).
This contact opens (Normally Closed contact)/closes (Normally
Opened contact) as soon as the station is in alarm mode and remains
opened/closed as long as the default has not been corrected.
The terminals can be connected to a BMS (Building Management Sys-
tem) system or to a live system (max. AC 250V / 16A, DC 250V / 17A).
• Use one of the pre-holes on the side of the enclosure.
• Open the hole by tapping rmly with a screwdriver.
• Connect the connection cable directly to the circuit board using the
illustrations below:
Location of BMS
Single-phase version: Three-phase version:
Wiring diagrams
Single-phase version:
NO dry contact
NC dry contact
External alarm
2

EN
20
Three-phase version:
NO dry contact
NC dry contact
External alarm
5. COMMISSIONING
5.1 START-UP CONFIGURATION
At the rst start-up, it may be necessary to congure the box by select-
ing the connected station using the and keys:
- the installation tank: [Sani]Cubic 1, [Sani]Cubic 2, [Sani]Fos 500,
[Sani]Fos 610 or [Sani]Fos 1300,
- the type of pump: Brushless, Grinder, Vortex or Solida.
Note: In case of an error or a change in the installation, it is possible to
access this menu (see
10.1Returntothestart-upscreen
)
The operating parameters must then be selected: date, time, language
and brightness of the display.
Note: The date and time must be set correctly for alarm management,
alarm history and maintenance frequencies.
For each conguration screen,
validate the selected setting by
pressing the validation button.
On the last screen (see oppo-
site), press the conrmation
button one last time to start the
Smart box operation.
5.2 CHECKS TO BE CARRIED OUT FOR THE
COMMISSIONING OF A SANIFOS LIFTING STATION
• Set the language, date and time.
• Dene the use of the station: Individual, Collective or Commercial.
• Check that the quick connectors are correctly connected to the
Smart unit.
• Check that the led on both pumps are green.
• Check the power supply voltage on the display.
• Fill the tank with water via the connected sanitary appliances.
• Check that the pumps switch on automatically at the set water level.
• Check that the water operating intensity of the pumps, shown on the
display, is between
– 4 and 7 A with Sanipump GR, Sanipump VX (single-phase and
three-phase), Sanicubic 1, Sanicubic 2, Sanicubic 2 VX three-phase,
– 6 and 12 A with Sanicubic 1 VX single-phase, Sanicubic 2 VX sin-
gle-phase,
– 7 and 10 A with Sanipump SLD single-phase,
– 3 and 5 A with Sanipump SLD three-phase.
• Check the correct operation of the motors in forced operation.
• Check that the wired alarm box is switched on.
• Check the level of water in the tank at the end of the cycle:
–Sanicubic: the water level must be below the longest dip tube.
–Sanifos with Sanipump VX or Sanispump SLD: the water level
must be above the pump cover plate.
–Sanifos with Sanipump GR: the water level is +/- 10 cm from the
bottom of the tank.
• Set the delay time accordingly.
• Set the delay for the start of the auxiliary pump. Measure the dura-
tion of an ON-OFF cycle and enter a value equal to at least 2 times
the ON-OFF cycle value.
• Check that the data has been correctly recorded by the Smart box
(log, pumping time…).
6. OPERATION
6.1 PRESENTATION OF THE FRONT OF THE BOX
6.1.1 Key identification
Current switch
Enter Key
Back
Navigation
Activation/deactivation of the
pumps
Pump operation
indicator light
Forced operation of pumps
6.1.2 Operating lights
The light is green when the pump is activated.
The light is red when the pump is deactivated (by a manual lockout or
automatically following a fault).
6.2 USING THE CONTROL BOX
6.2.1 On screen display
6.2.1.1 Normal operation
Time
Pump current
Power output
SC_2VX
6.2.1.2 Alarm display
SC_2VX
ALARM
Alarm indicator in real time,
with identication of the
problem detected for quick
maintenance.
A special window giving the
alarm type and the alarm
time remains open for some
time.
As soon as the fault disap-
pears, return to the general
screen on which an alarm
notication appears. To re-
move the alarm notication,
simply press one of the two
forced-on buttons. Details of
the alarms can be consulted
in the alarm log.
6.2.2 Pump activation/deactivation
In the case of maintenance or replacement of a pump, it is possible to
deactivate each pump independently.
indicator light
SC_2VX
P1
P2
SFA
SC_2VX
ALARM

