Siemens SIMATIC RF1070R User manual

Table of contents
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
2
©Siemens AG 2020 All rights reserved
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement –and continuously maintain –a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.

Table of contents
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
3
©Siemens AG 2020 All rights reserved
Table of contents
Legal information......................................................................................................... 2
1Introduction........................................................................................................ 4
1.1 Overview............................................................................................... 4
1.2 Principle of operation............................................................................ 5
1.3 Components used ................................................................................ 6
2Engineering of the STEP 7 Program................................................................ 7
2.1 Overview............................................................................................... 7
2.2 Function block "ReadUID".................................................................... 9
2.3 The "RFData" global data block......................................................... 16
2.4 Configuring the CM1241 RS232 communication module.................. 17
2.5 Diagnostics and error messages........................................................ 18
3Installation and commissioning..................................................................... 20
3.1 Hardware configuration...................................................................... 20
3.3 Loading the S7-1200 configuration .................................................... 22
4Operation.......................................................................................................... 23
5Useful information........................................................................................... 26
5.1 Programming via the RS232 interface ............................................... 26
5.1.1 Introduction......................................................................................... 26
5.1.2 Connecting via the CM1241 RS232 communication module............. 26
5.1.3 System jobs........................................................................................ 27
5.2 Project engineering of the S7 station with the CM1241 RS232
communication module ...................................................................... 31
6Appendix .......................................................................................................... 33
6.1 Service and support ........................................................................... 33
6.2 Links and literature............................................................................. 34
6.3 Change documentation...................................................................... 34

1 Introduction
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
4
©Siemens AG 2020 All rights reserved
1 Introduction
1.1 Overview
Starting point
Companies have been using RFID-based identification card systems for many
years to control access to buildings. The growing need for security and increasing
requirements for documentation call for solutions that can control access to
machines and equipment on a user-specific basis. The SIMATIC
RF1040R/RF1070R readers provide the option of using employee identification
cards even when operating machines. This allows finely graded access concepts to
be implemented or user-specific instructions to be stored - all with one card.
Requirement
A reader at the entrance to a company's factory must read the serial number (UID)
of a card and transmit to a SIMATIC S7 station via the communication interface of
the automation system. You can then use this UID to implement conditions for
access authorization or sharing on a machine in the S7 program.
The following figure provides an overview of the automation task.
Figure 1-1
SIMATIC
PLC Communication
interface RS232
Automation system
RFID
reader
Use case
•Use of a compact controller from the S7-1200 series
•Transmit the UID from the SIMATIC RF1070R reader to the
SIMATIC S7 CPU via the CM1241 RS232 communication module.
Solution approach
The RF1070R reader can be linked to a SIMATIC S7-1200 CPU using the CM1241
RS232 communication module. With this link, communication happens over the
Freeport protocol. The Freeport protocol offers the ability to communicate directly
with the reader.
Note
The RF1040R/RF1070R reader has two interfaces:
•USB
•RS232 serial interface
Only the RS232 serial interface is required for this application example. The USB
interface can be ignored.

1 Introduction
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
5
©Siemens AG 2020 All rights reserved
Note
Another application example for linking the
SIMATIC RF1040R/RF1070R reader to an S7-1500 station via the RF170C
communication module can be found in the Siemens Industry Online Support
(SIOS) under \4\.
1.2 Principle of operation
Diagram
The following figure schematically illustrates the most important components of the
solution:
Figure 1-2
SIMATICPLC
RFID System
SIMATICRF1070R
Serial coupling/ RS232
SIMATICS7-1200
CM1241RS232
Card with
UID
Implemented functions
The following functions are implemented in the application example:
•Parameter assignment for the point-to-point connection of the communication
module CM1241 RS232.
•Reset SIMATIC RF1070R reader.
•Monitor the antenna field of the RF1070R reader and select the card located
there.
•Receive the UID from the SIMATIC RF1070R reader from the CM1241 RS232
communication module and store it in a data block.
Advantages of this solution
•Save time and money when commissioning your own automation solution.
•Reusable STEP 7 code. This can be easily adapted for extensions.
Note
This application example can also serve as a basis for controlling a SIMATIC
RF1040R/RF1070R reader centrally on an S7-1500 CPU via the CM PtP RS232
BA; or decentralized via an ET 200SP CM PtP.