EN
21
6.2.3 Navigating the menu
SC_2VX
P1
P2
SFA
Pressing the “Enter” key
takes you to the main
menu:
SC_2VX
你好 Hello
Bonjour
Ciao HALLO
HO
LA
Navigation through the menus and submenus is done using the arrow
keys, Enter and Back:
Entrering the menu
or
to the previous menu
P1
P2
SFA
SC_2VX
你好 Hello
Bonjour
Ciao HALLO
HO
LA
6.3 PRESENTATION OF THE MENUS
6.3.1 Language Menu
SC_2VX
你好Hello
Bonjour
CiaoHALLO
HO
LA
Allows you to choose the
language used in the interface.
Enter the “Languages” menu by pressing the “Enter” key.
P1
P2
SFA
SC_2VX
你好Hello
Bonjour
CiaoHALLO
HO
LA
Language
English
Then press (previous language)
and (next language) to scroll
through the available languages.
• Press to conrm the
choice.
• Press to return to the
main menu.
6.3.2 Logs Menu
SC_2VX
你好Hello
Bonjour
CiaoHALLO
HO
LA
Allows:
- consult the alarm logs,
- consult the pump operation
log,
- consult the operating levels of
the level sensors,
- consult the software versions.
• Enter the “Logs” menu by pressing the “Enter” key.
• Then press and to scroll through the submenus. Conrm with
to enter the submenu.
6.3.2.1 Alarm logs
Possibility to consult the history of the last 32 alarms.
SC_2VX
Logs
alarm
Date of last alarm
Time of last alarm
SC_2VX
• Then press (previous alarm) and (next alarm) to scroll through
the alarm messages.
• Press to return to the main menu.
No modications are possible.
The oldest alarms are automatically deleted when the number of
searchable alarms is exceeded.
6.3.2.2 Pumps operation
Allows you to view the operating information of the pumps.
SC_2VX
Logs
SC_2VX
_
ump 1
ump 2
an
• Press to return to the main menu.
No modications are possible.
The resetting of the pump counter is reserved for professionals (see
8.1
Resettingthepumplog
)
6.3.2.3 Sensors operation
Allows to consult the activation height of the level sensors ON, OFF
(for Sanifos) and ALARM.
SC_2VX
Logs
Sanifos
SF_610
Sanicubic
SC_2VX

EN
22
SC_2VX
6.3.2.4 Consulting software versions and configuration
Allows you to consult:
- the tank-pump combination (Model) selected for the installation,
- the software versions for the control box’s motherboard and the
screen card. This may be necessary in case of maintenance or interven-
tion on the enclosure.
SC_2VX
Logs
SC_2VX
HW:
SW:
2.2
3.3.0
2.2
3.7.1
Logs>Version
Model: SANICUBIC 2 VX BLDC
Motherboard Screenboard
10.1Returntothestart-up
screen
to change the model.
• Press to return to the main menu.
This information cannot be changed.
6.3.3 Settings Menu
SC_2VX
你好Hello
Bonjour
CiaoHALLO
HO
LA
Allows you to:
- set the date and time,
- adjust the brightness of the
display, activate/deactivate the
audible alarm,
- set the pump delay time,
- set the delay time for the aux-
iliary pump to start,
- select the frequency of mainte-
nance,
- set the BMS parameters
6.3.3.1 Setting the date
The date setting is particularly important for alarm management and
maintenance monitoring.
SC_2VX
Settings
Date
P1
P2
SFA
SC_2VX
Settings>Date
• Then press and to select the value.
• Then press and to switch from day to month and month to
year.
• Press to conrm the choice.
• Press to return to the main menu.
6.3.3.2 Setting the hour
The hour setting is imporant for alarm management.
SC_2VX
Settings
Hour
P1
P2
SFA
SC_2VX
Settings>Hour
• Then press and to select the value.
• Then press and to switch from hour to minute and minute to
second.
• Press to conrm the choice.
• Press to return to the main menu.
6.3.3.3 Various
SC_2VX
Settings
Various
Then press and to scroll
through the submenus. Conrm
with to enter the submenu.
Brightness adjustment
Allows you to adjust the brightness of the display during use.
SC_2VX
Settings>Various
SC_2VX
Settings>Various
• Press and to select the value.
• Press to conrm the choice.
• Press to return to the main menu.
Enable/disable audible alarm
Selects whether the alarm notication (display of an alarm window) is
accompanied by an audible signal.
SC_2VX
Settings>Various
SC_2VX
Settings>Various
• Press and to choose between «Enable» or «Disable».
• Press to conrm the choice.
• Press to return to the main menu.
6.3.3.4 Setting the Stop delay time
The stop delay time is an additional pumping time when the pump’s
stop level has been reached. It allows the tank to be emptied as much
as possible and optimises the pumping of surface matter.
SC_2VX
Settings
Stop delay
SC_2VX
Settings>Stop delay
Mode: Manual
Duration: 2s
details see
10.3Learningloops
• Press and to choose between «Manual» and «Automatic».
• Press and to switch from Mode to Duration.
• Press and to choose the duration.
• Press to conrm the choice.
• Press to return to the main menu.
Note:
- If the automatic management mode has been chosen, the “Duration”
parameter cannot be modied.
- If Sanipump SLD was selected, the value is 0 s and cannot be changed.
6.3.3.5 Setting the start of the auxiliary pump
When one of the pumps is running continuously, the second pump is
activated after the time set in this menu to support the rst pump. This
activation of the auxiliary pump corresponds to an abnormal case (e.g.
a hydraulic problem on the 1st pump) and will cause the automatic de-
activation of the 1st pump.
To be relevant, the set time must be at least twice the duration of a
normal ON-OFF cycle.