1 Introduction
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
6
©Siemens AG 2020 All rights reserved
1.3 Components used
This application example was created with these hardware and software
components:
Table 1-1
Components
Quanti
ty
Item number
Note
Power supply
PM1207
1
6EP1332-1SH71
24 Volt for S7-1200
CPU 1214C
DC/DC/DC
1
6ES7214-1AG40-0XB0
A different S7-1200
CPU from the
SIMATIC product
range can also be
used as an
alternative.
Communication module
CM1241 RS232
1
6ES7241-1AH32-0XB0
Version 2.1 onward
SIMATIC RF1070R reader
1
6GT2831-6BA50
Alternatively, a
SIMATIC RF1040R
reader can also be
used
(6GT2831-6CA50).
RF1000 connection cable
with open ends for
communication via the
RS232 port
1
6GT2891-2UH30
-
LOGO!POWER/1AC/
DC5V/3A
1
6EP3310-6SB00-0AY0
5 Volt for RF1070R
STEP 7 V16 Professional
1
6ES7822-1AA06-0YA5
-
Note
This description also applies to the STEP 7 V15.1 project that you can find on
the same Siemens Industry Online Support page, \2\.
This Application Example consists of the following components:
Table 1-2
Components
File name
Note
Project
"109780625_RF1070R_CM1241_Read
UID_PROJ_V16_V10.zip"
This zipped file contains the
V16 project.
Documentation
"109780625_RF1070R_CM1241_Read
UID_DOCU_V10.pdf"
This description also applies
to the STEP 7 V15.1 project.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
7
©Siemens AG 2020 All rights reserved
2 Engineering of the STEP 7 Program
2.1 Overview
Introduction
The STEP 7 V16 project contains
•the user program for the S7 CPU with the "ReadUID" function block
•the configuration and project engineering of the CM1241 RS232 "Port_Config"
communication module
Note
In this application example, parameters are assigned for the basic interface
parameters of the CM1241 RS232 dynamically via the user program.
Calling "Port_Config" overwrites the settings of the hardware configuration.
Diagram
The following graphic shows the program structure of the whole STEP 7 V16
project.
Figure 2-1
RFData
ReadUID
FB1
•Port_Config
•Send_P2P
•Receive_P2P
•rfData
•Interface
•diagnostics
Main
OB1
Global
Program blocks
The user program for the SIMATIC S7-1200 CPU consists of the following
elements:
Table 2-1
Element
Symbolic name
Description
OB1
Main
In OB1, the "ReadUID" function block, including
the associated instance data block, is called
cyclically.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
8
©Siemens AG 2020 All rights reserved
Element
Symbolic name
Description
FB1
"ReadUID"
The function block "ReadUID" contains:
•the configuration of the CM1241 RS232
communication module
•the initialization of the RF1070R reader
•reading and analysis of the card serial
number (UID).
DB1
"InstReadUID"
Instance data block of the "ReadUID" function
block
DB4
"RFData"
Global data block for the storage of
•the most recently read UID
•the status of the "ReadUID" function block
point-to-point
instructions
"Port_Config"
The "Port_Config" instruction (port
configuration)
•dynamically parameterizes basic interface
parameters of the
CM1241 RS232 via the user program
•is called in the "ReadUID" function block.
"Send_P2P"
The instruction "Send_P2P" (send point-to-point
data)
•Sends data to the RF1070R reader
•is called in the "ReadUID" function block.
"Receive_P2P"
The instruction "Receive_P2P" (receive point-to-
point data)
•receives data from the RF1070R reader
•is called in the "ReadUID" function block.
Data type
"typeRFData"
Data type for addressing the configured
CM1241 RS232 communication module.
Data type
"typeDiagnostics"
Data type for saving the error messages that
occur in the "ReadUID" function block:
•status:
Last status code of the interface parameter
"status" of the FB.
•subfunctionStatus:
Status or returned value from internal
instructions or FBs where an error
occurred.
For detailed information, refer to the Online
Help for the instruction in question, or the
documentation of the FB.
•stateNumber:
State of the FB's state machine in which the
error occurred.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
9
©Siemens AG 2020 All rights reserved
2.2 Function block "ReadUID"
The "ReadUID" function block contains all functionality for communicating with the
RF1070R reader.
The "ReadUID" function block is a custom development for this application
example and is already integrated in the STEP 7 project so that you can adapt it to
your requirements. It is called cyclically in OB1 and automatically automatically
calls the point-to-point instructions "Port_Config", "Send_P2P" and "Receive_P2P".
Function
Function block "ReadUID" realizes
•the configuration of the CM1241 RS232 communication module
•the initialization of the RF1070R reader
•monitoring of the RF1070R reader's antenna field
•selection of the card located in the antenna field
•receipt and analysis of the UID
•output of status and error messages from the block.
This functionality is implemented as a simple sequencer with the following states:

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
10
©Siemens AG 2020 All rights reserved
Figure 2-2
Daten-
Ablage
1:
FB_STATE_POR
T_CONFIG
trigger “reset“ positive edge
2:
FB_STATE_RES
ET_READER
0:
FB_STATE_NO_
PROCESSING
3:
FB_STATE_RES
ET_WAIT
4:
FB_STATE_SET_
LED
5:
FB_STATE_SET_
LED_WAIT
14:
FB_STATE_RES
ET_LED_WAIT
6:
FB_STATE_SELE
CT_CARD
13:
FB_STATE_RESE
T_LED
7:
FB_STATE_SELE
CT_CARD_WAIT
8:
FB_STATE_REA
D_UID
9:
FB_STATE_REA
D_UID_WAIT
12:
FB_STATE_
DISABLING
trigger “enable“ positive edge & Reset done
trigger “enable“ negative edge
RESET:
ENABLING:
DISABLING:
Waiting for
response
telegram
Waiting for
response
telegram
Waiting for
response
telegram
Waiting for
response
telegram
Waiting for
response
telegram

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
11
©Siemens AG 2020 All rights reserved
Table 2-2
State
Description
RESET
0
FB_STATE_NO_PROCESSING
Idle process:
Process is doing nothing.
1
FB_STATE_PORT_CONFIG
Call of the point-to-point instruction
"Port_Config":
The point-to-point instruction
"Port_Config" dynamically parameterizes
basic interface parameters of the
CM1241 RS232 via the user program
(see Chapter 2.4).
2
FB_STATE_RESET_READER
Reset SIMATIC RF1070C reader.
•Call of the point-to-point instruction
"Send_P2P".
•The request telegram
"syscmd_reset" is sent to the reader.
3
FB_STATE_RESET_WAIT
•Waiting for response telegram.
•Call of the point-to-point instruction
"Receive_P2P".
•Evaluation of the response telegram:
•The LED of the reader is off.
Back to state 0.
ENABLING
4
FB_STATE_SET_LED
Set the LED of the SIMATIC RF1070C
reader to green:
•Call of the point-to-point instruction
"Send_P2P".
•The request telegram
"syscmd_set_port" is sent to the
reader.
5
FB_STATE_SET_LED_WAIT
•Waiting for response telegram.
•Call of the point-to-point instruction
"Receive_P2P".
•Evaluation of the response telegram:
•The LED of the reader is green.
6
FB_STATE_SELECT_CARD
Select a card located in the antenna field
of the reader.
•Call of the point-to-point instruction
"Send_P2P".
•The request telegram "vhl_select" is
sent to the reader.
7
FB_STATE_SELECT_CARD_WAIT
•Waiting for response telegram.
•Call of the point-to-point instruction
"Receive_P2P".
•Evaluation of the response telegram:

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
12
©Siemens AG 2020 All rights reserved
8
FB_STATE_READ_UID
Request the serial number (UID) of the
card in the reader's antenna field:
•Call of the point-to-point instruction
"Send_P2P".
•The request telegram "vhl_get_snr"
is sent to the reader.
9
FB_STATE_READ_UID_WAIT
•Waiting for response telegram.
•Call of the point-to-point instruction
"Receive_P2P".
•Copy the UID of the card from the
response telegram into the tag
"RFData.rfData.uid".
Back to state 5.
DISABLING
12
FB_STATE_DISABLING
Disable the function block "ReadUID"
13
FB_STATE_RESET_LED
Set the SIMATIC RF1070C reader LED
to red:
•Call of the point-to-point instruction
"Send_P2P".
•The request telegram
"syscmd_set_port" is sent to the
reader.
14
FB_STATE_RESET_LED_WAIT
•Waiting for response telegram.
•Call of the point-to-point instruction
"Receive_P2P".
•Evaluation of the response telegram:
•The LED of the reader is red.
Back to state 0.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
13
©Siemens AG 2020 All rights reserved
Parameter
The figure and table below show the call interface of the function block "ReadUID".
Figure 2-3
Table 2-3
Icon
Data type
Description
EN
BOOL
Enable input. Only relevant in FDP and LAD
representation
reset
BOOL
Starts the parameterization of the CM1241 RS232
communication module and the resetting of the
SIMATIC RF1070R reader.
enable
BOOL
Starts the read job.
•As long as "enable" remains set, the job handling
is active and new UIDs can be continuously read
and processed.
•The job is ended when the "enable" parameter is
reset.
Note:
Before enable is set the first time, a "reset" must
occur.
rfData
typeRFData
•For addressing the configured CM1241 RS232
communication module.
•Reference to global memory range for receive
data.
ENO
BOOL
Enable output. Only relevant in FDP and LAD
representation
ndr
BOOL
•New UID has been read and stored in the
"rfData" memory range.
•Only TRUE for one cycle.
valid
BOOL
•Is set as long as valid output values are available
and the "enable" input is set.
•Reset as soon as an error is pending or the
"enable" input is reset.
busy
BOOL
•The "ReadUID" function block is active.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
14
©Siemens AG 2020 All rights reserved
Icon
Data type
Description
•If "enable" is reset or an error occurs, "busy" is
reset.
error
BOOL
•Is set if the function block "ReadUID" finished
with errors.
•The error must be remedied by the user.
•If "enable" is reset, then "error" is also reset.
status
WORD
•Status of the instruction
•Error information ("error"=true)
diagnostics
typeDiagnostics
Error message that appears in the "ReadUID"
function block:
•status:
Last status code of the interface parameter
"status" of the FB.
•subfunctionStatus:
Status or returned value from internal instructions
or FBs where an error occurred.
For detailed information, refer to the Online Help
for the instruction in question, or the
documentation of the FB.
•stateNumber:
State of the FB's state machine in which the error
occurred.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
15
©Siemens AG 2020 All rights reserved
Signal flow chart
The following figure shows the signal flow chart for the "ReadUID" function block.
Figure 2-4
enable
valid
busy
error
1a) 1b)
3)
4)
2) 2)
reset
ndr 3)
4)
5) 5)
1. With "reset" as "TRUE", "busy" is set and "error" and "valid" are reset.
a. After successfully resetting the reader and when enable is FALSE, "busy"
is reset.
b. After successfully resetting the reader and when "enable" is TRUE, "busy"
and "valid" are set again. Job handling is active again and new data can be
continuously read and processed.
2. With "enable" to TRUE, "busy" and "valid" are set. Job handling is active and
new UIDs can be continuously read and processed.
3. New UID has been read and stored in the "rfData" memory range.
4. With "error" as TRUE, "busy" and "valid" are reset and all functions of the
"ReadUID" function block are stopped.
5. The pending error, which must be remedied by the user, can only be cleared
with a falling edge at "enable".

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
16
©Siemens AG 2020 All rights reserved
2.3 The "RFData" global data block
The DB "RFData" contains:
1. The PLC data type "typeRFData":
the input/output parameter "rfData" of the "ReadUID" function block is used for
addressing the configured CM1241 RS232 communication module and saving
the read UID. This parameter needs the PLC data type "typeRFData" as data
type:
–port:
Specifies the communication module used for communication.
"HW identifier" from the device configuration.
–cardType:
Card type of the card in the antenna field.
–uid:
Serial number of the card in the antenna field.
2. the "interface" PLC tags for calling the function block "ReadUID" in OB1,
3. the PLC data type "typeDiagnostics"
the "diagnostics" output parameter of the "ReadUID" function block helps save
error information and requires as a data type the
PLC data type "typeDiagnostics":
–status:
Last status code of the interface parameter "status" of the FB.
–subfunctionStatus:
Status or returned value from internal instructions or FBs where an error
occurred.
For detailed information, refer to the Online Help for the instruction in
question, or the documentation of the FB.
–stateNumber:
State of the FB's state machine in which the error occurred.
Figure 2-5
1
2
3