EN
23
SC_2VX
Settings
P_aux start
SC_2VX
Settings>P_aux start
Activation after: 1m05s
• Then press and to select the value.
• Press to conrm the choice.
• Press to return to the main menu.
6.3.3.6 Setting the maintenance frequency
SC_2VX
Settings
Maintenance
Indicates when the next mainte-
nance is due. A reminder on the
display will appear on the sched-
uled date.
The maintenance frequencies are dierent depending on the area of
use of the station (according to EN12056-4):
- collective: 3 months;
- commercial: 6 months;
- individual: 12 months.
Changing the type of use:
SC_2VX
Settings>Maintenance
Suivante: APRIL 2021
Usage: Commercial (+6 mois)
Important: Validating a use type
for the installation resets the
maintenance counter to 0.
• Then press (previous use) and (next use) to select the intensi-
ty of use for the station.
• Press to conrm the choice.
• Press to return to the main menu.
6.3.3.7 BMS
The BMS (Building Management System) menu allows setting the con-
ditions for the congurable BMS NO (Normally Open). It is possible to
set a voltage or current condition for its operation. By default, the BMS
is set to “Disable”.
SC_2VX
BMS
Settings
P1
P2
SFA
SC_2VX
Settings>BMS
• Press to switch from «Disable» to «Enable»
• Press to conrm the choice.
SC_2VX
U< 180V
Settings>BMS
Condition:
PARAMETER
• Press and to change the setting.
• Press and to switch from Parameter to Condition then from
Condition to the value.
• Press to conrm the choice.
• Press to return to the main menu.
6.4 REMOTE WIRED ALARM BOX
6.4.1 Technical data
Audio and visual information
5 m cable length
Protection index: IP44
6.4.2 Dimensions
6.4.3 Installation
• The alarm box must be installed indoors, in a damp-free location.
• The alarm signal must always be visible to the user.
Note: It does not require an independent power supply. The power sup-
ply is provided by the Smart box. In the event of a power cut, the bat-
tery of the alarm box takes over.
6.4.4 Operation
alarm
Reset
The red general alarm LED indicates that there is an alarm in the Smart
Control Box. The alarm unit sounds as long as the fault is present. To
stop the alarm, press the reset button under the alarm unit or solve the
problem on the Smart Control Box.
The yellow «mains» LED indicates the power supply status of the alarm
unit:
– light on steady = Smart Control Box on mains supply
– ashing and buzzer = power failure on the Smart Control Box. Af-
ter 1 minute, the siren is discontinued.
The alarm box can be completely switched o by pressing and holding
the reset button (*).
6.5 SFA CONNNECT (OPTIONAL)
The SFA connect option allows, thanks to your WiFi box, to link your
Smart box to a Smartphone application. It is then possible to remotely
consult the operating information of your lifting station (power supply
check, maintenance status...) and to be informed in real time of alerts
by notication or email. Please refer to the manual delivered with SFA
Connect.
7. SHUTDOWN
The Smart control box has a battery to keep the unit powered up in
case of a power failure.
When switching o the Control Box, the power supply to the box must
be switched o as well as this battery to allow the system to be pow-
ered down. 2 possibilities exist:
• During the 30 seconds following the powering up of the unit, switch-
ing the current switch to the OFF position allows a complete shutdown.
• Press the “Back”, “P1” and “P2” keys simultaneously.
8. MAINTENANCE
8.1 RESETTING THE PUMP LOG
It may be necessary to reset a pump’s operating counters to 0, e.g. if
the pump is changed.
Press the “Enter” and “P1” (or “P2” depending on the pump) keys si-
multaneously.
The 3 parameters (number of starts, maximum pumping time and total
running time) are then reset to 0 for the pump in question.

EN
24
8.2 MAINTENANCE UPDATE
SC_2VX
The icone
Once the maintenance has been done, enter a new frequency setting (see
6.2.3Navigatingthemenu
): the
new maintenance date is set and the icon disappears.
9. FAULT FINDING
Alarm message on the dis-
play Possible cause Remedy
No AC No power supply. Check power supply.
Turn the current switch into position ON (I)
Pump P1 switched OFF Pump 1 deactivated
(activation lamp lights up red).
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Pump P2 switched OFF Pump 2 deactivated
(activation lamp lights up red).
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
No pump activated Pumps deactivated
(activation lamps light up red).
Reactivate the pumps by pressing the activation buttons.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Levels sensors fault
Clogged sensor Clean the sensor, unclog the compression chambers.
Remove deposits in the tank.
Blocked sensor Check that the oats move freely.
Remove deposits in the tank.
Incorrect wiring of the sensors. Check the wiring of the sensor terminals.
Incorrect connection of the sensors. Check the correct location of the oat connection on the casing.
Incorrect position of the oats on the rail. Check the position of the oats.
Float defective. Contact after-sales service.
P1 I=0 Amp
P2 I=0 Amp
Pump disconnected. Check pump connection.
Check the wiring of the pump terminals.
Thermal break.
Pump connection occurs automatically after a delay.
Thermal break is a symptom of a malfunction that requires a
thorough check.
Defective pump. Check the pump.
P1 hydraulic issue
P2 hydraulic issue
Problem pump cover plate.
Impeller problem. Check pump hydraulics.
Clogged pipe. Check the discharge pipe.
Shut-o valve closed Open the shut-o valve
P1 I>Imax
P2 I>Imax
Blockage of the pump. Check for foreign bodies
Motor failure Contact after-sales service.
Evacuation issue Unable to evacuate water from the
station.
Check for clogged discharge pipe.
Check that the shut-o valve is open.
Check that both pumps are working properly.
10. FOR PROFESSIONALS
10.1RETURN TO THE START-UP SCREEN
You can return to the settings made when the device was commis-
sioned by pressing the 4 arrow keys , , and .
In particular, the choice of the connected station can be changed.
10.2 EXPLANATION OF THE LEDS ON THE ELECTRONIC
BOARD
ALARM BOX
LOOP P2
CCMOS
CONNECT COM
IOT CABLE ONLY
BMS2 RM BMS1 NC BMS1 NO
FLOOD SENSOR
N / C / L
N / C / L
LOOP P1
AC POWER
SCREENBOARD
N / L
CLR CMOS
OFF/ALARM/ON
BMS2
BMS1 NO
BMS1 NC
Green LED
Pumps
Red LED
BMS
Blue LED
Sensors
Note: The pho-
tograph below
is used as an
example. In-
deed, the lo-
cation of the
LEDs may vary
but the col-
ours and their
indications are
identical to
all electronic
boards.
NOTICE
If the enclosure has been opened, take care not to
pinch or pull the cable when refitting the front panel.
10.3 LEARNING LOOPS
The management of the delay time in “Automatic” mode is not ad-
justable. It is calculated using a learning loop that averages the last 5
switch-ons.
An increasing delay time is the symptom of a drop in output ow and
may therefore indicate a fault in the discharge installation (clogging, etc.).
11. GUARANTEE
Smart Control Box is guaranteed for 2 years for parts and labour, sub-
ject to correct installation, use and maintenance of the unit.

77
Sanicubic 3~ (400 V)

78
• Brown, Marron, Braun, Marrón, Marrone, Castanho, Bruin, Hnědá, Brun, Ruskea, Brązowy, Maro, Коричневый, Brun, 棕色
• Red, Rouge, Rot, Rojo, Rosso, Vermelho, Rood, Červená, Rød, Punainen, Czerwony, Roșu, Красный, Röd, 红色
• Green/Yellow, Vert/Jaune, Grün/Gelb, Verde/Amarillo, Verde/Giallo, Verde/Amarelo, Groen/Geel, Zelená/Žlutá, Grøn/Gul, Vihreä/Keltainen, Zielona/
Żółty, Verde/Galben, Зеленый/Желтый, Grön/Gul, 绿色/黄色
• Blue, Bleu, Blau, Azul, Blu, Azul, Blauw, Modrá, Blå, Sininen, Niebieski, Albastru, Голубой, Blå, 蓝色
• White, Blanc, Weiß, Blanco, Bianco, Branco, Wit, Bílá, Hvid, Valkoinen, Biała, Alb, Белый, Vit, 白
• Black, Noir, Schwarz, Negro, Nero, Preto, Zwart, Černá, Sort, Musta, Czarny, Negru, Черный, Svart, 黑色
Sanifos 3~ (400 V)

Table of contents
Other SFA Control Unit manuals
Popular Control Unit manuals by other brands

EOS
EOS ECON H2 Assembly and operating instructions

Homematic IP
Homematic IP HmIP-MOD-TM quick start guide

Belden
Belden lumberg automation LioN-P 0980 ESL 300... manual

TREND
TREND 3RM/24VAC Installation Instructions-Mounting

VAT
VAT 61228-KAGG-0002 Installation, operating, & maintenance instructions

Sentiotec
Sentiotec Pro-C2 Instructions for installation and use

PARCOL
PARCOL 1-6940 Series instruction manual

Zennio
Zennio MINiBOX 0-10V X3 Technical documentation

Festo
Festo HEL Series Installation and maintenance sheet

Eaton
Eaton Cutler-Hammer Durant PRESIDENT Series Installation and operation manual

Comelit
Comelit Simplebus1 UT1010 Technical manual

ICP DAS USA
ICP DAS USA tSG-3781B user manual