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
17
©Siemens AG 2020 All rights reserved
2.4 Configuring the CM1241 RS232 communication
module
The SIMATIC RF1070R reader can be connected to a SIMATIC controller with the
help of the CM1241 RS232 communication module and P2P communication
("Send_P2P" and "Receive_P2P").
The communication parameters of the RS232 interface of the SIMATIC RF1070R
reader are set as follows in the factory:
•Transmission speed: 115.2 kbps
•Parity: None
•Data bits: 8
•Stop bits: 1
•Flow control: None.
When connecting the SIMATIC RF1070R reader via the CM1241 RS232, the
communication parameters of the CM must match the communication parameters
of the RF1070R reader.
In this application example, parameters are assigned for the basic interface
parameters of the CM1241 RS232 dynamically via the user program by calling the
point-to-point instruction "Port_Config".
The following figure shows the parameterization of the basic interface parameters
of the CM1241 RS232:
Figure 2-6
•Transfer speed (BAUD)
16#b= 115.2 kbps
•Parity (PARITY):
16#01= none
•Data bits (DATABITS):
16#01= 8 data bits
•Stop bits (STOPBITS):
16#01= 1 stop bit
•Flow control (FLOWCTRL):
16#01= none.
Note
Calling "Port_Config" overwrites the settings of the hardware configuration.

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
18
©Siemens AG 2020 All rights reserved
2.5 Diagnostics and error messages
The "ReadUID" function block provides the status of the instruction via the output
parameter "status" and, in the case of an error, various error messages via the
"status" and "diagnostics" output parameters.
Status of the instruction
The following table provides an overview of the instruction status.
Table 2-4
"status"/
"diagnostics.status"
Meaning
16#8400
Reader error. No card has been selected.
16#8601
"Port_Config" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).
16#8602
"Send_P2P" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).
16#8603
"Receive_P2P" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).
"status"
Meaning
16#7000
No job processing active.
16#7001
Initial call when job is started.
16#7002
Second call when job is started.
16#7004
Monitoring of the antenna field of the RF1070R reader.
16#7006
New UID has just been read.
16#0001
The parameterization of the CM1241 RS232 communication
module and resetting of the SIMATIC RF1070R reader have
been completed successfully.
Error messages
The following table provides an overview of the error messages from the
"ReadUID" function block.
Table 2-5
"status"/
"diagnostics.status"
Meaning
16#8400
Reader error. No card has been selected.
16#8601
"Port_Config" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).
16#8602
"Send_P2P" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).
16#8603
"Receive_P2P" error
The status or returned value from the internal instruction can be
found in the tag "diagnostics.subfunctionStatus" (Table 2.6).

2 Engineering of the STEP 7 Program
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
19
©Siemens AG 2020 All rights reserved
The following table shows the error messages that occurred in the internal point-to-
point instructions "Port_Config", "Send_P2P" and "Receive_P2P".
Table 2-6
"diagnostics.subfunctionStatus"
Point-to-point instruction
16#80xx
Error messages that occurred in the internal point-
to-point instructions "Port_Config", "Send_P2P"
and "Receive_P2P".
Note:
For detailed information, refer to the Online Help
for the instruction in question.
16#81xx
16#82xx
16#83xx
16#89xx
16#8Axx

3 Installation and commissioning
Reading out UID with SIMATIC RF1070R
Article ID: 109780625, V1.0, 09/2020
20
©Siemens AG 2020 All rights reserved
3 Installation and commissioning
3.1 Hardware configuration
Section 1.3 lists the required hardware components.
CAUTION
Please observe the setup guidelines for the S7-1200 and SIMATIC
RF1070R. Refer to the corresponding device manuals \5\ and \3\.
CAUTION
Only switch on the power supply after you have completed and checked
the assembly!
The following graphic shows the hardware setup of the application.
Figure 3-1
Engineering station
CM1241 RS232 SIMATIC S7-1200 CPUCard with UID SIMATIC RF1070R
serial coupling / RS232
PROFINET IE
STEP 7 V16
The following table provides an overview of all IP addresses used in this example.
Assignment of static IP addresses is assumed.
Table 3-1
Components
IP address
Description
CPU 1214C DC/DC/DC
192.168.0.1
S7-1200 CPU
Engineering Station
192.168.0.10
STEP 7 V16
The subnet mask in all network components is 255.255.255.0.
Table of contents
Other Siemens Card Reader manuals

Siemens
Siemens PM500-Cotag User manual

Siemens
Siemens AR6111-MX User manual

Siemens
Siemens SIMATIC RF650M User manual

Siemens
Siemens SIMATIC MV440 User manual

Siemens
Siemens RB500 User manual

Siemens
Siemens AR10S-MF Installation instructions manual

Siemens
Siemens 6FL7171-8AD User manual

Siemens
Siemens AR50M-MF User manual

Siemens
Siemens AR4 S-MF Series Installation instructions manual

Siemens
Siemens Bewator PR500 Installation and operation manual